GARDASOFT RC1 Series User manual

RC1xx LED Lighting Controllers - User Manual
RC100/120 LED
Lighting Controllers
Issue 007
User manual
www.gardasoft.com

RC1xx LED Lighting Controllers - User Manual
Copyright and disclaimer notice
Except as prohibited by law:
All hardware, software and documentation is provided on an ‘as is’ basis. This
information is for guidance only. Installers must perform their own risk assessment
specic to each installation.
It is essential that the users ensure that the operation of the product is suitable for
their application.
The users must ensure that incorrect functioning of this equipment cannot cause
any dangerous situation or signicant nancial loss to occur.
Deliberate acts of endangerment and vandalism are not covered by this document
and must be considered by the installer.
While care has been taken in the preparation of this document Gardasoft Vision
Ltd will not accept any liability for consequential loss of any kind except those
required by law.
All trademarks acknowledged. This document is Copyright - 2021 Gardasoft Vision
Ltd.
EC conformity declaration
The EC Certicate of Conformity is available from Gardasoft Vision Ltd on request
Issue status of this document: Issue 0067 (September 2021)

RC1xx LED Lighting Controllers - User Manual
Contents
1 Getting started 5
1.1 RC1xx features - a summary 5
2 Safety precautions 5
2.1 Heat 6
2.2 Electrical 6
2.3 General 6
2.4 Installation guidance (disclaimer) 6
3 Sicherheitsvorkehrungen 6
3.1 Hitze 7
3.2 Elektrik 7
3.3 Allgemeines 7
3.4 Haftungsausschluss 8
4 Mesures de sécurité 8
4.1 Chaleur 8
4.2 Électricité 8
4.3 Général 9
4.4 Clause de non-responsabilité 9
5 Mounting the RC1xx 9
5.1 Environmental considerations 9
6 Connecting the RC1xx 10
6.1 Power 10
6.2 Lighting output 10
6.3 Trigger input 11
6.4 Ethernet 12
6.5 Connectors (general) 12
7 General description 12
7.1 Pulse and duty cycle limits 12
7.2 Triggering 13
7.2.1 Trigger input options 14
7.2.2 Internal trigger 15
7.3 SafeSense 15
7.4 SafePower 15
7.5 Light characterisation 15
7.6 Current adjust 16
7.7 Flags 16
7.8 Fault detection 17
7.9 Factory settings 17

RC1xx LED Lighting Controllers - User Manual
8 Ethernet address (RC120) 17
8.1 IP address 18
8.1.1 DHCP 18
8.1.2 Fixed IP address 19
8.2 Automatic sensing 19
9 Webpageconguration(RC120) 20
9.1 Main page 20
9.2 Conguration page 20
9.3 General setup page 21
10 Congurationcommands 22
10.1 Lighting setup 22
10.2 Front panel commands 22
10.2.1 Startup 22
10.2.2 Setting the light rating 24
10.2.3 Setting up continuous output 24
10.2.4 Setting up switched output 25
10.2.5 Setting up pulsed operation 25
10.2.6 Setting time periods 26
10.2.7 Setting the internal trigger timer 27
10.2.8 Using the key lock 28
10.2.9 Viewing the trigger status 29
10.2.10 Viewing the output current 29
10.3 Ethernet commands (RC120) 30
10.3.1 Ethernet communication 30
10.3.2 Command structure 30
10.3.3 General commands 31
10.3.4 Lighting commands 35
10.4 Command summary 36
11 RC1xx reference information 37
11.1 Specications and ratings 37
11.2 Restrictions 38
11.2.1 Continuous mode 38
11.2.2 Switched mode 38
11.2.3 Pulse mode 38
11.3 Event codes 39
11.4 Error codes 40

