Programmable Control Products
PACSystems RX3i Genius Communications Gateway
User Manual GFK-2892F
PACSystems RX3i Genius
Communications
Gateway
User Manual
GFK-2892F
March 2019

Legal Information
Warnings, Cautions, and Notes as Used in this Publication GFL-002
Warning
Warning notices are used in this publication to emphasize that hazardous voltages,
currents, temperatures, or other conditions that could cause personal injury exist in
this equipment or may be associated with its use.
In situations where inattention could cause either personal injury or damage to
equipment, a Warning notice is used.
Caution
Caution notices are used where equipment might be damaged if care is not taken.
Note: Notes merely call attention to information that is especially significant to understanding
and operating the equipment.
These instructions do not purport to cover all details or variations in equipment, nor to provide for every
possible contingency to be met during installation, operation, and maintenance. The information is supplied for
informational purposes only, and GE makes no warranty as to the accuracy of the information included herein.
Changes, modifications, and/or improvements to equipment and specifications are made periodically and
these changes may or may not be reflected herein. It is understood that GE may make changes, modifications,
or improvements to the equipment referenced herein or to the document itself at any time. This document is
intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing
of this document does not provide any license whatsoever to any of these patents.
GE PROVIDES THE FOLLOWING DOCUMENT AND THE INFORMATION INCLUDED THEREIN AS-IS AND
WITHOUT WARRANTY OF ANY KIND, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED
STATUTORY WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE.
* indicates a trademark of General Electric Company and/or its subsidiaries.
All other trademarks are the property of their respective owners.
©Copyright 2014-2019 General Electric Company.
All Rights Reserved

Contact Information
If you purchased this product through an Authorized Channel Partner, please contact the seller directly.
General Contact Information
Online technical support and GlobalCare
www.geautomation.com/support
Additional information
www.geautomation.com
Solution Provider
Technical Support
If you have technical problems that cannot be resolved with the information in this manual, please contact us
by telephone or email, or on the web at www.geautomation.com/support
Americas
Phone
1-800-433-2682
International Americas Direct Dial
1-780-420-2010 (if toll free 800 option is unavailable)
Customer Care Email
Primary language of support
English
Europe, the Middle East, and Africa
Phone
+800-1-433-2682
EMEA Direct Dial
+420-296-183-331 (if toll free 800 option is unavailable or
if dialing from a mobile telephone)
Customer Care Email
digitalsupport.emea@ge.com
Primary languages of support
English, French, German, Italian, Spanish
Asia Pacific
Phone
+86-21-3877-7006 (India, Indonesia, and Pakistan)
+86-400-820-8208 (rest of Asia)
Customer Care Email
Primary languages of support
Chinese, English


GFK-2892F March 2019 i
Table of Contents
PACSystems RX3i Genius Communications Gateway User Manual GFK-2892F
Table of Contents ............................................................................................................................................................. i
Table of Figures............................................................................................................................................................... iv
Chapter 1 Introduction ............................................................................................................................................... 1
1.1 Revisions in this Manual .......................................................................................................................... 2
1.2 Acronyms and Abbreviations ................................................................................................................ 3
1.3 PACSystems Documentation................................................................................................................. 4
1.4 Description ................................................................................................................................................. 5
1.5 Product Overview ..................................................................................................................................... 6
1.6 Specifications ............................................................................................................................................ 7
1.7 Controls and Indicators........................................................................................................................... 8
Mounting ................................................................................................................................................................9
1.8 PROFINET Operation Overview........................................................................................................... 10
1.9 System Limits .......................................................................................................................................... 14
1.10 Operational Differences vs. Genius Bus Controller........................................................................ 15
1.11 Supported Genius Devices.................................................................................................................... 16
Chapter 2 Installation ............................................................................................................................................... 17
2.1 Pre-Installation Check ........................................................................................................................... 17
2.2 Installation Location .............................................................................................................................. 17
2.3 Installation in Hazardous Areas .......................................................................................................... 18
ATEX Zone 2 .......................................................................................................................................................18
ATEX Marking.....................................................................................................................................................18
2.4 Module Installation ................................................................................................................................ 19
Install SD Card...................................................................................................................................................19
Mounting the GCG001 ...................................................................................................................................19
GCG001 Module Removal.............................................................................................................................21
Light-Emitting Diode (LED) Indications...................................................................................................22
Fault Notifications ...........................................................................................................................................23

