Garnet PC-732G User manual

SP SPANISH PC-732G
www.garnet.com.ar
PANEL DE ALARMA
Manual de Instalador

2
General Information
WARNING:
This manual contains information about the operation of the PC- 732G® and
its restrictions, therefore, it should be read carefully
Limited Warranty:
Alonso Hnos. Sirenas S.A. (the seller) warrants its products to be
free from defects in material and workmanship under normal use for one year. Except
as specically stated herein, all express or implied warranties, statutory or otherwi-
se, any implied warranties of merchantability or tness for a particular purpose are
expressly excluded. Because the seller does not install or connect the products and
because the products may be used in conjunction with products not manufactured by
the seller, the seller cannot guarantee the performance of the security system and shall
not be liable for circumstances resulting from the inability of the product to function.
The manufacturer’s obligation under this warranty is expressly limited to the repair or
replacement, at the seller’s option, of any product that does not meet specications.
All returns must include proof of purchase and be made within the warranty period.
In no event shall the buyer or any person hold the seller liable for any loss or damage,
whether direct or indirect, including, but not limited to, any damages for loss of prots,
stolen merchandise or claims made by third parties, which are caused by defective
goods or are due to misuse or faulty installation of material. Notwithstanding the above
paragraph, the seller’s maximum liability is strictly limited to the purchase price of the
defective product. Use of this product signies acceptance of this warranty.
ATTENTION:
Distributors, installers and/or others selling the product are not authori-
sed to modify this warranty or make additional warranties binding on the seller.
WARNING:
Please read carefully
Note to Installers
This warning contains vital information. For the sole individual in contact with the user’s
system, it is their responsibility to address each item in this warning for the attention of
the users of this system.
System Failures
The system has been carefully designed to be as eective as possible. However, there are
circumstances, including re, burglary or other emergencies where it will not be able to
provide protection.
Any alarm system can be deliberately compromised or fail to operate for a number of
reasons, some of which may include:
Improper Installation
A safety system must be properly installed to provide adequate protection. Equipment
must not be installed where it will be exposed to moisture or splashing. Each installation
must be evaluated by a safety professional to ensure that all points and access areas are
covered. All window and door locks and latches must be secure and operate as designed.
Windows, doors, walls, ceilings and other materials must possess sucient strength and
construction to provide the expected level of protection. A re-evaluation should be con-
ducted during and after any construction activity. An assessment by the police or re
service is highly recommended if this service is available.
The equipment must be installed in an environment with temperatures between 0ºC and
70ºC.
Criminal Knowledge and Sabotage
This system contains security features that were known to be eective at the time of
manufacture. It is possible for people with criminal intent to develop techniques which
reduce the eectiveness of these features. It is very important that the security system
be reviewed periodically, to ensure that its features remain eective and that they are
updated or replaced if they are found not to provide the expected protection.
Access by Intruders
Intruders can enter through an unprotected access point, circumvent a dis- posed sensor,
evade detection by moving through an area of insucient coverage, disconnect a war-
ning device, interfere with or prevent proper operation of the system.
Power Failure
Control units, intrusion detectors, smoke detectors and many other security devices re-
quire an adequate power supply for proper operation. If a device is battery operated,
it is possible for the batteries to fail. Even if the batteries have not failed, they must be
charged, in good condition and installed correctly. If a device operates on AC power, any
interruption, even a slow one, will render the device inoperable while without power.
Power interruptions of any duration are often accompanied by voltage uctuations which
can damage electronic equipment such as security systems.
After a power outage occurs, immediately conduct a complete system test to ensure that
the system is functioning as intended.
Compromised Wireless Devices
Signals will not be able to reach the receiver under all circumstances, which include
metal objects placed nearby or deliberate interference.
Failure of Replaceable Batteries
The expected battery life is a function of the environment, usage and type of device.
Environmental conditions such as excessive humidity, high or low temperatures, or var-
ying amounts of temperature uctuations may reduce battery life. Regular testing and
maintenance will keep the system in good working condition.
System Users
System Users
It is very important that all users of the system are trained in the correct operation of the
alarm system and know how to respond to an alarm
Smoke Detectors
Smoke detectors, which are a part of the system, may not properly alert occupants of a
re for a number of reasons, some of which are as follows: Smoke detectors may have
been incorrectly installed or located. Smoke may not be able to reach the smoke de-
tectors, such as when the re is in the chimney, walls or ceilings, or on the other side of
closed doors. Smoke detectors cannot detect smoke from res on other levels of the re-
sidence. Each re is dierent in the amount of smoke produced and the speed of the re.
Smoke detectors cannot detect all types of res equally well. Smoke detectors cannot
provide early warning of res caused by carelessness or lack of safety such as smoking in
bed, slow explosions, gas leaks, improper storage of combustion materials, overloaded
electrical circuits, playing with matches, or arson.
Even if the smoke detector functions as designed, there may be circumstances where
there is insucient warning time to allow occupants to escape in time to avoid injury or
death.
Motion Detectors
Motion detectors can only detect movement within the designated areas as shown in the
respective installation instructions. They do not discriminate between intruders and/or
inhabitants of the premises or residence, nor do they provide volumetric area protection.
They have multiple detection beams and motion can only be detected in unobstructed
areas covered by these beams. They cannot detect movement behind walls, ceilings,
oors, closed doors, glass partitions, glass doors or windows. Any kind of sabotage, in-
tentional or unintentional, will impair their proper operation.
Passive infrared motion detectors operate by detecting changes in temperature. Howe-
ver, their eectiveness may be reduced when the ambient temperature rises near or abo-
ve body temperature or if there are intentional or unintentional sources of heat in or near
the detection area. Some of the sources of heat may be heaters, radiators, cookers, grills,
replaces, sunlight, etc.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not alert or awaken someone
if there is an intervening door or wall. If warning devices are located on a dierent level
of the residence or premises, it is less likely that occupants can be warned or awakened.
Audible warning devices can be interfered with by other noise sources such as stereos,
radios, televisions, air conditioners, etc.
Audible warning devices, even loud ones, may not be heard by people with hearing im-
pairments.
Insucient Time
There may be circumstances when the system is functioning as designed, and yet the
occupants will not be protected from emergencies, due to their inability to respond to
warnings in a timely manner. If the system is supervised, the response may not occur in
time to protect the occupants or their belongings.
Component Failure
Despite all eorts at system reliability, the system may fail in the following cases.
its function, due to the failure of a component.
Incorrect Test
Most problems/failures of an alarm system can be found by regular testing and mainte-
nance. The entire system should be tested weekly and immediately after an intrusion,
attempted intrusion, re, storm, earthquake, accident or any kind of construction activity
on or o the premises. The test should include all devices that are part of the system,
such as sensors, keypads, sirens, etc.
Safety and Insurance
Despite its capabilities, an alarm system is not a substitute for property or life insurance.
Nor is an alarm system a substitute for property owners, tenants, or other occupants
to act prudently to prevent or minimize the harmful eects of an emergency situation.

3
INDEX
Wiring Diagram ............................................................................................................................................................................. 4
Section 1: System Introduction 4
1.1 Specications........................................................................................................................................................................... 4
1.2 Additional Devices................................................................................................................................................................... 5
Section 2: Starting the Installation 6
2.1 Installation Steps...................................................................................................................................................................... 6
2.2 Terminal Descriptions.............................................................................................................................................................. 6
2.3 Installation and Operation of the BUS-D485......................................................................................................................... 6
2.4 Current Ratings for Modules and Accessories...................................................................................................................... 7
2.5 Keyboard Assignments............................................................................................................................................................ 7
2.6 Monitoring................................................................................................................................................................................. 7
2.7 Remove Modules...................................................................................................................................................................... 7
2.8 Zone Wiring............................................................................................................................................................................... 7
2.9 Fire Zone Wiring........................................................................................................................................................................ 7
2.10 Keyboard Zones........................................................................................................................................................................ 7
2.11 Expansion Module Zones........................................................................................................................................................ 8
Section 3: Keyboard Commands 8
3.1 Arming and Disarming............................................................................................................................................................. 8
3.2 Arming in Present Mode.......................................................................................................................................................... 8
3.3 Automatic Arming and Disarming.......................................................................................................................................... 8
3.4 Forced Armed........................................................................................................................................................................... 8
3.5 Commands [ ]....................................................................................................................................................................... 8
3.6 Functional Keys........................................................................................................................................................................ 9
Section 4: How to Program 9
4.1 Installer Programming............................................................................................................................................................. 9
4.2 Programming Special Data...................................................................................................................................................... 9
4.3 See Programming..................................................................................................................................................................... 9
Section 5: Programme Descriptions 9
5.1 Programming Security Codes.................................................................................................................................................. 9
5.2 Programming Zones................................................................................................................................................................. 9
5.3 Zone Attributes......................................................................................................................................................................... 10
5.4 Crossing Zone............................................................................................................................................................................ 10
5.5 Group Inhibition Zone.............................................................................................................................................................. 10
5.6 Keyboard Zone Assignments................................................................................................................................................... 10
5.7 Download Information............................................................................................................................................................. 10
5.8 PGM Output Options................................................................................................................................................................ 11
5.9 Connection of PGMs................................................................................................................................................................. 11
5.10 Siren Output.............................................................................................................................................................................. 11
5.11 Periodic Test Report................................................................................................................................................................. 11
5.12 Armed System Follower Test Report...................................................................................................................................... 11
5.13 Manual Test Report.................................................................................................................................................................. 11
5.14 Retransmission of the Test and/or Network Failure Report in the event of a communication failure......................... 11
5.15 Fire, Medical and Panic Keys................................................................................................................................................... 11
5.16 Events Report............................................................................................................................................................................ 11
5.17 Zone Circuit Response............................................................................................................................................................. 11
5.18 Communication Scenarios...................................................................................................................................................... 11
5.19 How to operate communication scenarios........................................................................................................................... 11
5.20 Reset to Factory Defaults......................................................................................................................................................... 12
Section 6: Programming Wireless Devices 12
6.1 How to twin a wireless sensor................................................................................................................................................. 12
6.2 How to pair wireless key fobs.................................................................................................................................................. 12
6.3 How to remove wireless sensors............................................................................................................................................ 12
6.4 How to remove key rings......................................................................................................................................................... 12
6.5 How to verify the correct functioning of a wireless sensor................................................................................................. 12
6.6 How to display the zones assigned to each sensor............................................................................................................... 12
6.7 How to delete all sensors and/or key fobs.............................................................................................................................. 12
6.8 How to twin a PGM-W module.................................................................................................................................................. 12
6.9 How to remove PGM-W modules............................................................................................................................................. 12
Section 8: Report Codes Transmitted in Contact ID and SIA 13
Section 9: Programming parameters 14
Fault Table........................................................................................................................................................................................................ 31
Guarantee. 32
Notes......... 33