RC1xx LED Lighting Controllers - User Manual
—5 —
1 Getting started
Before you use this product, make sure that you have read and
understood Section 2, “Safety precautions” (oder Abschnitt 3,
“Sicherheitsvorkehrungen”, ou Section 4, “Mesures de sécurité”) and
Section 11, “RC1xx reference information”, and that you have checked the
RC1xx fulls your requirements.
Mount the RC1xx (see Section 5, “Mounting the RC1xx”) and connect it up
as required (see Section 6, “Connecting the RC1xx”).
Set up the RC1xx for the desired operation as described in Section 10,
“Conguration commands”, or Section 10.2, “Front panel commands”.
We recommend that you visit www.gardasoft.com for application notes on
this range of products.
There is also a support web page there, which has information on trouble-
shooting problems.
1.1 RC1xx features - a summary
The RC1xx product is a single channel LED lighting controller for use in
machine vision applications. It can deliver 1A for the RC100 and 2A for the
RC120 in pulse mode.
The RC120 has Ethernet connectivity and may be controlled through its
own web pages .
The RC1xx has SafeSense™ which allows the controller to automatically
sense the characteristics of your lights. The RC1xx also has SafePower™
which ensures low heat dissipation and the ability to deliver higher
currents with no need for heat sinking.
2 Safety precautions
Read this before using the RC1xx. Always observe the following safety
precautions. If in doubt, contact Gardasoft Vision Ltd. The following
symbols are used in this guide:
Warning: Read the instructions to understand the possible
hazards.
Warning: Surface may get hot.
Warning: Possible hazardous voltage.
Where these symbols appear in the manual, refer to the text for the
precautions to be taken.

RC1xx LED Lighting Controllers - User Manual
—6 —
2.1 Heat
Ensure the RC1xx is mounted correctly (see Section 5, “Mounting the
RC1xx”), and that you do not exceed any of the ratings for the unit (see
Section 11.1, “Specications and ratings”).
At its maximum ratings, the RC1xx’s enclosure can exceed 65°C which is
sucient to cause a burn if touched. Place in a position where personnel
cannot accidentally touch it and ensure there is a free ow of air around
the unit.
2.2 Electrical
The RC1xx produces high energy pulses. Take care to connect the outputs
correctly and protect the output wiring and load from any short-circuits.
When switched o, energy remains stored in the RC1xx for about 15
seconds.
The RC1xx does not have complete tracking isolation of input and output.
Transients caused by inductive loads must be suppressed externally to the
RC1xx.
Warning: This is a Class A product. Its use in residential areas may
cause radio interference, and such use should be avoided unless special
measures are taken by the user to restrict emissions to a level that allows
the reception of broadcast transmissions.
2.3 General
The RC1xx must not be used in an application where its failure could be a
danger to personal health or damage to other equipment.
If the equipment is used in a manner not specied by the manufacturer,
the protection provided by the equipment may be impaired.
2.4 Installation guidance (disclaimer)
This information is for guidance only. Installers must perform their own
risk assessment specic to each installation. While Gardasoft Vision Ltd
has taken every care in the preparation of this advice, Gardasoft Vision Ltd
accepts no liability for damages of any kind except those required by law.
Deliberate acts of endangerment and vandalism are not covered by this
document and must be considered by the installer.
3 Sicherheitsvorkehrungen
Bitte lesen Sie dieses Dokument, bevor Sie die RC1xx verwenden. Beachten
Sie immer die folgenden Sicherheitshinweise. Bei Fragen wenden Sie sich
an Gardasoft Vision Ltd. Die folgenden Symbole werden in dieser Anleitung
verwendet:

RC1xx LED Lighting Controllers - User Manual
—7 —
Warnung: Lesen Sie die Hinweise, um eine mögliche Gefahr
zu verstehen.
Warnung: Oberäche kann heiß werden.
Warnung:Mögliche gefährliche Spannung.
Wenn diese Symbole in dieser Anleitung erscheinen, nden Sie im
beistehenden Text die zu ergreifenden Vorsichtsmaßnahmen.
3.1 Hitze
Stellen Sie sicher, dass die RC1xx ordnungsgemäß montiert wurde (siehe
Abschnitt 5, “Mounting the RC1xx”) und dass Sie keinen der Werte für diese
Einheit überschreiten (siehe Abschnnitt 11.1, “Specications and ratings”).
Bei ihren Maximalwerten kann das Gehäuse der RC1xx mehr als 65°C
erreichen und folglich bei Berührung Verbrennungen verursachen.
Positionieren Sie sie an einem Ort, an dem sie nicht aus Versehen von
Personal berührt werden und an dem die Luft um die Einheit zirkulieren
kann.
3.2 Elektrik
Die RC1xx produziert energiereiche Pulse. Achten Sie darauf, die Ausgänge
korrekt anzuschließen und die Ausgangsverdrahtung und die Verbraucher
vor Kurzschlüssen zu schützen. Nach dem Ausschalten wird die Energie
noch etwa 15 Sekunden lang in der RC1xx gespeichert.
Die RC1xx verfügt über keine vollständige Nachlauf-Isolierung des Einund
Ausgangs.
Spannungsspitzen am RC1xx aufgrund von induktiven Ladungen müssen
extern unterdrückt werden.
Warnung: Dies ist ein Produkt der Klasse A. Es kann bei Benutzung im
Wohnbereich Funkstörungen verursachen. Aus diesem Grund wird
von einer derartigen Nutzung abgeraten, sofern vom Benutzer keine
besonderen Maßnahmen ergrien wurden, um die Emissionen auf ein
Niveau zu begrenzen, das den Empfang von Rundfunksendungen erlaubt.
3.3 Allgemeines
Die RC1xx darf nicht in Bereichen verwendet werden, in denen bei Ausfall
eine Gefahr von Personen- oder Sachschäden besteht. Wenn das Gerät
nicht entsprechend den Herstellerangaben eingesetzt wird, kann der durch
das Gerät bereitgestellte Schutz beeinträchtigt werden.