Contents
ii PACSystems RX3i Genius Communications Gateway GFK-2892F
2.5 Configuring the Genius Gateway to Operate with the RX3i CPU ............................................... 24
2.6 Ethernet Port Connections .................................................................................................................. 25
RJ-45 Port Connections.................................................................................................................................25
2.7 Firmware Updates.................................................................................................................................. 26
2.8 Spare Parts ............................................................................................................................................... 26
Chapter 3 Configuration........................................................................................................................................... 27
3.1 Configuration Tools................................................................................................................................ 27
3.2 Configuration Overview........................................................................................................................ 27
GCG001 in Simplex Genius Bus Configuration.....................................................................................27
Genius Hot-Standby Redundancy Configuration ................................................................................33
Genius Duplex Configuration ......................................................................................................................34
Genius Dual Bus Configuration...................................................................................................................34
Genius Hot Standby Dual Bus Configuration ........................................................................................35
Chapter 4 System Operation................................................................................................................................... 37
4.1 System Overview.................................................................................................................................... 37
Communications ..............................................................................................................................................37
Redundancy........................................................................................................................................................38
I/O Scans..............................................................................................................................................................39
Alarms...................................................................................................................................................................40
Chapter 5 Diagnostics............................................................................................................................................... 41
5.1 Status Data............................................................................................................................................... 42
Gateway Status Data......................................................................................................................................42
Genius Status Data..........................................................................................................................................43
Fault Status Data .............................................................................................................................................43
5.2 Module LED Indicators .......................................................................................................................... 43
5.3 Power-Up .................................................................................................................................................. 44
Problems during Power-up ..........................................................................................................................44
Transitioning from Firmware Update Mode to Operational Mode ..............................................44
5.4 Module Faults in the RX3i I/O Fault Tables....................................................................................... 45
Fault Types Reported to the RX3i Controller I/O Fault Table .........................................................46
Clearing the RX3i Fault Tables ....................................................................................................................47
Chapter 6 COMMREQ/Data_Init_Comm Programming..................................................................................... 49
6.1 COMMREQs and Passwords................................................................................................................. 50
6.2 Programming for a COMMREQ Communication Request............................................................. 50
6.3 COMMREQ Command Block Format .................................................................................................. 51
COMMREQ Command Block Contents....................................................................................................52

Contents
GFK-2892F March 2019 iii
COMMREQ Commands Supported by the Genius Gateway (GCG001) .....................................53
COMMREQ Command Block Quick Reference .....................................................................................54
Mechanics of the COMMREQ Instruction...............................................................................................55
Comparison: COMMREQ vs Data_Init_Comm ......................................................................................60
COMMREQ Differences: Genius Bus Controllers and Genius Gateway .....................................61
6.4 COMMREQ Descriptions and Formats............................................................................................... 62
COMMREQ #1: Pulse Test Command.......................................................................................................62
COMMREQ #2: Read Configuration Command ....................................................................................63
COMMREQ #3: Write Configuration Command................................................................................... 64
COMMREQ #4: Read Diagnostics Command ........................................................................................65
COMMREQ #5: Clear Circuit Fault Command.......................................................................................66
COMMREQ #6: Clear All Circuit Faults Command ..............................................................................67
COMMREQ #7: Assign Monitor Command.............................................................................................68
COMMREQ #8: Enable/Disable Outputs Command...........................................................................69
COMMREQ #10: Switch BSM Command.................................................................................................70
COMMREQ #11: Read Device Command................................................................................................71
COMMREQ #12: Write Device Command ..............................................................................................72
COMMREQ #19: Read Identification.........................................................................................................73
COMMREQ #20: Write Point Command .................................................................................................75
COMMREQ #21: Read Block I/O Command ...........................................................................................76
COMMREQ #22: Read Map Command.....................................................................................................80
COMMREQ #23: Write Map Command ...................................................................................................81
COMMREQ #24: Read Data Command....................................................................................................82
COMMREQ #25: Write Data Command ..................................................................................................83