4
G-LED732/G-LCD732/G-LCD732RF
EXP-8Z
PC-732G
Bateria
Transformador
Rojo +
Negro -
16.5 VAC
25 VA
50/60 Hz
A B
E1
C E2 E3 C E4 E5 C E6 E7 C E8
-+
+ BUS - A B Z MIC
Magnético
RFL
2.2K
N.C.
N.C.
N.O.
N.O.
RFL
2.2K
RFL
2.2K
RFL
2.2K
SIRENA
1.4A Max.
STATUS
RUNNING
BUS-C485
BUS-D485
COMUNICADORES
- AUX + + BELL - A B
PGM1 PGM2
Z1 Z6CZ5Z4CZ3Z2C
AC + BAT - A B+ AUX -
Y B A - +G
General characteristics
• Up to 32 total zones
• 2 partitions
• 2 wired PGM outputs + possibility of 4 Wireless PGM outputs
• Panel and/or communicator programming via Keyboard/Cellular/PC
• Possibility to use and program communicators with LED keypads (KPD-800/G-
LED732)
• Schedule of Days/Times for automatic arming/disarming
• Panel arming by non-movement time
• Conguration and Choice of events to be reported.
• Event blocking for faults or repeated tripping (Optional)
• Possibility to report by various means congurable from Scenarios of communi-
cation
• 512 event memory
• Shutdown of the alarm panel due to low battery voltage. Previously sent low
battery event and panel shutdown (avoids false triggers).
• Direct integration with Pivot Access family of access control systems
• Zone conguration in special modes: Double Trigger and/or Zone Crossing
• 13 dierent zone programming
• Simple operation of 2 partitions from a single keyboard
• Compatible with 3G-COM-G/4G-MAX-G and IP-500G family of communicators
SECTION 1: System Introduction
This manual is designed to help you through the installation process of the PC-
732G® Alarm Panel. We suggest that you read this manual, in its entirety, before
beginning the installation process so that you can better understand all that this
security system has to oer. This manual is not intended for end users. End users
are recommended to read the User Manual provided with the system. If you have
any questions regarding the procedures described in this manual, please log on to
www.garnet.com.ar/Soporte_Tecnico/Consultas.
1.1 Specications
Programming
• Local programming via keypads.
• Local programming via PC-Link cable (adapter cable).
• Remote programming via 3G-COM-G/4G-MAX-G AC4 software.
• Remote programming via IP-500G and AC4 software.
Partitions
The system has 2 independent partitions, as well as the possibility of sharing zones
in any of them, obtaining partitions with zones common to 2 partitions.
Flexible Zone Conguration
• 32 fully programmable zones with 19 dierent operating congurations and 8
dierent, individual attributes for each zone.
• 1 additional zone for each keypad installed.
• Zone circuit with single RFL.
• Fire zones with fault discrimination and alarm.
• Using EXP-8Z zone expanders, the system supports up to 24 wired zones.
additional (maximum 3 expanders)
• With KPD-860RF/G-LCD732RF keypads (one is sucient), the system supports up
to 24 wireless zones (out of 32 available).
• Crossing areas
• Zones of Group Inhibition
Codes
The equipment has 36 codes available for the following functions:
• 1 master code.
• 31 user codes.
• 2 duress codes (individual for each partition).
• 1 installer code.
• 1 Local Programming Code by Cable Adapter (PC-Link).
WARNING DIAGRAM

5
Bus Data: BUS-D485
Its works through the RS-485 protocol, its connection is made using 4 wires, 2 for
power supply and 2 for data. The system is able to supervise each device connected
to the bus and generate a fault in the event of an error condition.
The maximum connection distance between the panel and the devices is 200
metres.
• Supports up to 8 keyboards.
• 3 EXP-8Z Expander modules.
• 1 Auxiliary Power Supply 1.5A FRA-200
• 1 Adapter cable for local programming (PC-Link).
Data Bus: BUS-C485
It is specially designed for high speed data transmission, it works through the
RS-485 protocol, its connection is made using 4 wires, 2 for power supply and 2 for
data.
The system is able to supervise each device connected to the bus and generate a
fault in the event of an error condition. The maximum connection distance between
the panel and the devices is 200 mts.
• Supports IP-500G, 3G-COM-G/4G-MAX-G devices.
Audible Alarm Output
The system supports up to 3 alarm outputs, using a combination between
Programmable Outputs (PGMs) and the Outdoor Siren Output.
Each programmable output can be congured as a siren output for any of the 2 par-
titions, so you could have 2 siren outputs (independent for each partition), and an
external siren output common to both partitions through the panel’s Siren Output.
The siren sound is continuous or pulsating in the event of a re alarm.
The re alarm can be congured to be Pulse (1 second on, 1 second o) or Tempo-
rary 3, according to NFPA 72 standard (500mS on, 500 mS o, 500mS on, 500 mS
o, 500mS on, 500mS on, 1.5 sec. o).
• 1 1.4A, 12VDC Outdoor Siren output.
Monitored for short-circuit and disconnection.
• 2 Siren outputs per PGM.
NOTE: Take into account the current values when connecting a siren to a program-
mable output, as these are not supervised in the event of excess consumption.
Power requirements
Transformer: 16.5 VAC, 25VA.
Battery: 12 volt 4Ah minimum.
Regulated Energy Supply
2 independent power supply outputs: AUX and AUX-3G/IP
• Supply: AUX 700mA, 12 VDC
• Power supply: AUX-3G/IP 300mA, 12 VDC
EEPROM memory
No loss of programming or system status in the event of a complete power failure.
Garnet Keypads Specications: KPD-800/KPD-860/KPD-860RF/ G-LED 732/
G-LCD732/G-LCD732RF.
• They are connected by 4 wires.
• Internal piezo buzzer with volume control.
• Backlight brightness control (only for models KPD-860/KPD-860RF/ G-LD732/
G-LCD732RF)
• Built-in radio frequency receiver (Model KPD-860RF/G-LCD732RF only).
• Anti-disassembly and anti-disassembly tamper.
• Independent indication of partition statuses.
• Separate armed, away and disarmed keys for facilitate their use.
Communication protocols
• Residential SMS (Only with 3G-COM-G/4G-MAX-G).
• SDC2 (Only with 3G-COM-G/4G-MAX-G or IP-500G).
• DC1 (Only with 3G-COM-G/4G-MAX-G or IP-500G).
System monitoring features
• CA power failure (on panel).
• CA power failure (on auxiliary source FRA-200).
• Low battery condition (on panel).
• Low battery condition (auxiliary source FRA-200).
• Failure of auxiliary power supply.
• Zone fault (supervised zones).
• Lack of internal clock programming.
• Siren output faults (disconnection and over current).
• Mobile Data communication failure (3G-COM-G/4G-MAX-G only).
• SMS communication failure (3G-COM-G/4G-MAX-G only).
• Link Failure (IP-500G and 3G-COM-G/4G-MAX-G only).
• Low battery per zone (only with wireless sensors).
• Zone Tamper (only with wireless sensors).
• Keyboard Tamper.
• Monitoring of modules installed in the BUS-D485 and BUS-C485.
• Failure in re zones.
• False Alarm Prevention Features
• Audible Exit Delay with dierentiated sound in the last 10 seconds.
• Audible input delay.
• Double-triggered alarm in zones.
• Cross Zone Burglary Alarm.
• Independent entry/exit times for each partition.
• Auto Arming and Auto Disarming with independent programmable times and
days for each partition.
• Auto arming on inactivity in zones with independent programmable times for
each partition.
• Keypad-activated manual communication test.
• Programmable automatic communication test with start time and intervals.
• All modules are connected to the system via a 4-wire bus. Up to 200m from the
PC-732G® panel.
• A 512-log event memory with date and time of occurrence. The memory can be
viewed with the KPD860 /860RF G-LCD732/ keypad. G-LCD732RF and/or with
AC4 Software.
• Automatic Shutdown: In the event of AC power failure and a signicantly dischar-
ged battery, the panel will automatically shut down and restart when AC power
returns.
• Swinger Shutdown: Separate programmable counters for 17 types of shutdowns
dierent faults and/or alarms.
• Force arming for local and/or remote arming modes.
• Time programmable retransmission of Test Report and/or Network Fault Report
in the event of a communication failure.
1.2 Additional Devices
LCD Keyboard with Wireless Receiver KPD-860RF/G-LCD732RF
The Wireless Receiver is built into each keypad, and can be used to connect up to
24 wireless sensors, 64 remote controls, and 4 PGM-W/MA-220G to the system.
2-Way Wireles System® communication system.
All wireless sensors operate at 434 MHz and are bi-directional monitoring devices,
using CR123A lithium batteries.
NOTE: KPD-860RF/G-LCD732RF keypads shall be assigned addresses 1-4.
If a KPD-860RF/G-LCD732RF keypad is assigned an address greater than four, the
keypad will override its RF receiver.
The following devices are available:
• Wireless Motion Detector DGW-500. Adds wireless space protection to a sector of
the site
• Universal Wireless Transmitter DGM-300. Adds wireless door/window contacts to
your system
• PGM-W/MA-220G programmable wireless output module: It allows, without the
need for interconnection of cables, to control lights, motors, automatic irrigation
and many other devices.
• Wireless Remote Control TX-500
The 3 buttons on the remote control are congurable for dierent functions.
They are:
• Arm and disarm the system.
• Partition panic button.
• Activate a PGM output.
• Activate PGM-W./MA-220G output
• Wireless outdoor sensor IR-1000RF. Ideal for outdoor detection
• Wireless Photoelectric Smoke Detector DH360i. Early re detection
3G-COM-G / 4G-MAX-G Cellular Communicator
The 3G-COM-G / 4G-MAX-G Cellular Communicator can be used in two dierent
forms:
• WiFi reporting as rst means and cellular network as backup.
• Reporting by cellular network as rst and only means.