RC1xx LED Lighting Controllers - User Manual
—8 —
3.4 Haftungsausschluss
Diese Angaben dienen lediglich der Orientierung. Der Monteur muss für
jede Installation eine eigene spezische Risikobewertung durchführen.
Gardasoft Vision hat bei der Zusammenstellung dieser Empfehlungen
größtmögliche Sorgfalt walten lassen. Gardasoft Vision übernimmt über
das gesetzlich erforderliche Maß hinaus keine Haftung für Schäden aller
Art.
Vorsätzliche Gefährdungen und Vandalismus werden von diesem
Dokument nicht abgedeckt und sind vom Monteur zu berücksichtigen.
4 Mesures de sécurité
Veuillez lire la notice avant d’utiliser le RC1xx. Respectez toujours les
mesures de sécurité qui suivent. En cas de doute, contactez Gardasoft
Vision Ltd. Les symboles suivants sont utilisés dans ce manuel:
Attention: Lisez les instructions pour comprendre quels sont
les risques éventuels.
Attention: La surface peut devenir chaude.
Attention:Risque d’électrocution.
Veuillez vous référer aux consignes du manuel pour connaître les
précautions à suivre au regard de ces symboles.
4.1 Chaleur
Assurez-vous que le RC1xx est monté correctement (voir Section 5,
“Mounting the RC1xx”) et que vous ne dépassez pas les charges pour l’unité
(voir Section 11.1, “Specications and ratings”).
À ces charges maximales, le boitier du RC1xx peuvent dépasser 65 °C, ce
qui est susant pour occasionner des brûlures en cas de contact. Assurez-
vous que le personnel ne peut pas y toucher accidentellement et que l’air
circule autour de l’unité.
4.2 Électricité
Le RC1xx produit de fortes pulsations énergétiques. Assurez-vous que les
sorties sont bien connectées et que les ls de sortie et les charges sont
bien à l’abri d’éventuels courts circuits. Une fois l’appareil éteint, l’énergie
résiduelle reste stockée dans le RC1xx pendant environ 15 secondes.
Le RC1xx ne dispose pas de système complet d’isolation des entrées et
sorties.
Les transitoires causés par les charges inductives doivent être supprimés à
l’extérieur du RC1xx.

RC1xx LED Lighting Controllers - User Manual
—9 —
Attention : Ce produit est de catégorie A. Son utilisation en zone
résidentielle peut causer des interférences radio, et devra alors être
évitée sauf si des mesures spéciales ont été prises par l’utilisateur pour
restreindre les émissions à un niveau permettant la réception des
transmissions radiodiusées.
4.3 Général
Le RC1xx ne doit pas être utilisé dans une situation où toute panne
de celui-ci mettrait en danger la santé des personnes ou risquerait
d’endommager d’autres équipements.
Si l’appareil est utilisé d’une manière diérente de celle recommandée par
le fabricant, la protection oerte par l’appareil pourra en être altérée.
4.4 Clause de non-responsabilité
Ces informations sont seulement à titre indicatif. Les installateurs doivent
établir leur propre évaluation de risques pour chaque installation. Gardsoft
Vision a préparé minutieusement ces conseils, mais Gardasoft Vision
déclinent toute responsabilité concernant les dommages de toute nature à
l’exception de ceux requis par la loi.
Les actes malveillants d’endommagement et de vandalisme ne sont pas
couverts par ce document et doivent être pris en compte par l’installateur.
5 Mounting the RC1xx
Mount the RC1xx unit vertically or horizontally on the DIN rail to allow the
display to be read easily.
5.1 Environmental considerations
If the average output power exceeds 15W, the RC1xx must be mounted
vertically to allow air to pass through it. Leave 25mm clear either side of
the RC1xx to aid cooling.