Contents
iv PACSystems RX3i Genius Communications Gateway GFK-2892F
Table of Figures
Figure 1: Simplex PLC System Using Genius Gateway GCG001 .................................................................................................. 5
Figure 2: GCG001 Module............................................................................................................................................................................ 6
Figure 3: Genius Gateway GCG001 Front Panel View ...................................................................................................................... 8
Figure 4: GCG001 Panel Mount Diagram .............................................................................................................................................. 9
Figure 5: Application Relationships between PROFINET Controller & Genius Gateway ....................................................10
Figure 6: Real-Time & Non-Real-Time Data Types...........................................................................................................................11
Figure 7: PLC - GCG - Genius Scan Cycles...........................................................................................................................................12
Figure 8: Rear View of GCG001 ...............................................................................................................................................................19
Figure 9: GCG001 Power Connector......................................................................................................................................................19
Figure 10: Daisy Chain Genius Bus Wiring .........................................................................................................................................20
Figure 11: Genius Bus Wiring for Bus Termination..........................................................................................................................20
Figure 12: PROFINET Discovery Screenshot .......................................................................................................................................21
Figure 13: GCG001 Firmware Upgrade ZIP File UnZIPped to SD Card .....................................................................................26
Figure 14: Hardware Configuration Expanded Tree ........................................................................................................................28
Figure 15 - GCG Data Reference Addresses........................................................................................................................................28
Figure 16: Genius Gateway Parameters ..............................................................................................................................................28
Figure 17: Change Module List for Genius Gateway GCG001 .....................................................................................................29
Figure 18: Populating the Genius IO Devices to be Controlled by the Genius Gateway ....................................................30
Figure 19: Populating Slots in S90-70 Rack Controlled by Remote I/O Scanner (BEM733).............................................30
Figure 20: PME Display of Complete Genius Gateway Configuration ......................................................................................32
Figure 21: GCG001 Units Deployed in Genius Hot Standby Dual Bus Redundancy ...........................................................36
Figure 22: Genius Hot Standby Redundancy .....................................................................................................................................38
Figure 23: PROFINET Media Redundancy............................................................................................................................................39
Figure 24: Gateway Status Data.............................................................................................................................................................42
Figure 25: Genius Status Data .................................................................................................................................................................43
Figure 26: Fault Status Data.....................................................................................................................................................................43
Figure 27 - I/O Fault Table Message Identifiers.................................................................................................................................46
Figure 28: Genius Discrete Block Failed Switch Fault Display (Example) ...............................................................................47
Figure 29: Genius Analog Block Over Range Fault Display (Example) .....................................................................................47
Figure 30: Ladder Logic to Clear Circuit Fault....................................................................................................................................59
Figure 31: Data_Init_Comm to Clear Circuit Fault............................................................................................................................60

GFK-2892F March 2019 1
Chapter 1 Introduction
This manual describes the RX3i Genius Communications Gateway, which acts as a gateway between
PROFINET and Genius I/O. Introductory material may be found in this chapter. Chapter 2 provides installation
and set-up information. Chapter 3 provides configuration instructions. Chapter 4 describes system operation.
Chapter 5 provides diagnostic information. Chapter 6 covers the use and format of ladder logic COMMREQ
instructions.

Chapter 1. Introduction
2 PACSystems RX3i Genius Communications Gateway GFK-2892F
1.1 Revisions in this Manual
Rev
Date
Description
F
Mar
2019
•In Section 5.1.3, added Fault Status Data.
E
Oct
2018
•Added note 3.2.2 concerning PNC001 Critical Network Ports feature with GCGs.
D
Mar
2018
•Added compatibility with CPE302.
C
Dec
2017
•Added support for Field Control Bus Interface Unit.
•Added Outputs at Startup hardware configuration parameter.
•Added Enable/Disable Outputs and Switch BSM COMMREQs.
•Documented GCG001 Units deployed in Genius Hot Standby Dual Bus Redundancy
(Section 3.2.5).
B
Aug
2016
•Added support for VersaMax Genius Network Interface (GNIU)
•Added support for IC660BSS101 isolated I/O block
•Added support for additional Genius baud rates
A
Mar
2015
•Behavior of GCG001 with respect to input references associated with a faulted block
is described in Section 1.10, with workaround in Section 4.1.4.
•Correction to Figure 22: Genius Hot Standby Redundancy to indicate CPU type is CRU
and RMX modules are required.
•Clear All Faults can now be dispatched to all blocks on the bus in a single command.
See Section 6.4.6.
-
Jun
2014
Initial release