6
IP-500G WiFi Communicator
The IP-500G Communicator has the same capabilities as the 3G-COM-G / 4G-MAX-G
communicator, but instead of a GSM connection, it will use a WIFI connection to
communicate. It connects to the panel via the BUS-C485. It can also be used in
three dierent ways:
• As the main communicator with or without back-up.
• As a back-up communicator for other media.
• As a simultaneous communicator alongside other media.
Please refer to the explanation of the dierent scenarios of
communication, backup scenario and dual or simultaneous reporting scenarios.
EXP-8Z Zone Expander
It is a wired 8-zone expander for the PC-732G® panel.
The system supports a maximum of 3 expanders, growing to a maximum of 32
zones.
Each expander must be addressed and assigned in the programming to the die-
rent zones of the system.
Connects to BUS-D485 and can be installed inside or outside the panel enclosure
PC-732G®.
Supervised Auxiliary Power Supply FRA-200
The FRA-200 power supply provides an extra power supply for systems where
power consumption is important. At the same time, it can have a battery backup
for AC outages.
The installer should distribute the power consumptions so that, in the event of an
AC power failure, both batteries are evenly discharged (the main battery of the
panel and the battery of the auxiliary source FRA-200).
The FRA-200 source is also connected to the BUS-D485 and is fully supervised by
the PC-732G® alarm panel. The panel will indicate low battery and mains failure of
the auxiliary source.
Access Control CP-4000
Each CP-4000 access control module can control up to two independent doors,
with entry and exit readers or a combined reader with a button and exit require-
ment.
SECTION 2: Starting the Installation
This section will provide a comprehensive description of how to install and
congure the dierent devices and zones.
2.1 Installation Steps
Read this section thoroughly before you begin. Once you have a general unders-
tanding of the installation process, work carefully through each step.
Step 1: Create a sketch
Draw a sketch of the construction, to get an idea about the location of detectors,
keypads and other modules that will be placed.
Step 2: Mount the Control Panel
Mount the control panel in a dry area near the entrance of a power outlet.
of non-interruptible AC power.
NOTE: All wiring must be completed before connecting the battery, or applying AC
to the control panel.
Step 3: Installing devices on the BUS-D485 (See also Section 2.3) Install the bus
to each of the modules following the guidelines provided in Section 2.3 of this
manual.
Step 4: Install the Zones (Section 2.8)
You must remove power from the PC-732G® panel to install zone circuits. Please
refer to Section 2.8 when wiring zones, using normally closed circuits, RFL end-of-
line resistors, re zones and Keyswitch “Arming” zones.
Step 5: Complete Installation (Section 2.2)
Complete all other installations including sirens, programmable outputs if availa-
ble, and other devices following the guidelines provided in Section 2.2 (Terminal
Descriptions).
Step 6: Energising the Control Panel
Once the installation of all zones and keypads is complete, activate the Control Pa-
nel. First, connect the red battery cable to the positive terminal and the black cable
to the negative terminal. Then connect the AC power.
NOTE: Always connect the battery before connecting AC power. AC power must be
applied for at least 10 seconds, or the control panel will not operate.
The control panel will not activate with battery connection alone.
Step 7: Keyboard Assignment (Section 2.5)
In order for the keypads to be properly monitored, each one must be assigned
to a dierent “address” on the bus. Please follow the guidelines provided in Section
2.5.
Step 8: Monitoring (Section 2.6)
Supervision of each module must be enabled by programming. Verify that all mo-
dules are recognised by the system, according to the instructions in Section 2.6.
Step 9: Programming the System (Sections 4 and 5)
Section 4 explains how to program the control. Section 5 contains a complete des-
cription of several of the programmable features, which options are available and
how they work. Complete the programming sheets before attempting to program
the system.
Step 10: Test the System
Fully test the system to ensure that all features and functions are operating as
programmed.
2.2 Terminal Descriptions
Battery Connection: +BAT-
A 12V, 4/7Ah rechargeable battery is used as a backup power source in the event
of an AC failure. The battery also provides additional power when the demand on
the control panel exceeds the power capacity of the transceiver, such as when the
system is in alarm.
NOTE: Do not connect the battery until all other installations are complete. Con-
nect the battery before connecting the AC.
Connect the RED battery cable to the positive battery terminal; connect the BLACK
cable to the negative.
Transformer terminals: ~AC~
The control panel requires a 16.5 volt, 25 VA transformer. Connect the transformer
primary to an interruptible outlet and the secondary to these terminals.
NOTE: Be sure to clearly identify the transformer primary and secondary wires
before connecting. Do not connect the transformer until all other installations have
been completed.
Auxiliary power terminals: - AUX+
These terminals provide up to 700mA of auxiliary current at 12 VDC for devices re-
quiring power. Connect the positive side of any device requiring power to the +AUX
terminal, the negative side to -AUX. The AUX output is protected. This means that if
too much current ows through these terminals (such as in a short circuit), the PC-
732G® panel will temporarily shut down the output until the problem is corrected.
Siren Output Terminals: +BELL-
These terminals provide up to 1.4A of DC current at 12VDC to power bells, sirens,
strobes or other warning equipment. Connect the positive of any warning device to
+BELL, the negative to -BELL.
Note that the Siren output is protected: if there is a high consumption of these
terminals (such as in a short circuit), the protection will open. Three am- peres can
be consumed for short periods only.
The Bell output is supervised. If no warning device is used, connect a 1000 ohms
resistor between the +BELL - terminals to prevent the panel from displaying a fault
condition. For more information (see section 3.5 “Commands [*]).
BUS-C485 terminals: +AUX-, A, B.
The Accessory bus is used by the control panel to communicate with the 3G-COM-G
/ 4G-MAX-G and IP-500G communicators. Each Communicator has four bus termi-
nals which must be connected to the four terminals of
this bus on the control panel.
Programmable Output Terminals: PGM1 to PGM2
Each PGM output is designed so that when activated by the control panel, the ter-
minal connects to ground. PGM1-PGM2 can draw up to 50mA of current. Connect
the positive of an LED or buzzer to the +AUX terminal and the negative to the PGM.
If more than 50mA of current is required, a relay must be used.
Please study the PGM wiring in the diagram. For a list of programmable output
options, please see section 5.9 “PGM Output Options”.
Zone Input Terminals - Z1 to Z6
Each detection device should preferably be connected to one zone in the control
panel. However, it is possible to install multiple devices on the same zone. For zone
installation specications, please see section 2.8 “Zone Wiring”.
2.3 Installation and Operation of the BUS-D485
The data bus is used by the PC-732G® panel to communicate with all connected
modules and vice versa. Terminals (A) and (B) are for data.
NOTE: The four bus terminals on the PC-732G® panel must be connected to the
four bus terminals or bus cables on all modules.

7
The following restrictions apply to BUS-D485 wiring:
• Each bus conductor must be at least 0.5mm gauge, a two twisted pair cable is
suitable.
• Each module can be connected directly to the control panel, but can also be
connected in series or in shunt.
• No module may be more than 200m (in cable length) from the control panel.
• Shielded cable reduces the maximum distance.
2.4 Current Ratings for Modules and Accessories
For the PC-732G® system to operate properly, the power output capabilities of the
panel and expansion devices must not be exceeded. Use the data below to ensure
that no part of the system is overloaded and cannot function properly.
PC-732G® (12 VDC)
+AUX: 700mA Subtract the values listed for each detector or device.
accessory connected to the AUX+.
+1.4A continuous rating. Available only with battery back-up
connected.
Device Ratings for PC-732G® (at 12VDC):
• LED keypad: 100 mA max. (60 mA idle).
• LCD keypad: 210 mA max. (90 mA idle).
• LCD-RF keypad: 210 mA max. (90 mA idle).
• EXP-8Z Zone Expander Module: 15mA
• PC-732G Board: Approx 100mA
Other Devices
Please read the manufacturer’s documentation carefully to determine the maxi-
mum current demands required for each device during activation or alarm and
include the correct values for power calculations. Connected devices must not
exceed the capabilities of the system during any possible mode of operation.
2.5 Keyboard Assignments
There are eight bus addresses available for the keypads. The keypads
KPD-800/KPD-860/KPD-860RF/G-LED732/G-LCD732/G-LCD732RF están, por
Each keypad must be registered to a dierent address. dierent address (1 to 8).
Keypad registration is required, as it tells the control panel which addresses are
busy. The control panel can generate a fault when a keypad supervision is not
present.
How to program the address of the KPD-800/ G-LED732 keypads
1. Press the [ ] [8].
2. Then press the [4] key to indicate that you wish to enter programming.
keyboard.
3. Finally press the [8] key to conrm the programming entry.
de address.
4. Enter the new address (1 to 8). To cancel, press the [#] key.
How to program the address of the keypads KPD-860 / KPD-860RF / G-LC-
D732/G-LCD732RF
1. Press the programming button [ ] and scroll with the scroll buttons [ ]
to option [4] Keypad Programming, then press [ ].
2. Then press the [8] key, you will not nd this option by navigating with the scroll-
buttons as it has been hidden for the purpose of avoiding unwanted programming.
3. Enter a new address (1 to 8) for that keypad. Or press the [#] key to exit pro-
gramming. After addressing all keypads, enable them in command [298] in the
installer programming. The control panel will monitor all keypads and modules
registered to the system bus.
NOTE: To enter installer programming you must do so from the keypad with ad-
dress1, as this is the only address that is enabled at the factory.
2.6 Monitoring
Only registered modules are monitored by the panel.
Supervision operates at all times so that the PC-732G® panel can indicate a fault
if a module is removed from the system or simply stops working. To check which
modules are currently connected and supervised, check installer programming
commands [298] and [299].
A registered module that was not present will produce a fault condition and the
Fault/System indicator [ ] on the keypad will illuminate. This condition may be
due to one of the following circumstances:
• The module is no longer connected to the BUS-D485.
• There is a problem with the BUS-D485 wiring.
• The module, or keypad, is more than 200m from the panel.
• Module or keypad does not have sucient power supply
• The module or keypad is damaged.
• There is more than one device with the same address.
For more information concerning module monitoring issues,
see section 3.5 “Commands [ ]” on page 8.
2.7 Remove Modules
The PC-732G® Panel must be recongured to no longer supervise a module that
has been removed from the system. To remove the module, disconnect it from the
Bus and disable it in the [298] or [299] installer programming command.
2.8 Zone Wiring
For a complete description of the mode of operation of the dierent types of
zone, see section 5.2 “Programming Zones”. There is only one way to install the
zone circuits and that is by using a resistor at the end of the 2200 ohm line.
The control panel can accept and monitor NC or NO detectors.
NOTE: Any zone on the main panel can be programmed as a 24 Hour Fire. Zones
so programmed will generate a trouble when the circuit is open.
Resistors (2200 ohms) at End of Line (RFL)
Using the end-of-line resistors, note the dierent variants for connecting the zone
circuit.
NOTE: This is the appropriate connection mode for Normally Open (N.O.) or
Normally Closed (N.C.) sensing contacts.
2.9 Fire Zone Wiring
4-wire smoke detectors
All re zones shall be installed in accordance with the following
diagram:
2.10 Keyboard Area
Each keypad has a zone input, to which a sensing device (such as a magnetic door
contact, motion sensor, etc.) can be connected. This saves you having to run wires
to the control panel for that device.
To install the keypad, open the plastic enclosure of the unit and locate the six ter-
minals on the keypad PCB terminal block. Connect the four BUS-D485 wires from
the control panel, red wire to [+], black to [-], blue to [A] and white to [B]. To con-
nect the zone, use an end-of-line resistor also 2200 ohms between the [Z] terminal
and the [-] terminal. To power devices that require power, use the power terminals
(the red and black wire) to supply power. Connect the red wire to the [+] terminal
and the black wire to the [-] terminal.
NOTE: End-of-Line Resistors must be placed at the sensing device at the end of
the circuit, not at the keypad. This zone cannot be programmed as a supervised
re zone.
RFL
2.2K
Zona
Zona
+ Aux.
PGM
C
C
C
RFL
2.2K
Zona C
RFL
2.2K
Zona C
RFL
2.2K
RFL
2.2K
Zona C
CONTACTO NORMAL
CERRADO CON RFL
CONTACTO NORMAL
ABIERTO CON RFL
CONEXIÓN DETECTOR DE HUMO DE 4 HILOS CON REAJUSTE
Detector
de humo
Detector
de humo
CONTACTO NORMAL
ABIERTO Y NORMAL
CERRADO CON RFL
2 CONTACTOS NORMAL
ABIERTOS Y 2 CONTACTOS
NORMAL CERRADOS CON RFL
+
-
+
-
Panel de Alarma
Rele
RFL
2.2K
Zona
Zona
+ Aux.
PGM
C
C
C
RFL
2.2K
Zona C
RFL
2.2K
Zona C
RFL
2.2K
RFL
2.2K
Zona C
CONTACTO NORMAL
CERRADO CON RFL
CONTACTO NORMAL
ABIERTO CON RFL
CONEXIÓN DETECTOR DE HUMO DE 4 HILOS CON REAJUSTE
Detector
de humo
Detector
de humo
CONTACTO NORMAL
ABIERTO Y NORMAL
CERRADO CON RFL
2 CONTACTOS NORMAL
ABIERTOS Y 2 CONTACTOS
NORMAL CERRADOS CON RFL
+
-
+
-
Panel de Alarma
Rele