RC1xx LED Lighting Controllers - User Manual
—10 —
The RC1xx has an ingress rating of IP20 and it should be sited so that water
or dirt cannot enter the unit.
6 Connecting the RC1xx
Refer to Section 11, “RC1xx reference information” for the ratings of the
connections. The RC1xx’s connections are shown below (an RC120 is
illustrated):
6.1 Power
Any power supply derived from mains electricity must have a Safety Extra
Low Voltage (SELV) output. Route low voltage wiring to the RC1xx controller
separately from mains electricity wiring. If this is not possible, make sure
the low voltage wiring has an insulation rating that is appropriate or
supplementary insulation is used. The connections are shown below:
6.2 Lighting output
Note: Make sure you set up the current or voltage rating for the light
before you connect it See Section 10.1, “Lighting setup”.

RC1xx LED Lighting Controllers - User Manual
—11 —
The lighting output connections must not be commoned to any other
controllers or grounded in any way. The connections are shown below:
6.3 Trigger input
The trigger input is a Smart Input; it accepts a range of trigger sources with
minimal extra circuitry. Refer to Section 7.2.1, “Trigger input options” for
further information.
Note: The Smart Input is not isolated, it is ground referenced to the power
supply negative connection.
In operating environments where there is a high level of radiated electrical
noise, use a shielded cable for the trigger input as shown below:

RC1xx LED Lighting Controllers - User Manual
—12 —
6.4 Ethernet
The RJ45 connector tted to the RC120 requires a straight-through cable to
connect to a network switch, hub or router. The connection is 10Base-T and
operates at 10MBits per second.
6.5 Connectors (general)
The connectors required to mate with the RC1xx controller’s connectors
are as follows:
Connector Description Supplier/Part number
Power input Würth 351 series 2 way
screw terminal free
socket
Würth 69135100002
Farnell 164-1952
Newark 19P1467
Trigger input Würth 361 series 4 way
screw terminal free
socket
Würth 69136110004
Farnell 184-1351
Newark 16T1571
Lighting output Würth 348 series 2 way
screw terminal free
socket
Würth 691348500002
7 General description
Three modes of operation are provided for the light output:
Continuous – the output is constant, but variable between 0% and
100% in steps of 0.1%.
Pulse (strobe) – the output is pulsed once per trigger. The delay from
trigger to pulse, the pulse duration and the brightness can all be set.
Switched – the trigger input can be used to switch the output current
on and o.
The set-up is non-volatile, so the RC1xx resumes the same operation after
a power cycle.
7.1 Pulse and duty cycle limits
The output is o by default. Upon being triggered, the RC1xx pulses to the
output after a delay. The delay, pulse width, re-trigger delay, and pulse
intensity are all congurable (see Section 9, “Web page conguration
(RC120)”, or Section 10.3.4, “Lighting commands”, or Section 10.2, “Front
panel commands”).
In pulse and switched modes, the brightness can be set up to 1000% of
its rating for short periods and low duty cycles. To avoid damage to the
lighting, the RC1xx limits the duty cycle by ignoring triggers that are too