Chapter 1. Introduction
GFK-2892F March 2019 3
1.2 Acronyms and Abbreviations
AR
PROFINET Application Relationship
CR
PROFINET Communication Relationship
DCP
PROFINET Discovery & Configuration Protocol
GBIU
Genius Bus Interface Unit
GCG
Genius Communications Gateway (specifically GCG001)
GENA
Genius Network Adaptor
GENI
Genius Network Interface
GNIU
Genius Network Interface Unit
GR7
Series 90-70 Remote I/O Scanner (IC697BEM733)
GSDML
General Station Description Markup Language
HHM
Genius Hand-Held Monitor
HWC
Hardware Configuration (in PME)
LAN
Local Area Network
LED
Light Emitting Diode
MRC
Ethernet Media Redundancy Client
MRM
Ethernet Media Redundancy Manager
MRP
Ethernet Media Redundancy Protocol
NRT
Non-Real-Time PROFINET Communication
PCIM
Personal Computer Interface Module
PME
Proficy® Machine Edition
PNC
PROFINET Controller
PPV
PLC Protocol Variables
RT
Real-Time PROFINET Communication
SBA
Genius Serial Bus Address
SD
Secure Digital Card Slot
STP
Shielded Twisted Pair
UTP
Unshielded Twisted Pair

Chapter 1. Introduction
4 PACSystems RX3i Genius Communications Gateway GFK-2892F
1.3 PACSystems Documentation
PACSystems Manuals
PACSystems RX7i, RX3i and RSTi-EP CPU Reference Manual
GFK-2222
PACSystems RX7i, RX3i and RSTi-EP CPU Programmer’s Reference Manual
GFK-2950
PACSystems RX7i, RX3i and RSTi-EP TCP/IP Ethernet Communications User Manual
GFK-2224
PACSystems TCP/IP Ethernet Communications Station Manager User Manual
GFK-2225
C Programmer’s Toolkit for PACSystems
GFK-2259
PACSystems Memory Xchange Modules User’s Manual
GFK-2300
PACSystems Hot Standby CPU Redundancy User Manual
GFK-2308
PACSystems Battery and Energy Pack Manual
GFK-2741
Proficy Machine Edition Logic Developer Getting Started
GFK-1918
Proficy Process Systems Getting Started Guide
GFK-2487
PACSystems RXi, RX3i, RX7i and RSTi-EP Controller Secure Deployment Guide
GFK-2830
PACSystems RX3i & RSTi-EP PROFINET I/O Controller Manual
GFK-2571
PACSystems RX3i Genius Communications Gateway
GFK-2928
RX3i Manuals
PACSystems RX3i System Manual
GFK-2314
PACSystems RX3i PROFINET Scanner Manual
GFK-2737
PACSystems RX3i CEP PROFINET Scanner User Manual
GFK-2883
Distributed I/O Systems Manuals
Genius I/O System and Communications User’s Manual
GEK-90486-1
Genius I/O Analog and Discrete Blocks User’s Manual
GEK-90486-2
Genius Hand-Held Monitor User’s Guide
GFK-0121
Series 90-70 Remote I/O Scanner User’s Manual
GFK–0579
VersaMax Systems Manuals
VersaMax System Genius Network Interface Unit User’s Manual
GFK-1535
In addition to these manuals, datasheets and product update documents describe individual modules and
product revisions. The most recent PACSystems documentation is available on the GE Automation & Controls
support website www.geautomation.com/support.

Chapter 1. Introduction
GFK-2892F March 2019 5
1.4 Description
The RX3i Genius Communications Gateway, IC695GCG001 (or GCG001), interfaces Genius IO devices on a
Simplex Genius Serial Bus to a GE PROFINET IO Controller.
Figure 1: Simplex PLC System Using Genius Gateway GCG001
The GCG001 operates as a Genius Bus Controller on a Genius network. It scans the Genius IO devices
configured to it, retrieving input data and providing output data. It then exchanges that data with its configured
PROFINET IO Controller over its Ethernet interfaces at the configured production rate. The GCG001 can
manage communications for up to 31 Genius IO devices on a single Genius Serial Bus.
The GCG001 also operates as an IO Device on PROFINET. It may be controlled by any of the following PROFINET
IO Controllers:
•PNC001 (the RX3i rack-mounted PNC module), or by
•CPE330 LAN 2 when configured as a PROFINET LAN, or by
•CPE400 LAN 2 when configured as a PROFINET LAN.
Thus, when correctly configured, the entire Genius Bus, including the GCG001 itself, becomes visible to the
controlling PLC. Note that the GCG001 operates only with GE PLC PROFINET IO Controllers.
PROFINET operates on an Ethernet network. If the Ethernet network or Genius serial bus communications are
lost, the GCG001 manages I/O states according to the individual module configurations.
Both PROFINET and Genius may be set up in Redundant configurations. These are discussed later in this
manual.