8
2.11 Expanding Modules Zones
Each expander module has 8 zones. The maximum number of expander modules
supported by the panel is 3, and up to 24 additional zones can be obtained in addi-
tion to the 8 on the main panel board. Each expander module must be assigned an
address, so 3 addresses are available. For an expander module to function, it must
be enabled. Enable the expander modules in the command [299] “Enable modules,
options [1], [2] and [3]. The expander modules have 8 zone inputs. To assign a zone
number to each input, commands [220]-[227] must be programmed for expander
module zones with address 1, [228]-[235] for expander module zones with address
2 and [236]-[243] for expander module zones with address 3.
SECTION 3: Keyboard Commands
Use any system keypad to enter commands and/or program the PC-732G® securi-
ty system. The LCD keypad provides a menu of options on the liquid crystal display
and uses a combination of LEDs and display legends to communicate system
status to the user.
The [ ] indicator functions as a Fault indicator. Simultaneously, these conditions
will be shown with legends on the LCD display.
The [ ] indicator alerts the user that all zones in the partition are secured and the
system is ready to arm.
The 1 2 3 4 indicators show the armed or disarmed status of the dierent parti-
tions. If a partition is armed, the indicator for that partition will be lit.
The PC-732G® User Instruction Manual provides a basic guide to arming and
disarming the system, bypassing zones, and performing user functions from the
keypads.
The following sections provide additional details about these functions.
3.1 Arming and Disarming
For the operation of arming and disarming, please refer to the PC-732G® User
Instruction.
NOTE: The Event Log will record “Armed in Present Mode” or “Armed” in Away
Mode” every time the system is armed. If a delayed type zone remains open until
the end of the exit delay time, and forced arming is disabled, the entry delay will
begin. At the end of the entry delay period, if the system has not been disarmed,
an alarm will be generated.
3.2 Arming in Present Mode
When arming the system in present mode, zones previously dened as interior are
auto-bypassed (see section 5.2 “Programming Zones”).
3.3 Automatic Arming and Disarming
The system can be programmed for Automatic Arming at a time specic every day
if it is in the disarmed condition.
The Automatic Arming schedule is independent for each partition, thus which there
are 4 commands that refer to Automatic Arming Schedule [280] - [281].
The system can also be programmed for Automatic Disarming. The Automatic
Disarming schedule is also independent for each partition, so there are also 4 com-
mands that refer to the Automatic Disarming Schedule [284] - [285].
Finally, you can dene the days of the week on which you want it to take place.
Automatic Arming and Disarming of each of the partitions, the commands [290] -
[291] refer to Automatic Arming Days of each partition while [294] - [295] refer to
Automatic Disarming Days of each partition.
When the system’s internal clock matches the Auto-Arming Time, the PC-732G®
panel will check the system status.
If the system is armed, the panel will do nothing until the next day at the Auto-Ar-
ming Time, and check the system again.
If the system is disarmed at the time of Auto-Arming, the panel will sound the
buzzer on all keypads for one minute.
If a Valid Access Code is entered, Auto Arming will be cancelled.
NOTE: If Auto Arm is cancelled, the number of the user who cancelled the auto
The event will be recorded in the Event Log.
If no code is entered, the panel will arm automatically.
If a zone is opened, the panel will transmit a Partial Closing Reporting Code, this
will indicate to the monitoring station that the system is not fully secured. If the
zone is restored, the panel will add the zone back to the system.
NOTE: Auto Arming can be cancelled only by entering a valid access code on any
keypad.
3.4 Forced Armed
Force arming allows the system to be armed even when zones are open (not
secured).
When armed with open zones, at the end of the exit time, the panel will
will be bypassed until the zone is closed. If the zone is closed, it shall be automa-
tically restored to the system, whereby an alarm shall be generated if the zone is
opened again.
There are two dierent forced armings that can be enabled, forced arming by
keypad or keyswitch and forced arming for automatic and/or remote arming.
3.5 Commmands [ ] (Keypads KPD-800 / G-LED732)[ ]
[ ][0] Quick Arm/Disarm: If the “Quick Arm/Disarm” option is enabled, the sys-
tem will arm in Away mode without the need to enter a user code.
If the system is in exit delay, entering this command will immediately disarm the
system, without the need to enter a valid user code.
The quick disarm option only works during the exit delay time. After the exit delay
has expired, the quick disarm function will remain disabled.
[ ][1] Bypass Zones: This command is similar to pressing the [Bypass] key.
of the KPD-860/KPD-860RF/G-LCD732/G-LCD732RF keypads.
[ ][2] Fault Display: The panels constantly monitor the various fault conditions.
If a fault condition is present, the Fault indicator will ash (see Fault Index Table).
[ ][3] Alarm Memory for the last activation period: The alarm memory indica-
tes the zones tripped during the last activation period. To view the alarm memory,
press [ ] [3].
[ ][4] Arming in Delayed Stay mode: The system will arm, leaving
inhibited all zones congured as Inner Zones.
[ ][5]: Future Use
[ ][6]: Future Use
[ ][7] Keypad Control of Programmable Outputs: The PGM outputs can be
controlled from any keypad. To do this, enter [ ] [7] followed by your user code,
then select PGM’s and PGM-W with the scroll keys.
Note: The user code shall have the PGMs / PGM-Ws control option enabled.
Note: PGM-W/MA-220G can only be used from KPD-860RF/G-LCD732RF.
[ ][8] Enter Programming mode: This command is similar to pressing the [Pro-
gram] key on the KPD-860/KPD-860RF/G-LCD732/G-LCD732RF keypads.
[ ][9] Instant Stay Arming: The system will arm, bypassing all zones congured
as Stay zones. Zones congured as Delayed Zones will operate without delay,
where by the delayed zones will operate as Instant Zones.
Commands [ ] (Keypads KPD-860 / KPD-860RF / G-LCD732 / G-LCD732RF)
The [ ] key commands provide an easy way for the user to access basic system in-
formation. The LCD display provides written information, guiding the user through
each command.
Use the arrow keys [ ] to scroll through the information. provided.
[ ][1] View Bypassed Zones: Use the [ ][1] keypad command to display the
bypassed zones.
NOTE: Use the scroll keys to display all zones.
[ ][2] Fault Display: The panels constantly monitor for various fault conditions.
If a fault condition is present, the Fault indicator will ash. To display faults, enter
[ ] [2]. Use the arrow keys [ ] to move around the dierent fault conditions
present.
[ ][3] Alarm Memory for the last activation period: The alarm memory
indicates the zones tripped during the last activation period.
To view the alarm memory, press [ ] [3].
NOTE: Each time a partition is armed, the alarm memory of the zones in that
partition will be cleared.
[ ][4] View Open Zones: To view the zones that are open, enter [ ][4].
Use the [ ] arrow keys to scroll through the dierent open zones.
[ ] [5] View Status of Keypad Tampers: To view the status of the keypad tam-
pers, enter [ ] [5]. Use the arrow keys [ ] to scroll through the dierent open
tampers.
[ ][6] View Zone Tampers Status: To view the status of the zone tampers, enter
[ ][6]. Use the [ ] arrow keys to scroll through the dierent open tampers.
[ ][7] Keypad Control of Programmable Outputs: PGM outputs can be contro-
lled from any keypad. To do so, enter [ ] [7] followed by your user code.
Note: The user code shall have the pgms control option enabled.
[ ] [8] Viewing Low Battery Zones: To view the low battery status of zones, enter
[ ] [8]. Use the [ ] arrow keys to scroll through the dierent low battery zones.
[ ][9] Viewing Supervisory Faulted Zones: To view supervisory faulted zones,
enter [ ][9]. Use the [ ] arrow keys to scroll through the dierent zones.
3.6 Functional Keys:
There are 6 functional keys on the KPD-860/KPD-860RF/G-LCD732/G-LCD732RF
keypads. Away arming, present arming, disarming, event memory, zone bypassing
and programming.
Arm Absent [ ]
The system will arm in Away mode. Enable the Quick Arm/Disarm feature (by pro-
gramming command [271], option [3]) to have this key function without the need
to enter an access code. If the Quick Arm option is not enabled, the user will have
to enter an access code before the “Away Arming” function will be executed.

9
Arm Present [ ]
The system has two dierent present arming modes, delayed present arming and
instantaneous present arming. The dierence between them is that in instant
present arming, delayed zones behave as instant zones, without allowing an entry
delay. Enable the Quick Arm/Disarm feature (by programming command [271], op-
tion [3]) to have this key functional without the need to enter an access code. If the
Quick Arm option is not enabled, the user will have to enter an access code before
the “Stay Arming” function will be executed.
Disassemble [ ]
This key allows you to quickly indicate that you wish to disarm the system. Enable
the Quick Arm/Disarm feature (by programming command [271], option [3]) to
have this key functional without the need to enter an access code. If Quick Disarm
is not enabled, the user will have to enter an access code before the “Disarm”
function will be executed.
NOTE: The Quick Disarm option only works on partitions that are in exit delay.
Bypasear Zones [ ]
Use this key to enter the zone bypass menu. If the “Zone Bypass
Zones without code” is disabled, you must enter your user code.
Event memory [ ]
Use this key to choose between the alarm memory and event memory options. Use
the [ ] keys to select between one option or the other.
Programming [ ]
The system allows you to choose from a number of programming options, some of
which are: Codes, Clock/Date, Zone Chime, Keypad, Panel, PC-Link, RF Devices and
Communicators.
SECTION 4: How to Program
The following section of the manual describes the function of Installer Program-
ming and how to program the dierent commands.
NOTE: Read the following section very carefully before you start programming.
We also recommend completing the Programming Sheets section before
programming the control panel.
4.1 Installer Programming
Installer Programming is used to program all options of the PC-732G® panel. The
default Installer Code is [5555] but can be changed to prevent unauthorised access
to programming.
1. From any keypad, press the [ ] key followed by option 5 [PANEL], then enter
the Installer Code. The keypad will display the message “Entering Installer prog”.
NOTE: If you are attempting to program from a KPD-800/G-LED732 keypad, you
must enter the [ ] [8] command instead of the [ ] key.
2. Enter the three digits corresponding to the number of the command you wish
to program. The keypad will display the current programming of the command
entered.
3. Modify the programming at the desired command positions and press
Press the [OK] key to save the changes.
If you made a mistake in the data entered and do not wish to record it, press the
[#] key to quit programming the command.
Select a new command and re-enter the information correctly.
NOTE: If you are programming from a KPD-800 / G-LED732 keypad, you must enter
the three digits of the command followed by the command data. When the last
digit of the command is entered, the command will be saved and awaiting a new
programming command.
If you are programming the data for a command, you can cancel the data recording
by entering the [#] key. To exit programming press [#] + 1.
4.2 Programming Special Data
There are sections that require programming of hexadecimal data or simple
alphanumeric characters. To do this, simply press the [ ] key and the keypad
will display a screen with the dierent special data that can be programmed into
the command entered. Select the data you wish to enter and press the [OK] key.
This value will be automatically inserted and you will continue programming the
command you were programming.
NOTE: If you are programming from a KPD-800 / G-LED732 keypad, you should
refer to the tables that refer to the programming of the special data.
4.3 See Programming
When you enter a valid command number, the keypad will display all programming
that has that command. Use the [ ] arrow keys to scroll through all the data
being displayed. Press the [ ] key to view the next command programming or
press the [#] key to exit command programming.
NOTE: Programming can only be viewed from the keypad models.
KPD-860 / KPD-860RF / G-LCD732 / G-LCD732RF
SECTION 5: Programme Descriptions
The following section explains the operation of all programmable functions and
options.
It also provides a summary of the corresponding locations of
programming.
5.1 Programming Security Codes
There are 5 codes which can be programmed by the installer in the Installer
Programming function: the Master user code, the Installer code, 2 duress codes for
the dierent partitions and the wired programming code (Pc-Link). All other access
codes can be programmed by the same Master code (User 32) through the User
Codes programming.
Users can program user codes if they have enabled the attribute
“User Code Programming”.
The master code can also be programmed by the user as a user code (32).
Duress codes can be programmed as users 37-38.
5.2 Program Zones
Zones 1-8 are enabled by factory default. Disable unused zones,
or enable additional zones in programming commands [070]-[101].
The zone denitions set out how they operate.
On the other hand, each zone has its own individual attributes, which allow further
customisation of the zone’s behaviour.
Program the zone attributes in the commands [110]-[141] (see section 5.3 “Zone
Attributes”).
Zone Denitions
[00] Null Zone
The zone is bypassed. Unused zones must be programmed as bypassed zones.
[01] Delayed Zone 1
This type of zone, normally used by entry/exit doors, can be violated during the
exit delay period without causing an alarm. Once the exit delay has expired,
opening the zone will start the entry delay counter. During the entry delay period,
the keypad buzzer will sound a continuous tone to warn the user that the system
should be disarmed. If the PC-732G® panel is disarmed before the entry delay
expires, an alarm will not be generated. The entry delay time1 is programmed in
the [151] command.
[02] Delayed Zone 2
The mode of operation is identical to that of Delayed Zone1, except that its
time is programmed independently in the command [152].
[03] Delayed Zone 3
The mode of operation is identical to that of Delayed Zone1, except that its
time is programmed independently in the command [153].
[04] Delayed Zone 4
The mode of operation is identical to that of Delay Zone1, except that its time is
programmed independently in the command [154].
[05] Instant Zone
This zone type causes an instant alarm if violated when the PC-732G® panel is
armed. Typically, this zone is used for windows, patio doors or other perimeter
zones, and for glass break detectors.
This type of zone only works with the system armed.
[06] Safe / Access Control Area
The Safe/Access Control zone generates an instant arming on the partition to which
it belongs at the moment the partition is restored. The timer “Auto Arming Partition
with Safe/Access Control Zone” is used to arm the partition.
sets the maximum time a partition with safe/access control zones can remain
disarmed, after which time the partition will be automatically armed. In order for
the partition to be armed, the partition must be in the “Ready to Arm” condition. It
is recommended that these partitions do not have “Force Arming” enabled.
Anti-Entruder System:
Working with Safe/Access Control zones, an infrared barrier can be installed behind
a vehicle barrier, once the mobile passes through the infrared barrier the partition
is armed, therefore, if a person or car wished to enter behind the car that has just
entered, an alarm would be generated.
[07] 24 Hs Zone
If this zone is violated, an instant alarm will be generated, regardless of whether
the system is armed or disarmed.