RC1xx LED Lighting Controllers - User Manual
—13 —
soon after the previous trigger. The maximum pulse width and duty cycles
are shown below:
Output
brightness
Maximum
pulse width
Maximum
duty cycle
0 to 100% 100ms 100%
101% to 200% 30ms 30%
201% to 300% 10ms 20%
301% to 500% 2ms 10%
501% to 1000% 1ms 5%
So for example, if the brightness is set to 250%, then the RC1xx does
not allow pulses greater than 10ms long. With 10ms pulses, any trigger
occurring within the next 50ms is ignored as the duty cycle would be
greater than 20%.
The RC100 pulsed current cannot exceed 1.0A, so for a lighting rating of
0.1A, 1000% brightness is possible. For 0.25A lighting rating the maximum
brightness is 400%.
Similary the RC120 pulsed current cannot exceed 2A, so for a lighting rating
of 0.2A, 1000% brightness is possible. For 0.5A lighting rating the maximum
brightness is 400%.
7.2 Triggering
Trigger pulses should have a minimum pulse width of 2μs. You can set
the sense of the RC1xx trigger input. Do this by setting the P ag from
the front panel (see Section 10.2, “Front panel commands”), the web page
(see Section 9, “Web page conguration (RC120)”) or the RE command (see
Section 10.3.3, “General commands”). The eect of setting the P ag is
summarised below:
Mode Flag state Eect
Continuous Unused Output is on.
Switched P Flag = 1 Output is o when trigger is o.
Output is on when trigger is on.
P Flag = 0 Output is on when trigger is o.
Output is o when trigger is on.
Pulsed P Flag = 1 Pulse is triggered on rising edge.
P Flag = 0 Pulse is triggered on falling edge.
Note: The P Flag inverts the sense of the trigger.

RC1xx LED Lighting Controllers - User Manual
—14 —
7.2.1 Trigger input options
You can connect the following types of trigger to the Smart Input:
3V to 24V voltage source
Any voltage between 0V and 0.9V is
taken as logic 0.
Any voltage between 3V and 24V is
taken as logic 1.
TTL signal
You can connect a TTL signal to the
RC1xx’s input. However, a 3.3V TTL
signal only works if it can drive 8kΩ
without dropping below 2.7V.
If the P ag is set to ‘1’, the RC1xx
output turns on when the TTL driver
goes HIGH. To reverse this, set the P
ag to ‘0’ (see Section 7.2, “Triggering”).
NPN signal
You can connect an NPN open collector
drive to the RC1xx’s input. Use the
connections shown opposite.
If the P ag is set to ‘1’, the RC1xx
output turns on when the driving
transistor turns on. To reverse this,
set the P ag to ‘0’ (see Section 7.2,
“Triggering”).
Opto-coupler
You can connect an opto-coupler as
an NPN drive to the RC1xx’s input. This
prevents a ‘ground-loop’ and reduces
spurious triggering in high-interference
environments.
If the P ag is set to ‘1’, the RC1xx
output turns on when the driving
transistor turns on. To reverse this,
set the P ag to ‘0’ (see Section 7.2,
“Triggering”).

RC1xx LED Lighting Controllers - User Manual
—15 —
PNP signal
You can connect a PNP open collector
drive to the RC1xx’s input. Use the
connections shown opposite. The PNP
transistor should not pull up to more
than 24V.
If the P ag is set to ‘1’, the RC1xx
output turns on when the driving
transistor turns on. To reverse this,
set the P ag to ‘0’ (see Section 7.2,
“Triggering”).
7.2.2 Internal trigger
You can set the RC1xx to generate its own trigger pulses. The period of
these pulses can be set in increments of 100μs from approximately 10ms
to 5000ms.
You can set the RC1xx to produce a single pulse for testing purpose. This is
set by either a TR1 command (see Section 10.3.3, “General commands”) or
using the web page Trigger button (see Section 9, “Web page conguration
(RC120)”).
7.3 SafeSense
The SafeSense feature of the RC1xx operates automatically. After setting
the rating for the light, the RC1xx senses the light on connection for its type
and characteristics. The unit does not need to sense the light again unless
the light has changed or the RC1xx has been power-cycled.
For further information on this feature, see the application note, APP936 –
SafeSense Technology, available from www.gardasoft.com.
7.4 SafePower
The RC1xx’s SafePower needs no intervention from the user for its
operation. The advantages of SafePower are:
»Heat dissipation in the controller is very low
»The load voltage can be higher than the supply voltage
»High continuous currents can be output with a reduced need for
heatsinking
For further information on this feature, see the application note, APP966 –
SafePower Technology, available from www.gardasoft.com.
7.5 Light characterisation
You can reduce the time it takes for your RC120 controller to reach high
accuracy in time-critical machine vision systems when changing from one
overdrive brightness setting to another. This can be done by instructing the
controller to make current and voltage measurements up to a customer