Chapter 1. Introduction
6 PACSystems RX3i Genius Communications Gateway GFK-2892F
1.5 Product Overview
Features of the GCG001 module include:
•Attachment of two RJ-45 Ethernet connections (Ports 1 & 2)
•Support for both star (switched) and linear (daisy-chained) network
topologies
•Supports Ethernet Media Redundancy Protocol (MRP)
•LEDs to indicate Ethernet status (ACT & LINK)
•Genius bus terminal block attachment
•Supports Genius Redundancy consisting of a single Genius bus with two
GCG001 Gateways, one at SBA #30 and the other at SBA #31.
•LED to indicate Genius Communications Status (COM)
•LEDs to indicate module status (refer to module header)
•Panel-mount (typical)
•Optional mounting in RX3i expansion slot
•Cable tie-down loop on underside of module (at front)
•24Vdc power connector on underside of module
•0.2A maximum current draw
•Secure Digital (SD) Card Slot, accessible at rear of module
•Firmware load pushbutton, accessible at rear of module
ETHERNET
ACT LINK
PORT 1
PORT 2
COM
POWER
FAULT
CONNECT
OK
GCG001
LINK
ACT
GENIUS A
SER 1
SER 2
SHLD
IN
GENIUS
SHLD
OUT
Figure 2: GCG001
Module
Note: Although the hardware supports the 10/100BASE TX Ethernet standard, PROFINET I/O
over wired infrastructure must be 100Mbps full-duplex or faster. 10Mbps should not be
used for PROFINET.

Chapter 1. Introduction
GFK-2892F March 2019 7
1.6 Specifications
RX3i Genius Communications Gateway Specifications
PROFINET Support
PROFINET version 2.3 Class A IO-Device
CPU Compatibility
RX3i CPE330
RX3i CPE302/CPE305/CPE310 with firmware version 8.15 or later
RX3i CPU315/CPU320/CRU320 with firmware version 8.15 or later
Rx3i CPE302 (any firmware version)
PNC001 Compatibility
Firmware version 2.05 or later
Embedded PROFINET
Compatibility
RX3i CPE400 embedded PROFINET
RX3i CPE330 embedded PROFINET with firmware version 8.90 or
later
Proficy* Machine Edition
Compatibility
PME 8.0 or later
Power Requirements
External 24Vdc: (±10%) 0.2A
Operating Temperature Range
0 to 60°C
Number of Port Connectors
Two RJ-45
Local Area Network (LAN)
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100 Mbps
Status Data
64 (two banks of 32 bits)
Genius Bus Support
Supports One Genius Bus.
Serial 1, Serial 2, Shield In and Shield Out, as marked.
Up to 29 additional devices supported per Genius Bus.
Selectable Baud Rate, per Genius specifications.
Genius Hot Standby and Duplex Redundancy supported.
HHM Compatibility
IC660HHM501
Other Genius Compatibility
See table in Section 1.11
SD Card
2GB or smaller. Not compatible with SDHC or SDXC cards.
Configuration
GSDML file is available on the Support website for download and
import into PME. The GSDML supporting a firmware release is part
of the firmware upgrade kit available on the Support website.
Hot Swappable
The Genius Gateway requires an external 24Vdc power supply
and does not draw power from the Rx3i backplane. Swapping out
the GCG001 will therefore not impact the PLC. However, this
cannot be performed without disconnecting its power supply. If
configured to support Genius Hot Standby, the loss of a single
GCG001 will be tolerated; otherwise not.
For system standards, general operating specifications, and installation requirements, refer to the PACSystems
RX3i System Manual, GFK-2314.