10
[08] Tamper Zone (24 Hs)
This type of zone is used to prevent dismantling/disassembly of devices in an alarm
installation.
Triggering this zone will generate an instant alarm, regardless of whether the
system is armed or disarmed.
[09] Assault Zone (24 Hs)
If this zone is violated, an instant alarm will be generated, regardless of whether
the system is armed or disarmed.
Normally, this zone is congured as a quiet zone.
[10] Medical Emergency Area (24 Hs)
If this zone is violated, an instant alarm will be generated, regardless of whether
the system is armed or disarmed.
[11] Fire Zone (24 Hs)
If this zone is violated, an instant alarm will be generated, regardless of whether
the system is armed or disarmed. If the zone is short-circuited, an alarm will be
generated, while if the zone is open, a fault will be generated.
This zone can be programmed with pulsed or temporary sound three times.
(See command [270], option [4] “Fire Siren Sound”).
[12] Water Loss Zone (24 Hs)
This type of zone is used in places where ooding is to be prevented. If this zone is
breached, an instant alarm will be generated, regardless of whether the system is
armed or disarmed.
[13] Follower Zone
This zone will not cause an alarm if violated during an entry delay period. If the
delay period expires, the zone will generate an alarm.
If the zone is tripped without the panel rst being in the entry delay condition, an
instant alarm will be generated.
This type of zone only works with the system armed.
[14] Inner and Follower Zone (Self-cancelling)
This zone will not cause an alarm if violated during an entry delay period. If the
delay period expires, the zone will generate an alarm.
If the zone is tripped without the panel rst being in the entry delay condition, an
instant alarm will be generated.
Zones congured as indoor shall be self-canceling when the user arms the system
in present mode, to allow free movement within the enclosure.
[15] Keyswitch Zone for Partition N° 1
Momentary violation of this zone will alternately arm or disarm the status of Parti-
tion N°1.
[16] Keyswitch zone for Partition N° 2
Momentary violation of this zone will alternately arm or disarm the status of Parti-
tion N°2.
5.3 Zone Attributes
Additional zone attributes can be programmed to make the operation of a zone for
a specic application. The following attributes are programmable for each zone:
Swinger Shutdown: This attribute determines whether the zone will auto-cancel
for reporting and siren triggering once its alarm counter limit is reached.
(See command [254] Zone Alarm Counter).
Bypassable: This attribute determines whether or not the zone can be manually
bypassed (see section 3.6 Functional Keys).
Partition Assignment No. 1: This function denes the zone as belonging to the
zone. to partition N° 1.
Partition Assignment No. 2: This function denes the zone as belonging to the
zone.
This attribute determines whether the zone will activate (Audible) or not the alarm
output (Silent).
Response rate: This attribute determines whether the zone operates at 50mS or
50mS. 500 mS. Zone Attributes are congured in Commands [110] - [141].
5.4 Cruce zones
The control panel includes a cross zone option that requires triggering on two or
more zones within a programmable time period to initiate an alarm transmission
sequence.
On the other hand, if the “Double trip on same zone” option is enabled, it will
generate an alarm transmission sequence if the zone is violated twice during the
programmed time period. It will also generate the same eect if the zone remains
open for the entire time period programmed as “Cross Zone Time Interval”. See
Commands [142]-[145] and [163].
5.5 Zones of Group Inhibition
Zones dened as group inhibit zones can be automatically inhibited by pressing the
[ ] key for more than 3 seconds. See Commands [146]-[149].
NOTE: Only available on KPD-860/KPD-860RF / G-LCD732/ G-LCD732RF keypads.
5.6 Keyboard Zone Assignment
Los teclados KPD-800/KPD-860/KPD-860RF/G-LED732/G-LCD732/G-LCD732RF
have a zone input to which a device, such as a door contact, can be connected. (See
Section 2.10 “Keypad Zone” for more information on wiring).
Once the keypad zones are installed, assign the zones in programming commands
[200]-[207].
NOTE: If the zones assigned to the keypads are between the zones 1-8, they will
override the PC-732G® backplane zones.
5.7 Download Information
The required Download Information software is AC4.
Downloading information can be done in 4 dierent ways:
• By means of a PC-Link adapter cable and the PC, without the need for a modem.
• Using the 3G-COM-G / 4G-MAX-G module as a programmer.
• Using the IP-500G module as a programmer.
5.8 PGM Output Options
Program the programmable outputs (PGM1 and PGM2 on the main board). by
selecting one of the output options listed below.
[00] Partition No. 1 Armed Indication: The output will remain on as long as
partition 1 is armed.
[01] Partition No. 2 Armed Indication: The output will remain active while parti-
tion 2 is armed.
[04] Output command held: The output can be used as a switch. Its change of
state can be controlled via a keypad (see section 3.4 “[ ][7]” Keypad Control of
Programmable Outputs”),
through the use of TX-500 keyfobs (have RF LCD Keypad), with the use of AC4
software or through the Garnet Control APP (have IP-500G/ 3G-COMG/ 4G-MAX-G
communicator).
Note: The output can also be controlled by sending a text message via
of the 3G-COM-G / 4G-MAX-G / 4G-MAX-G module.
[05] Output command Pulse: The output delivers a pulse. The pulse can be
triggered via a keypad (see Section 3.5 “[ ][7]” Controlling Programmable Outputs
by Keypad” on page 8), by using a telephone (See Section 6.0 “Telephone Remote
Control” on page 12) or by using the AC4 software.
Note: The output can also be controlled by sending a text message to via
3G-COM-G / 4G-MAX-G module.
[07] Pulse on siren trigger: The PGM will pulse each time the siren is triggered.
siren output is triggered.
[08] Partition Siren No. 1: The PGM becomes a partition siren. Each time an alarm
occurs in that partition, the PGM will activate for the partition’s programmed siren
time period.
[09] Partition Siren No. 2: The PGM becomes a partition siren. Each time an alarm
occurs in that partition, the PGM will activate for the partition’s programmed siren
time period.
[13] Mobile Data communication failure: The PGM shall be activated upon Mobi-
le Data communication failure.
[15] Battery Failure: The PGM will activate in the event of a battery failure.
[16] Mains Failure: The PGM shall be activated in the event of a mains failure.
[17] Auxiliary Power Failure: The PGM will activate on Auxiliary Power Failure: The
PGM will activate on Auxiliary Power Failure. auxiliary output power supply.
[18] Smoke Sensor Reset: The PGM will always remain on and turn o for 3
seconds after the [ ][7] command is entered (see section 3.5 “[ ][7”] Keypad
Programmable Output Control”).