RC1xx LED Lighting Controllers - User Manual
—16 —
specied brightness limit when the light is characterised. This is called
the characterisation limit. The measured overdrive voltage and current
relationship is stored in the RC120 and allows it to respond much more
rapidly to new overdrive parameters up to that limit.
When a light is detected, the characteristics of the light are measured up to
the brightness set for the characterisation limit. It is not essential to set this
value and it can be left at 200 (meaning 200% brightness). The feature can
also be turned o by setting this value to 0.
You can change the characterisation limit brightness through the RC120’s
web pages (see Section 9, “Web page conguration (RC120)”) or by
command (see Section 10.3.4, “Lighting commands”).
7.6 Current adjust
The current adjust feature provides a more accurate and repeatable
output current. After setting an output current, the controller continually
measures the actual current and adjusts the output to maintain the target
current. This will compensate for any inaccuracies such as temperature
drift in the controller.
If the output current is less than 100mA, the adjustments the feature
imposes can have a signicant eect on the lighting brightness. If some
ickering is seen, it is recommended that the current adjust feature is
turned o.
Current adjust can be turned on and o from the RC120’s web pages (see
Section 9, “Web page conguration (RC120)”) or by using the RE command
(see Section 10.3.3, “General commands”).
7.7 Flags
You can set ags on the RC1xx controller to alter its operation. They can be
set from the unit’s front panel, the web page or through the RE command
(see Section 10.3.3, “General commands”). The following conguration ags
are available:
E Flag – Enables or disables fault detection. Error checking is enabled
as the default setting.
P Flag – Sets the trigger input active high or active low. The default
setting is active high. Refer to Section 7.2.1, “Trigger input options” for
a detailed description of the settings.
S Flag – Sets the SafeSense feature of the RC1xx. When cleared it
removes the SafeSense light detection and the controller assumes a
light is connected. The default setting is for SafeSense to be enabled.
This ag cannot be used when the light is set according to its voltage
rating. The S ag cannot be changed from the RC1xx’s front panel.

RC1xx LED Lighting Controllers - User Manual
—17 —
7.8 Fault detection
The RC1xx can detect a range of errors when connected to a light. The
displayed error codes are shown below with their reasons.
Error Reason
PO Internal power dissipation too high. Output turned o.
OP Output current to lighting is too low. The light is open
circuit or there is not enough supply voltage for the
requested current.
Sh Output voltage is too low. The RC1xx detects that the
output is short-circuited.
HI The voltage required for the lighting has increased too
much. Check for ageing of the light or a failed LED.
LO The voltage required for the lighting has decreased too
much. Check for ageing of the light or a failed LED.
Note: When the output current falls below 100mA, some fault detection is
disabled. Press SEL to cancel the error and allow the RC1xx to sense the
light again.
7.9 Factory settings
You can clear the RC1xx conguration to return it to its factory settings:
The lighting rating is cleared and the light does not illuminate.
Clear the conguration from the front panel by pressing and holding SEL
and for about 5 seconds, until COL is displayed. You can also clear the
conguration by using the CL command (see Section 10.3.3, “General
commands”).
You can start the RC1xx from a powered down state (cold boot) with the
front panel keypad locked; this process removes the keypad lock.
8 Ethernet address (RC120)
You may need to ask your network administrator for advice about setting
up the Ethernet connection.
The application note APP923 – Troubleshooting Ethernet problems is
available from www.gardasoft.com/Downloads.
The Ethernet set up of the RC120 is not aected by cold-booting the
controller.

RC1xx LED Lighting Controllers - User Manual
—18 —
8.1 IP address
The RC120 needs an Internet Protocol (IP) address to communicate over
Ethernet. There are two ways to get an IP address; either programmed into
the unit or using DHCP.
For DHCP mode, the RC120 acquired its IP address, subnet mask, and
gateway address from the DHCP server. Otherwise the RC120 has a xed IP
address, subnet mask, and gateway address.
DHCP mode or the IP address can be set or read using the GardasoftMaint
program available from www.gardasoft.com.
The GardasoftMaint window is shown below:
GardasoftMaint allows you to view the controllers on your network, change
their IP addresses and upgrade their rmware if it becomes necessary.
In the messaging section of GardasoftMaint, you can communicate with
your controller using the commands explained in Section 10.3.3, “General
commands” and Section 10.3.4, “Lighting commands”. You can also open
the selected controller’s web pages at the click of a button. For more
information about the RC120’s web pages, see Section 9, “Web page
conguration (RC120)”.
8.1.1 DHCP
Most networks use a DHCP server. If there is a PC on the network, you
may be able to nd out whether a PC on the same network uses DCHP as
follows:

RC1xx LED Lighting Controllers - User Manual
—19 —
i. Right-click the Windows 10™ icon at the left of your PC’s task bar.
ii. Select Network Connections.
iii. in the Status pane, click on View your network properties.
iv. DHCP enabled will be set to ‘yes’ if DHCP is in use.
You can nd out what IP address is being used by a PC at any time by
following the steps below:
i. Right-click the Windows 10™ icon at the left of your PC’s task bar.
ii. Select Network Connections.
iii. In the left hand pane, click on Ethernet.
iv. Click on your network icon under Ethernet.
Your IP address will be given as the ‘IPV4 address’.
8.1.2 Fixed IP address
When using a xed IP address, you must ensure that you use an IP address
that is not being used by any other device on the network. It is usual to
keep the rst three numbers of the IP address the same as other devices
and to change only the last number. For example, if you have a network
consisting of a PC (IP address 192.168.1.35) and two RC12xs, they could be
allocated addresses 192.168.1.201 and 192.168.1.202.
8.2 Automatic sensing
The RC12x ends out a message on three events:
»On power up,
»When an IP address is received or renewed by DHCP, and
»When an enquiry message is received
On the rst two events, the message is broadcast. On the third it is a reply
to a single IP address.
An enquiry message is a UDP packet from source port 30310, destination
port 30311 with the message body ‘Gardasoft Search’ (8-bit ASCII, 16
characters).
The message output by the RC12x is a UDP packet from source port 30311,
destination port 30310. It is formatted as:
Gardasoft,RC12x,000000,111111111111,22222222
(8-bit ASCII, 44 characters), where:
000000 is the serial number of the unit
111111111111 is the MAC address in 6 HEX bytes
22222222 is the IP address in 4 HEX bytes

RC1xx LED Lighting Controllers - User Manual
—20 —
For example, for RC12x serial number 12345, IP address 192.168.1.103,
MAC address 00.0B.75.01.80.99 the packet comprises:
Gardasoft,RC12x,012345,000B75018099,C0A80167
9 Web page conguration (RC120)
You can set up the RC120 through its own internal web pages. After
locating your controller on your network, click the Open webpage... button
in GardasoftMaint to take you directly to the RC120’s web pages. You can
also type the controller’s IP address (displayed in GardasoftMaint) into your
web browser, which will display the Main page. GardasoftMaint software is
available from www.gardasoft.com.
9.1 Main page
The main page (shown below) is the rst to open when you access the
RC120’s web pages. This gives the controller’s hardware and rmware
revision levels and the serial number. It also tells you the power being
dissipated and the RC120’s internal temperature.
9.2 Conguration page
The conguration page allows you to set up the lighting parameters,
view the light data, and view the measurements the RC120 makes
during operation. To refresh this page it is important that you click the
Refresh button on the web page () rather than on your web browser.
When conguration changes are submitted, the URL includes the new
conguration, so refreshing the page re-submits the URL.
You can set the mode (continuous, pulsed, or switched), the light’s
brightness and pulse settings. You must click the Submit button to eect
any changes you make.
Click the Refresh button at the bottom of the screen to update the
measurements being taken.
This manual suits for next models
2
Table of contents
Other GARDASOFT Controllers manuals

GARDASOFT
GARDASOFT CC320 User manual

GARDASOFT
GARDASOFT CC320 User manual

GARDASOFT
GARDASOFT OC-G-5646-2-ET User manual

GARDASOFT
GARDASOFT RC100 User manual

GARDASOFT
GARDASOFT RT 20 Series User manual

GARDASOFT
GARDASOFT TR-RT Series User manual

GARDASOFT
GARDASOFT PP600F LED User manual

GARDASOFT
GARDASOFT PP420 User manual

GARDASOFT
GARDASOFT CL190 User manual

GARDASOFT
GARDASOFT PP600 User manual