Chapter 1. Introduction
8 PACSystems RX3i Genius Communications Gateway GFK-2892F
1.7 Controls and Indicators
The following figure shows the front of the module and identifies the controls and indicators.
ETHERNET
ACT LINK
PORT 1
PORT 2
COM
POWER
FAULT
CONNECT
OK
GCG001
LINK
ACT
GENIUS A
SER 1
SER 2
SHLD
IN
GENIUS
SHLD
OUT
Module Status
Indicator LEDs:
POWER, OK,
FAULT,
CONNECT
Ethernet Port
Indicator LEDs:
LINK,
ACT
24 V dc
Power
Connector
Genius Bus
Indicator LEDs:
COM
PROFINET
Ports
Genius Bus
Connector
Figure 3: Genius Gateway GCG001 Front Panel View

Chapter 1. Introduction
GFK-2892F March 2019 9
Mounting
The GCG001 may either be panel-mounted or be mounted in the rightmost slot (expansion slot) of an RX3i
rack (IC695CHS012 or IC695CHS016).
Note: The SD Card supplied with the GCG001 will have been installed at the factory. See
section 2.4.1 for instructions for installing the SD Card when doing a retrofit. The
presence of the SD Card should be checked before mounting the module.
Note: Clearance of 3 inches (75mm) must be provided above and below the module for proper
ventilation and to permit cable access.
Note: External power must always be supplied to the module, regardless of which mounting
arrangement is chosen. When rack-mounted, the GCG001 does not draw power from the
RX3i Universal Backplane.
RX3i Backplane Mounting
The GCG001 may be mounted in the rightmost slot
(expansion slot) of an RX3i Universal Backplane.
The two captive M3.5 screws at the rear of the GCG001
align with mating tapped holes on the right side of the
backplane, providing a convenient mounting location.
When rack-mounted, the module does not make contact
with the backplane connector.
Panel-Mounting
Panel-mounting allows for mounting where no RX3i
backplane slot is available. The two captive M3.5 machine
screws on the GCG001 can be used for attaching the unit
to a panel.
Note: The panel must have a minimum
thickness of 2.4mm (0.094in).
1. Drill two mounting holes using the spacing
shown in the drawing (at right) and tap for
M3.5 (3.5 x 0.6mm).
2. Align the two mounting screws of the module
with the mounting holes in the panel.
3. Using a Philips screwdriver, tighten the two
screws to a maximum torque of 0.5 Nm
(4.4 in-lbs).
Figure 4: GCG001 Panel Mount Diagram

Chapter 1. Introduction
10 PACSystems RX3i Genius Communications Gateway GFK-2892F
1.8 PROFINET Operation Overview
An RX3i Genius Communications Gateway (GCG001) uses PROFINET communications for data exchange with
the PLC. As noted above, the data rate must be 100Mbps full-duplex or faster. The same network may be used
for basic Ethernet communications, but use of a separate Ethernet network and RX3i Ethernet interface is
recommended.
PROFINET Communications
Communications on an RX3i PROFINET network use the standard PROFINET communications described in this
section. Note, however, that the Genius Gateway GCG001 is constrained to work only with GE PROFINET PLC
products.
Application Relationships
Before a PROFINET IO-Controller can exchange data with a PROFINET IO-Device such as the GCG001, an
Application Relationship (connection) must be established between the devices. The PROFINET IO-Controller
automatically sets up the correct number and types of Application Relationship and Communication
Relationship channels (see below) based on its PME configuration. Usually, only one Application Relationship is
established per IO-Device.
Communication Relationships within an Application Relationship
Within each Application Relationship, the PROFINET IO-Controller establishes the following types of
Communication Relationships (CRs):
Record Data CRs –always the first to be established within an Application Relationship. Record Data
Communication Relationships are used for non-real-time transfers of data records such as startup parameter
data, diagnostics data, identification data, and configuration data.
IO CRs –used for the real-time, cyclic transfer of IO data
Alarm CR –used for real-time, acyclic transfer of alarms and events
The following illustration represents an Application Relationship between an RX3i PROFINET Controller and an
RX3i Genius Gateway GCG001.
Record Data Communication Relationship
I/O Data Communication Relationship
Alarm Communication Relationship
Application Relationship
Genius Gateway (GCG001)
1
2
3
4
PNS001
ACTIVE
USB
OK
LAN
STATUS
CONN
USB
IPADDRESS
MACADDRESS
PORTS
TOINSTALL,
TORQUETO
6IN-LB.
IO DEVICE
FRONT
3 4
1 2
SDCARD
!
RX3i with PROFINET Controller (PNC)
Figure 5: Application Relationships between PROFINET Controller & Genius Gateway