11
NOTE: PGM outputs cannot be completely disabled in installer programming.
To completely disable a PGM output, you must remove all wiring from the PGM
output.
5.10 Siren Output
The siren shall be silenced after the number of minutes programmed for the parti-
tion siren time.
Each partition has its own independent bell time (See commands [159]- [160]). The
panel supervises the siren output in the event of a trip or short circuit condition.
5.11 Periodic Test Report
To ensure that the communication link with the monitoring station is functioning
properly, program the panel to send a test signal periodically.
The test report can be programmed to send signals in minutes, hours or days (see
command [360] option [1] “Test report transmission counters”).
5.12 Armed System Follower Test Report
The panel can be programmed to send a follower test report during the time it is
armed. This test can be programmed with a dierent period than the periodic test
report. Normally, the period of this test is programmed in a shorter time than the
periodic test, thus obtaining a greater check on the panels that are armed (See
command [360] option [2] “Test report transmission counters”).
5.13 Manual Test Report
The manual test report is generated by holding down the “0” key on the key for a
period of time longer than three seconds.
5.14 Retransmission of Test Report and/or Network Failure in the event of a
communication failure.
In many cases, when the power goes out in a certain area, the panels start transmi-
tting mains failure to the monitoring station.
If the number of subscribers who need to report such an event is too high, colli-
sions may occur, resulting in communication failures and the event cannot be sent
successfully. To solve this problem, the panel can be programmed to retry to send
the test report or network failure report after a specied time. The retransmission
time is programmed in the command [170] “Re-Transmission Delay of Test and
Network Failure Report on Failure to Send”.
5.15 Fire, Medical and Panic Keys
Emergency keys are available on all keypads. These keys must be pressed and held
for three seconds to activate. This delay is designed to prevent activation accidents.
The emergency keys can be congured as audible or silent, independently and for
each keypad (See commands [190]-[197] options [5], [6] and [7]).
5.16 Events Report
The PC-732G® panel stores the last 512 events that occurred on the system. The
Event Memory contains the date and time of each event, along with the zone num-
ber, user number, and any other information pertaining to the event.
5.17 Zone Circuit Response
The normal circuit response time for all zones is 500 milliseconds. The PC-732G
panel will not consider a zone violated unless it is violated for at least 500 millise-
conds.
Zones 1-8 on the PC-732G panel board can be programmed for
a fast circuit response (under 50 mS).
(See commands [110]-[115] option [8] “Response Speed”).
5.18 Communication Scenarios
Your system has several means of communication for reporting, among these,
we can highlight the possibility of reporting to dierent IP addresses, through the
3G-COM-G / 4G-MAX-G and IP-500G modules, sending notications, etc.
to the users and/or monitoring station, using the 3G-COM-G/ 4G-MAX module.
G. Communication scenarios are an orderly alternative way of organising commu-
nication communications.
The PC-732G® panel has 2 communication scenarios:
Call Scenario N° 1 (Reports with Backups): This scenario has one main output me-
dium and seven dierent backup possibilities.
(See command [370] “Call Scenario No. 1”).
Call Scenario No. 2 (Simultaneous Reporting): This scenario is used for the same
event to go out by several dierent means of communication (see command [371]
“Call Scenario No. 2”).
5.19 How to operate communication scenarios
For ease of understanding, we will cite dierent examples of operation:
1) The system shall report the events to the monitoring centre through the
3G-COM-G / 4G-MAX-G module, via the Wi network of the site, in case of not being
able to report such events, it shall report through the same equipment by means
of the cellular network (mobile data) of the chip, if the equipment has one.
This is a case of Scenario N°1, as it involves the use of backups.
Call scenario No. 1 is programmed in the command [370], its programming
should be: [370] [4][3][5][0][0][0][0][0][0][0].
Position N°3 has the option [5] loaded, which indicates that the backups are termi-
nated.
2) The system shall report the event to the monitoring centre and to the end user
through the 3G-COM-G / 4G-MAX-G module, via the chip’s cellular network (mobile
data) simultaneously.
This is a case of Scenario N°2, as it must send an event by various means. Scenario
N°2 is programmed in the command [371], its programming should be:
[371] [0][0][0][1][0][1][0][0].
Position N° 4 has a [1], which enables reporting by mobile data to monitoring, and
position N° 6 enables reporting for the event to reach the end-user via the App.
NOTE: The format “Residential” is valid only for scenario N° 2.
5.20 Reset to Factory Defaults
Sometimes it will be necessary to reset the panel to Factory settings,
To do so, please follow the steps below:
1. Enter Installer Programming.
2. Enter the command [600].
3. Conrm that you wish to reset the panel programming by entering the [1] key.
SECTION 6: Programming wireless devices
The PC-732G® alarm panel has the ability to control up to 24 wireless sensors, 64
keyfobs and 4 PGM-W/MA-220G.
Compatible motion sensors are:
DGW-500 and DGW-500-PET for pet immunity.
The DGM-300 sensor is a wireless magnetic sensor with the ability to accept a
second N/C loop with one or more external magnetic detectors. For more informa-
tion, refer to their respective manuals.
NOTE: Programming of wireless devices can only be performed if has a KPD-
860RF/G-LCD732RF keypad.
C
Rele
+ AUX -
PGM1 PGM2 PGM3 PGM4
+ AUX -
PGM1 PGM2 PGM3 PGM4
Resistor
+ -
+
-
Bateria
Fusible
Conexionado de PGM como Sirena de Interior
5.12 Conexionado de PGMs
Conexionado de un Led
5.9 Connection of PGMs - Wiring of an LED

12
6.1 How to twin a wireless sensor
To twin a sensor, the following steps must be carried out:
1) Be sure to remove the battery from the sensor.
2) Press the [ ] key on the keypad.
3) Select [7] RF Disp.
4) Enter the installer code.
5) Choose option [1] Grab Sensor.
6) Indicate the memory location where you want to record the device.
The positions
The available memory slots are 01-24.
7) The keypad will indicate that it is searching for the sensor.
8) Insert the battery into the sensor. Remember to check for correct polarity.
9) Wait for the keypad to conrm that the sensor has been successfully engraved.
and then press the [ ].
10) If you wish to continue recording more sensors, repeat the steps from point 6.
Otherwise, press the [#] key to exit the sensor recording option.
6.2 How to pair wireless key fobs
To twin a wireless key fob, the following steps must be carried out:
1) Press the [ ] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [2] Record. Key Ring.
5) Indicate the memory location where you want to save the key fob. The memory
locations memory available are 01-64.
6) Press and hold any key on the key fob and wait for the keypad to conrm.
your recording. Then press the [ ] key on the keypad.
7) If you wish to continue recording more key fobs, repeat the steps from option 5
onwards. If you wish to exit the key fob recording option, press the [ ] key.
6.3 How to remove wireless sensors
To remove a wireless sensor, the following steps shall be performed:
1) Press the [ ] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [3] Delete Sens.
5) Indicate the memory location of the sensor to be deleted.
6) Conrm that you really want to delete this sensor by pressing the [1] key.
7) Press the [ ] key to accept the deleted sensor conrmation.
8) If you wish to continue deleting more sensors, repeat the steps from point 5.
Otherwise, press the [#] key to exit this option.
6.4 How to remove key rings
To delete a key fob, the following steps must be carried out:
1) Press the [program] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [4] Delete Key Fob. Key Ring.
5) Indicate the memory location of the sensor to be deleted.
6) Conrm that you really want to delete this sensor by pressing the [1] key.
7) Press the [ ] key to accept the deleted sensor conrmation.
8) If you wish to continue deleting more sensors, repeat the steps from point 5.
Otherwise, press the [#] key to exit this option.
6.5 How to verify the correct operation of a wireless sensor
To be sure that a wireless sensor is working correctly, the panel has a function that
evaluates the level of Signal Strength (RSSI) with which the sensor transmits, in this
way, you will be able to know the signal level with which the signals transmitted
by each wireless sensor enabled in your installation arrive. To evaluate the signal
strength of the wireless sensors, the following steps must be carried out:
1) Press the [program] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [5] Test. Sensor.
Each time a sensor generates a transmission, the keypad will indicate the zone
where the sensor is working, the memory location where it is recorded and the
signal level.
6.6 How to display the zones assigned to each sensor
In order to visualise the zones where the dierent wireless sensors work, the
following steps must be carried out:
1) Press the [program] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [6] Zone Assign. Zones.
The keypad will inform you of the memory location where the sensor is stored and
the assigned work zone. To switch to another sensor, use the [ ] scroll keys.
6.7 How to remove all sensors and/or key fobs
To remove all sensors or keyfobs from your system in one step, the following steps
must be performed:
1) Press the [program] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [7] Delete All. All.
5) Choose to delete all sensors by pressing the [1] key or choose to delete all key fobs
by pressing the [2] key.
6) Conrm that you really are sure to delete the selected devices
key and wait for the keypad to indicate that the deletion has been completed.
nished. Press the [ ] key to return to the RF Devices menu.
6.8 How to twin a PGM-W/MA-220G module
1) Make sure that the PGM-W module is without 12 V power supply.
2) Press the [ ] key on the keypad.
3) Select [7] RF Disp.
4) Enter the installer code.
5) Choose option [8] Record PGM-W.
6) Enter the PGM-W number to be recorded (use the [ ] keys to enter the PGM-W
number). select the desired PGM-W number). The available PGM-Ws are 1 to 4.
7) The keypad will indicate that it is searching for the device.
8) Power up the PGM-W module, then press the “SINGLE” button located on the
upper left corner of the module.
9) Wait for the keypad to conrm that the PGM-W has been recorded correctly.
and then press the [#] key.
10) If you wish to continue recording other PGM-W modules, repeat the steps from
point 6 onwards. Otherwise, press the [#] key to exit the PGM-W module recording
option.
6.9 How to remove PGM-/MA-220G modules.
1) Press the [ ] key on the keypad.
2) Select [7] RF Disp.
3) Enter the installer code.
4) Choose option [9] Delete PGM-W.
5) Enter the PGM-W number to be deleted (use the [ ] keys to enter the PGM-W
number). select the desired PGM-W number)
6) Conrm that you really want to delete this module by pressing the [1] key.
7) Press the [ ] key to accept the conrmation of the deleted module.
8) If you wish to continue deleting more modules, repeat the steps from point 5.
Otherwise, press the [#] key to exit this option.

SECTION 8: Reporting Codes Transmitted in Contact ID and SIA
T
ype of Event New event or assembly Restoration or Disassembly New Event or Armed Restoration or Disassembly
Emergency Medical Key 1 1AA 3 1AA MA MH
Fire Emergency Key 1 115 3 115 FA FH
Police Emergency Key 1 12A 3 12A PA PH
Disarmed by Coercion 1 121 - HA -
Zone Alarm 1 13A 3 13A BA BH
Perimeter Alarm 1 131 3 131 BA BH
Indoor Zone Alarm 1 132 3 132 BA BH
Alarm in Zone 24 Hs 1 133 3 133 BA BH
Zone Alarm Input/Output 1 134 3 134 BA BH
Tamper 1 137 3 137 TA TH
Intruder Verication 1 139 - BV -
Unveried Alarm 1 378 - BG -
Assault 1 122 3 122 PA PH
Flooding 1 154 3 154 WA WH
Wireless sensor tamper 1 383 3 383 TA TH
Keyboard Tamper (4) 1 145 3 145 TA TH
Wireless Sensor Monitoring Failure 1 381 3 381 YX YZ
Network Failure 1 3A1 3 3A1 AT AR
Low Battery in Panel 1 3A2 3 3A2 YT YR
System Reset 1 3A5 - RR -
Change of panel programming and/or keyboard texts 1 3A6 - LS -
System Shutdown 1 3A8 - YX -
Power supply Overloaded 1 312 3 312 YI YJ
Siren circuit fault 1 321 3 321 YA YH
Failure in Expander Module (3) 1 333 3 333 ET ER
Failure in 3G-COM-G/4G-MAX-G 1 333 3 333 ET ER
IP-500 failure 1 333 3 333 ET ER
Communication failure 1 354 3 354 YC YK
Jamming (3GCOM-G/4G-MAX-G) 1 344 3 344 HQ XH
Weapon/Disarm 3 4AA 1 4AA OP CL
Weapon/Disarm User 3 4A1 1 4A1 OP CL
Automatic Arming/Disarming 3 4A3 1 4A3 OA CA
Late to assemble/disassemble 1 4A4 3 4A4 OJ CJ
Cancellation 1 4A6 - BC -
Remote arming/disarming (1) 3 4A7 1 4A7 OQ CQ
Key Arming/Disarming 3 4A9 1 4A9 OS CS
Armed Present 3 441 - OP -
Early Arming/Disarming 3 451 1 451 OK CK
Quick Arming/Disarming (2) 3 4A1 1 4A1 OP CL
Auto-Arming Failure 1 455 - CI -
Recent closure 1459 - CR -
Zone Bypass 1 57A 3 57A UB UU
Group Bypass 1 574 3 574 BB BU
Manual Test Report 1 6A1 - RX -
Periodic No-Fault Test Report 1 6A2 - RP -
Periodic Failure Test Report 1 6A8 - RY -
Follower Test Report 1 6A5 - TX -
Clock out of time 1 626 - JT -
Programming login 1 627 - LB -
Programming Output 1 628 - LS -
Clock Programming 1 3A6 - JD -
Mains Failure Auxiliary Source 1 342 3 342 AT AR
Low battery Auxiliary Source 1 338 3 338 YT YR
Link failure 3G-COM-G/4G-MAX-G 1 35A 3 35A YC YK
IP-500 Link failure 1 35A 3 35A YC YK
Low battery in wireless sensor 1 384 3 384 XT XR
Fire Zone Failure 1 373 3 373 FT FJ
13
Contact ID SIA
Arming by 3G-COM-G / 4G-MAX-G is reported as user 70. Arming by local cable (PC-Link) is reported as user 75.
IP-500 arming is reported as user 80.
Quick arming/disarming is reported as user 0.
The keypad supervisory fault is identied by the zone/user number. For example, a keypad fault with address 1 is reported with the zone/user eld equal
to 1. A keypad with address 8 will be reported with the zone/user eld equal to 8.
The monitoring faults of the expander modules are identied through the zone/user eld and the reported values are 9 for expander1 to 11 for
expander2.
Auxiliary source supervision fault is reported with zone/user eld equal to 12.
3G-COM-G / 4G-MAX-G module failure is reported with the zone/user eld equal 13. IP-500 Module failure is reported with zone/user eld equal 14.
3G-COM-G / 4G-MAX-G Link failure is reported with zone/user eld equal to 1.
IP-500 Link fault is reported with the zone/user eld equal to 2.
The keypad tampers are identied in the eld “zone/user number” and the reported values are 41 for the keypad with address 1 to 48 for the keypad
with address 8.

14
SECTION 9: Programming parameters
Command Number 001: Master User Code (User No. 32 )
Default values ------------------------------> 1 2 3 4
0 0 1
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Master User Code
The code must be 4 digits long. Valid values are 0-9. If you program the values
[0000] the code will be overridden.
Command Number 003: Installer Code
Default values ------------------------------> 5 5 5 5
0 0 3
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Installer Code
The code must be 4 digits long. Valid values are 0-9
Command Number 004: Duress Code (Partition No. 1)
Default values ------------------------------> 0 0 0 0
0 0 4
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Duress Code
The code must be 4 digits long. Valid values are 0-9
Command Number 005: Duress Code (Partition No. 2)
Default values ------------------------------> 0 0 0 0
0 0 5
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Duress Code
The code must be 4 digits long. Valid values are 0-9
Command Number 012: Duress Code for Access Control.
Default values -------------------------> 0 0 0 0
0 1 2
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Duress Code
The code must be 4 digits long. Valid values are 0-9
Command Number 017: Wired Programming Code (PC Link)
Default values ---------------------> 1 1 1 1
0 1 7
Positions ---------------------------------------------------> (1) (2) (3) (4)
Digit positions (1) - (4): Programming Code (PC Link)
The code must be 4 digits long. Valid values are 0-9
Command Number 025: User Code Attributes Nº1
Default values ------> 1 0 0 0 1 1 1 0
0 2 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Partition Assignment No. 1
0 = No Control Partition No. 1
1 = Controls Partition No. 1
Digit position (2): Partition Allocation No. 2
0 = No Control Partition No. 2
1 = Controls Partition No. 2
Digit position (3): Future Use
0 = Future Use
1 = Future Use
Digit position (4): Future Use
0 = Future Use
1 = Future Use
Digit position (5): Arming Enabled
0 = Arming Disabled
1 = Arming Enabled
Digit position (6): Disarming Enabling
0 = Disarmed Disabled
1 = Disarmed Enabled
Digit position (7): Enable Zone Bypass and Control PGMs
0 = Zone Bypass and PGM Control Disabled
1 = Zone Bypass and PGMs Control enabled
Digit position (8): Programming of User Codes and Keypad Texts
0 = No Program User Codes
1 = User Codes Programme
Note: The Commands 026 to 057 (User Code Functions) are programmed in the
same way as Command No. 025.
Command Number 026: User Code No. 2 Attributes
Default values ----------------------> 1 0 0 0 1 1 1 0
0 2 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 027: User Code No. 3 Attributes
Default values ----------------------> 1 0 0 0 1 1 1 0
0 2 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 028: User Code No. 4 Attributes
Default values -----------------------> 1 0 0 0 1 1 1 0
0 2 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 029: User Code No. 5 Attributes
Default values -----------------------> 1 0 0 0 1 1 1 0
0 2 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 030: User Code Attributes No. 6
Default values ------------------------> 1 0 0 0 1 1 1 0
0 3 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 031: Attributes of User Code No 7
Default values ------> 1 0 0 0 1 1 1 0
0 3 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 032: User Code Attributes No. 8
Default values ----------------------> 1 0 0 0 1 1 1 0
0 3 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 033: User Code Attributes No. 9
Default values -----------------------> 1 0 0 0 1 1 1 0
0 3 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 034: User Code Attributes No. 10.
Default values ----------------------> 1 0 0 0 1 1 1 0
0 3 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 035: User Code Attributes No. 11
Default values ----------------------> 1 0 0 0 1 1 1 0
0 3 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 036: User Code Attributes No. 12
Default values ---------------------> 1 0 0 0 1 1 1 0
0 3 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 037: User Code Attributes No. 13
Default values ----------------------> 1 0 0 0 1 1 1 0
0 3 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)

15
Command Number 038: User Code Attributes No 14
Positions ----------------------------> 1 0 0 0 1 1 1 0
0 3 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 039: User Code Attributes No. 15
Default values ---------------------> 1 0 0 0 1 1 1 0
0 3 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 040: User Code Attributes No. 16
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 041: User Code Attributes No 17
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 042: User Code Attributes No 18
Default values -----------------------> 1 0 0 0 1 1 1 0
0 4 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 043: User Code Attributes No. 19
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 044: Attributes of User Code No. 20
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 045: Attributes of User Code No 21
Default values -----------------------> 1 0 0 0 1 1 1 0
0 4 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 046: User Code Attributes No. 22
Default values -----------------------> 1 0 0 0 1 1 1 0
0 4 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 047: Attributes of User Code No 23
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 048: User Code Attributes No 24
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 049: User Code Attributes No. 25
Default values ----------------------> 1 0 0 0 1 1 1 0
0 4 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 050: User Code Attributes No. 26
Default values -----------------------> 1 0 0 0 1 1 1 0
0 5 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 051: User Code Attributes No. 27
Default values -----------------------> 1 0 0 0 1 1 1 0
0 5 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 052: User Code Attributes No. 28
Default values ----------------------> 1 0 0 0 1 1 1 0
0 5 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 053: User Code Attributes No. 29
Default values -----------------------> 1 0 0 0 1 1 1 0
0 5 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 054: User Code Attributes No. 30
Default values ----------------------> 1 0 0 0 1 1 1 0
0 5 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 055: User Code Attributes No. 31
Default values ----------------------> 1 0 0 0 1 1 1 0
0 5 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 056: User Code Attributes No Nº 32 (Master)
Default values ----------------------> 1 1 0 0 1 1 1 1
0 5 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 070: Zone conguration Nº 1
Default values -----------------------------------------------------------------------------> 0 1
0 7 0
Positions -------------------------------------------------------------------------------------> (1) (2)
Digit position (1) - (2):
00 = Nil Zone
01 = Delayed Zone 1
02 = Delayed Zone 2
03 = Delayed Zone 3
04 = Time Delay Zone 4 05 = Instantaneous Zone
06 = Safe/Access Control Zone 07 = 24 Hs Zone
08 = Tamper Zone (24 Hs)
09 = Assault Zone (24 Hs)
10 = Medical Emergency Zone (24 Hs)
11 = Fire Zone (24 Hs)
12 = Water Loss Zone (24 Hs)
13 = Follower Zone
14 = Inner and Follower Zone (Self-annulling)
15 = Keyswitch Zone Part No. 1
16 = Keyswitch Zone Part No. 2
17 = Future Use
18 = Future Use
Note: Commands 071 to 101 (Zone Conguration) are programmed as follows
same way as Command No. 070.
Command Number 071: Zone No. 2 Conguration
Default values ------------------------------------------------------------------------------> 1 4
0 7 1
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 072: Zone No. 3 Conguration
Default values ------------------------------------------------------------------------------> 0 5
0 7 2
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 073: Zone No. 4 Conguration
Default values -------------------------------------------------------------------------------> 0 5
0 7 3
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 074: Zone No. 5 Conguration
Default values -----------------------------------------------------------------------------> 0 5
0 7 4
Positions -------------------------------------------------------------------------------------> (1) (2)

16
Command Number 075: Zone No. 6 Conguration
Default values -------------------------------------------------------------------------------> 0 5
0 7 5
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 076: Zone No. 7 Conguration
Default values -------------------------------------------------------------------------------> 0 5
0 7 6
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 077: Zone No. 8 Conguration
Default values ------------------------------------------------------------------------------> 0 5
0 7 7
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 078: Zone No. 9 Conguration
Default values -------------------------------------------------------------------------------> 0 5
0 7 8
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 079: Zone Conguration No. 10
Default values ----------------------------------------------------------------> 0 5
0 7 9
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 080: Zone No. 11 Conguration
Default values -------------------------------------------------------------------------------> 0 5
0 8 0
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 081: Zone No. 12 Conguration
Default values ------------------------------------------------------------------------------> 0 5
0 8 1
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 082: Zone No. 13 Conguration
Default values-------------------------------------------------------------------------------> 0 5
0 8 2
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 083: Zone Conguration No. 14
Default values -------------------------------------------------------------------------------> 0 5
0 8 3
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 084: Zone Conguration No. 15
Default values ----------------------------------------------------------------> 0 5
0 8 4
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 085: Zone Conguration No. 16
Default values ----------------------------------------------------------------> 0 5
0 8 5
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 086: Zone Conguration No. 17
Default values ----------------------------------------------------------------> 0 5
0 8 6
Positions-------------------------------------------------------------------------------------> (1) (2)
Command Number 087: Zone Conguration No. 18
Default values ----------------------------------------------------------------> 0 5
0 8 7
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 088: Zone Conguration No. 19
Default values ----------------------------------------------------------------> 0 5
0 8 8
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 089: Zone Conguration No. 20
Default values -------------------------------------------------------------------------------> 0 5
0 8 9
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 090: Zone Conguration No. 21
Default values --------------------------------------------------------------------------------> 0 5
0 9 0
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 091: Zone Conguration No. 22
Default values -------------------------------------------------------------------------------> 0 5
0 9 1
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 092: Zone Conguration No. 23
Default values -------------------------------------------------------------------------------> 0 5
0 9 2
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 093: Zone Conguration No. 24
Default values -------------------------------------------------------------------------------> 0 5
0 9 3
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 094: Zone Conguration No. 25
Default values -------------------------------------------------------------------------------> 0 5
0 9 4
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 095: Zone Conguration No. 26
Default values -------------------------------------------------------------------------------> 0 5
0 9 5
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 096: Zone Conguration No. 27
Default values -------------------------------------------------------------------------------> 0 5
0 9 6
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 097: Zone Conguration No. 28
Default values -------------------------------------------------------------------------------> 0 5
0 9 7
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 098: Zone Conguration No. 29
Default values---------------------------------------------------------------------------------> 0 5
0 9 8
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 099: Zone Conguration No. 30
Default values --------------------------------------------------------------------------------> 0 5
0 9 9
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 100: Zone Conguration No. 31
Default values--------------------------------------------------------------------------------> 0 5
1 0 0
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 101: Zone Conguration No. 32
Default values --------------------------------------------------------------------------------> 0 5
1 0 1
Positions -------------------------------------------------------------------------------------> (1) (2)
Command Number 102: Zone Conguration No. 1
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)