Chapter 1. Introduction
GFK-2892F March 2019 11
Types of PROFINET Communications
Genius Communications Gateways use two types of PROFINET communication transfers: real-time and non-
real-time. The illustration below shows real-time communications as solid lines and non-real-time
communications as dashed lines.
1
2
3
4
PNS001
ACTIVE
USB
OK
LAN
STATUS
CONN
USB
IPADDRESS
MACADDRESS
PORTS
TOINSTALL,
TORQUETO
6IN-LB.
IO DEVICE
FRONT
3 4
1 2
SDCARD
!
RX3i with PROFINET Controller (PNC)
Real-Time Data
Inputs
Outputs
Alarms
Non Real-Time
Data
Parameters
Configuration Data
Figure 6: Real-Time & Non-Real-Time Data Types
Real-Time (RT) communication: PROFINET real-time communication is used for time-sensitive data. A
PROFINET IO-Controller (PROFINET Controller) and PROFINET IO-Device use two types of real-time
communications to exchange data: cyclic communication and acyclic communication:
Real-time Cyclic communication is used to periodically transfer the application’s input and output data. Cyclic
communication occurs each PROFINET IO production cycle.
Real-time Acyclic communication is used to transfer non-periodic data such as alarms. Acyclic communication
occurs only when needed.
Non-Real-Time (NRT) communication: PROFINET non-real-time communication is used for less time-
sensitive data such as configuration, parameterization, diagnostics, and identification data.
Operations of the Genius Communications Gateway
The Genius Communications Gateway performs the following operations:
Consumes PROFINET IO-Device configuration from the PROFINET IO-Controller over the PROFINET network.
Scans input data from each Genius device it manages and produces that data to the PROFINET IO-Controller.
Consumes the output data that it receives from the PROFINET IO-Controller and applies it to each Genius
device it manages.
Where needed, translates Genius Datagrams (background traffic) into PROFINET packages that are sent to the
PROFINET Controller. This includes Datagrams that originated at the Genius Devices, such as Fault Reports.
Translates PROFINET packages that are sent by the PROFINET Controller into Genius Datagrams. This includes
Datagrams that originated at the PLC through use of COMMREQ or Data_Init_Comm instructions. For example,
a COMMREQ is used to generate a Clear Fault Report datagram.

Chapter 1. Introduction
12 PACSystems RX3i Genius Communications Gateway GFK-2892F
IO Scanning
In the PACSystems RX3i PROFINET network, multiple IO cycles run asynchronously and independently. Figure 7
illustrates typical cycles in a system with an RX3i CPU with a PROFINET Controller module communicating with
a Genius Communications Gateway. Cycles may be different for third-party devices.
Genius
I/O
Genius
I/O
Genius
I/O
Genius
I/O
Genius
I/O
PROFINET I/ O
Genius
I/O
Genius
I/O
Genius
I/O
Genius
I/O
Genius
I/O
Genius Bus Scans
P
S
C
P
U
P
N
C
PROFINET IO
Production Cycle
RX3i CPU Sweep
Figure 7: PLC - GCG - Genius Scan Cycles
Genius IO-Device Scan: In this example, each GCG scans all of its Genius devices. The GCG stores the devices’
input data into its internal memory. Every time the GCG gets a turn on the Genius bus, it transmits the output
data from its internal memory to each of the Genius devices.
3rd party devices: The transfer of IO data between an IO module and the PROFINET IO network is device
dependent. Refer to the third-party manufacturer documentation for specifics for a particular device.
PROFINET IO Production Cycle: Each PROFINET Controller and IO-Device publishes data from its internal
memory onto the network at its scheduled PROFINET production cycle (Note: Production cycles between
IO-Controllers and IO-Devices are not synchronized; each publishes at its configured update rate
independently). The PROFINET Controller publishes output data received from the RX3i CPU to each IO-Device,
and the IO-Device publishes input data from its memory to the PROFINET Controller.
RX3i CPU Sweep: The RX3i CPU Sweep includes both an input scan and an output scan. The CPU input scan
retrieves the current input data being stored within the PROFINET Controller module. This input data is then
available for use by the application logic. After the logic solution, the CPU output scan writes the outputs to the
PROFINET Controller.
Table of contents
Other GE Gateway manuals

GE
GE POWER LEADER GEH-6505A User manual

GE
GE Multilin D400 Instructions for use

GE
GE MDS WiYZ User manual

GE
GE G500 User manual

GE
GE NX-592E-GSM User manual

GE
GE Multilin D400 User manual

GE
GE PACSystems RX3i Genius User manual

GE
GE G500 User manual

GE
GE ProBridge User manual

GE
GE Interlogix 0150-0265A User manual