17
Digit position (1): Self-cancellation by Repeated Alarms
0 = Disabled
1 = Enabled
Digit position (2): Bypass Zone
0 = Zone cannot be Bypassed
1 = Zone can be Bypassed
Digit position (3): Partition Assignment No. 1
0 = Zone does not Belong to Partition No. 1
1 = Zone Belongs to Partition No. 1
Digit position (4): Partition Assignment Nº 2
0 = Zone does not Belong to Partition No. 2
1 = Zone Belongs to Partition No. 2
Digit Position (5): Future Use
0 = Future Use
1 = Future Use
Digit position (6): Future Use
0 = Future Use
1 = Future Use
Digit position (7): Sound
0 = Silent Zone
1 = Audible Zone
Digit position (8): Response Speed
0 = Slow Response (500 mS)
1 = Fast Response (50 mS)
Note: Commands 111 through 141 (Zone Attributes) are programmed in the same
manner as Command No. 110.
same as Command No. 110.
Note: Only zones 1-6 can have fast response speed.
Command Number 111: Zone Conguration No. 2
Default values-----------------------> 1 1 1 0 0 0 1 0
1 1 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 112: Zone Conguration No. 3
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 113: Zone Conguration No. 4
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 114: Zone Conguration No. 5
Default values------------------------> 1 1 1 0 0 0 1 0
1 1 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 115: Zone Conguration No. 6
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 116: Zone Conguration No. 7
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 117: Zone Conguration No. 8
Default values -----------------------> 1 1 1 0 0 0 1 0
1 1 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 118: Zone Conguration No. 9
Default values-----------------------> 1 1 1 0 0 0 1 0
1 1 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 119: Zone Conguration No. 10
Default values ----------------------> 1 1 1 0 0 0 1 0
1 1 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 120: Zone Conguration No.11
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 121: Zone Conguration No. 12
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 122: Zone Conguration No. 13
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 123: Zone Conguration No. 14
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 124: Zone Conguration No. 15
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 125: Zone Conguration No. 16
Default values ------------------------> 1 1 1 0 0 0 1 0
1 2 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 126: Zone Conguration No. 17
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 127: Zone Conguration No. 18
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 128: Zone Conguration No. 19
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 129: Zone Conguration No. 20
Default values -----------------------> 1 1 1 0 0 0 1 0
1 2 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 130: Zone Conguration No. 21
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 131: Zone Conguration No. 22
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 132: Zone Conguration No. 23
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 133: Zone Conguration No. 24
Default values ----------------------> 1 1 1 0 0 0 1 0
1 3 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)

18
Command Number 134: Zone Conguration No. 25
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 135: Zone Conguration No. 26
Default values ------------------------> 1 1 1 0 0 0 1 0
1 3 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 136: Zone Conguration No. 27
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 137: Zone Conguration No. 28
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 138: Zone Conguration No. 29
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 139: Zone Conguration No. 30
Default values -----------------------> 1 1 1 0 0 0 1 0
1 3 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 140: Zone Conguration No. 31
Default values -----------------------> 1 1 1 0 0 0 1 0
1 4 0
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 141: Zone Conguration No. 32
Default values -----------------------> 1 1 1 0 0 0 1 0
1 4 1
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Command Number 142: Crossing Zones ( 1 to 8 )
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 2
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 1
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 2
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 3
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 4
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 5
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 6
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 7
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 8
0 = Disabled
1 = Enabled
Note: Crossover zones only work in zones dened as Snapshots,
Followers or Interiors.
Command Number 143: Crossing Zones ( 9 to 16 )
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 3
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 9
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 10
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 11
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 12
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 13
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 14
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 15
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 16
0 = Disabled
1 = Enabled
Note: Crossover zones only work in zones dened as Snapshots,
Followers or Interiors.
Command Number 144: Crossing Zones (17 to 24)
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 4
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 17
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 18
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 19
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 20
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 21
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 22
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 23
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 24
0 = Disabled
1 = Enabled
Note: Crossing zones only work in zones dened as Snapshots,
Followers or Interiors.
Command Number 145: Crossing Zones (25 to 32)
Default values ------> 0 0 0 0 0 0 0 0
1 4 5
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 25
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 26
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 27
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 28
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 29

19
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 30
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 31
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 32
0 = Disabled
1 = Enabled
Note: Crossover zones only work in zones dened as Snapshots,
Followers or Interiors.
Command Number 146: Group Inhibition Zones ( 1 to 8 )
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 6
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 1
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 2
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 3
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 4
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 5
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 6
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 7
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 8
0 = Disabled
1 = Enabled
Command Number 147: Group Inhibition Zones (9 to 16)
Default values------------------------> 0 0 0 0 0 0 0 0
1 4 7
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 9
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 10
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 11
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 12
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 13
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 14
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 15
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 16
0 = Disabled
1 = Enabled
Command Number 148: Group Inhibition Zones (17 to 24).
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 8
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 17
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 18
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 19
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 20
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 21
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 22
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 23
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 24
0 = Disabled
1 = Enabled
Command Number 149: Group Inhibition Zones ( 25 to 32 )
Default values -----------------------> 0 0 0 0 0 0 0 0
1 4 9
Positions ---------------------------> (1) (2) (3) (4) (5) (6) (7) (8)
Digit position (1): Zone No. 25
0 = Disabled
1 = Enabled
Digit position (2): Zone No. 26
0 = Disabled
1 = Enabled
Digit position (3): Zone No. 27
0 = Disabled
1 = Enabled
Digit position (4): Zone No. 28
0 = Disabled
1 = Enabled
Digit position (5): Zone No. 29
0 = Disabled
1 = Enabled
Digit position (6): Zone No. 30
0 = Disabled
1 = Enabled
Digit position (7): Zone No. 31
0 = Disabled
1 = Enabled
Digit position (8): Zone No. 32
0 = Disabled
1 = Enabled
Command Number 151: Entry Delay No. 1
Default values ----------------------------------------------------> 0 3 0
1 5 1
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Input Delay No. 1
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 152: Entry Delay No. 2
Default values----------------------------------------------------> 0 3 0
1 5 2
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Input Delay No. 2
The code must be 3 digits long. Valid values are from 000 to 255 seconds.

20
Command Number 153: Entry Delay No. 3
Default values ----------------------------------------------------> 0 3 0
1 5 3
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Input Delay No. 3
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 154: Entry Delay No. 4
Default values ----------------------------------------------------> 0 3 0
1 5 4
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Input Delay No. 4
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 155: Exit Delay Partition No. 1
Default values ----------------------------------------------------> 0 6 0
1 5 5
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Exit Delay Partition N° 1
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 156: Exit Delay Partition No. 2
Default values ----------------------------------------------------> 0 6 0
1 5 6
Positions-------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Exit Delay Partition N° 2
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 159: Partition No. 1 Siren Time
Default values ----------------------------------------------------> 0 0 5
1 5 9
Positions-------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Partition Siren Time
The code must be 3 digits long. Valid values are from 000 to 255 minutes.
Command Number 160: Partition No. 2 Siren Time
Default values ----------------------------------------------------> 0 0 5
1 6 0
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Partition Siren Time
The code must be 3 digits long. Valid values are from 000 to 255 minutes.
Command Number 163: Time Interval for Crossing Zones
Default values ----------------------------------------------------> 0 3 0
1 6 3
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Time Window for Crossing Zones
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Note: If you program a time equal to 000, the crossing zones will never generate
an alarm.
Command Number 165: Network Failure/Restore Transmission Delay
Default values ----------------------------------------------------> 0 0 0
1 6 5
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Network Failure/Restore Transmission Delay
The code must be 3 digits long. Valid values are from 000 to 255 minutes.
Note: This delay has a tolerance of +/- one minute.
Command Number 166: Partition No. 1 Inactivity Arming Timeout
Default values ----------------------------------------------------> 0 0 0
1 6 6
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Partition Inactivity Arming Time The code must be 3 digits
long. Valid values are from 000 to 255 hours.
Note: If 000 is programmed, the inactivity arming will be cancelled.
Command Number 167: Partition No. 2 Inactivity Arming Timeout
Default values ----------------------------------------------------> 0 0 0
1 6 7
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Partition Inactivity Arming Time The code must be 3 digits
long. Valid values are from 000 to 255 hours.
Note: If 000 is programmed, the inactivity arming will be cancelled.
Command Number 170: Re-Transmission Delay of Test and Fault Reports
Network in the event of a failure to send
Default values ----------------------------------------------------> 0 3 0
1 7 0
Positions -------------------------------------------------------------------------> (1) (2) (3)
Digit positions (1) - (3): Re-Transmit Delay Time
The code must be 3 digits long. Valid values are from 000 to 255 minutes.
Note: To cancel this command, it must be programmed with the digits 000
Command Number 172: PGM Pulse Time
Default values ----------------------------------------------------> 0 0 5
1 7 2
Positions -------------------------------------------------------------------------> (1) (2) (3)
The code must be 3 digits long. Valid values are from 000 to 255 seconds.
Command Number 173: Tamper Auto-Arming of Partition with Safe Zone/
Access Control.
Default values ---------------------------------------------------> 0 3 0
1 7 3
Positions -------------------------------------------------------------------------> (1) (2) (3)
The code must be three digits long. Valid values are from 000 to 255 seconds.
Note: If 000 is programmed, the function will be cancelled.
Command Number 174: Maximum time of disarmed partition or door open
(Access Control)
Default values ----------------------------------------------------> 0 0 0
1 7 4
Positions-------------------------------------------------------------------------> (1) (2) (3)
The code must be three digits long. Valid values are from 000 to 255 seconds.
Note: If 000 is programmed, the function will be cancelled.
Command Number 175: Electrolock pulse time.
Default values ---------------------------------------------------> 0 0 3
1 7 5
Positions -------------------------------------------------------------------------> (1) (2) (3)
The code must be three digits long. Valid values are from 000 to 255 seconds.
Command Number 178: PGM Conguration No. 1
Default values -------------------------------------------------------------------------------> 0 0
1 7 8
Positions -------------------------------------------------------------------------------------> (1) (2)
Digit position (1)- (2): PGM conguration No. 1
00 = Partition Indication No. 1 Enabled 01 = Partition Indication No. 2 Enabled
02 = Future Use
03 = Future Use
04 = Output Command “Hold”
05 = Output Command “Pulse”
06 = Future Use
07 = Pulse on Alarm Trigger
08 = Siren for Partition No. 1
09 = Siren for Partition No. 2
10 = Future Use
11 = Future Use
12 = Future Use
13 = Mobile Data Communication Failure
14 = Future Use
15 = Battery Failure
16 = Network Failure
17 = Auxiliary Power Failure
18 = Resetting Smoke Sensors
19 = Future Use
20 = Future Use
21 = Pulse in the face of coercion/entrapment
Note: Commands 179 through 181 (PGMS Conguration) are programmed in the
Table of contents
Other Garnet Measuring Instrument manuals

Garnet
Garnet SeeLeveL II 709-RVC PM User manual

Garnet
Garnet SeeLevel II User manual

Garnet
Garnet SeeLevel II 900-D4S Single User manual

Garnet
Garnet SeeLeveL II 709-P3 User manual

Garnet
Garnet SeeLeveL II 709-RVC User manual

Garnet
Garnet 709-RVC NLP User manual

Garnet
Garnet SeeLevel I 705 Series User manual

Garnet
Garnet SeeLevel II User manual

Garnet
Garnet SeeLeveL Special 809-DM User manual

Garnet
Garnet SEELEVEL II 714 User manual