GE ML Series 350 User manual

GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094
GE Digital Energy
Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
Instruction manual
350 revision: 1.41
Manual P/N: 1601-9086-A8
GE publication code: GEK-113507G
Copyright © 2011 GE Multilin
*1601-9086-A8*
350
Feeder Protection System
Feeder protection and control
Courtesy of NationalSwitchgear.com

© 2011 GE Multilin Incorporated. All rights reserved.
GE Multilin 350 Feeder Protection System instruction manual for revision 1.41.
350 Feeder Protection System, EnerVista, EnerVista Launchpad, and EnerVista SR3 Setup
are registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9086-A8 (May 2011)
Courtesy of NationalSwitchgear.com

350C FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Table of Contents
1. INTRODUCTION Overview ................................................................................................................................1 - 1
Cautions and warnings ...................................................................................................1 - 2
Description of the 350 Feeder Protection System..............................................1 - 3
350 order codes..................................................................................................................1 - 6
Specifications.......................................................................................................................1 - 7
Password security....................................................................................................................1 - 7
Protection.....................................................................................................................................1 - 7
Metering........................................................................................................................................1 - 9
Data capture ..............................................................................................................................1 - 10
Control...........................................................................................................................................1 - 10
Inputs .............................................................................................................................................1 - 11
Outputs..........................................................................................................................................1 - 12
Power supply..............................................................................................................................1 - 13
Communications ......................................................................................................................1 - 13
Testing and certification .......................................................................................................1 - 14
Physical .........................................................................................................................................1 - 15
Environmental............................................................................................................................1 - 15
2. INSTALLATION Mechanical installation ...................................................................................................2 - 1
Dimensions..................................................................................................................................2 - 1
Product identification .............................................................................................................2 - 2
Mounting ......................................................................................................................................2 - 3
Unit withdrawal and insertion............................................................................................2 - 5
Electrical installation ........................................................................................................2 - 7
Terminal identification ...........................................................................................................2 - 8
Phase sequence and transformer polarity...................................................................2 - 10
Current inputs ............................................................................................................................2 - 11
Ground and sensitive ground CT inputs ........................................................................2 - 11
Zero sequence CT installation............................................................................................2 - 12
Voltage inputs............................................................................................................................2 - 13
Control power ............................................................................................................................2 - 13
Contact inputs ...........................................................................................................................2 - 14
Trip and Close output relays ...............................................................................................2 - 15
Serial communications..........................................................................................................2 - 17
IRIG-B .............................................................................................................................................2 - 18
3. INTERFACES Front control panel interface........................................................................................3 - 2
Description ..................................................................................................................................3 - 2
Display ...........................................................................................................................................3 - 3
Working with the Keypad....................................................................................................3 - 3
LED status indicators..............................................................................................................3 - 4
Relay messages ........................................................................................................................3 - 5
Target messages.....................................................................................................................3 - 5
Self-test errors..........................................................................................................................3 - 6
Flash messages.......................................................................................................................3 - 7
Software setup....................................................................................................................3 - 9
Quick setup - Software interface ......................................................................................3 - 9
EnerVista SR3 Setup Software............................................................................................3 - 9
Hardware and software requirements.........................................................................3 - 10
Courtesy of NationalSwitchgear.com

350C FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Installing the EnerVista SR3 Setup software..............................................................3 - 10
Connecting EnerVista SR3 Setup to the relay ............................................................3 - 13
Configuring serial communications...............................................................................3 - 13
Using the Quick Connect feature ....................................................................................3 - 14
Configuring Ethernet communications ........................................................................3 - 15
Connecting to the relay........................................................................................................3 - 16
Working with setpoints and setpoint files....................................................................3 - 17
Engaging a device..................................................................................................................3 - 17
Entering setpoints...................................................................................................................3 - 17
File support ................................................................................................................................3 - 19
Using setpoints files...............................................................................................................3 - 19
Downloading and saving setpoints files......................................................................3 - 19
Adding setpoints files to the environment..................................................................3 - 19
Creating a new setpoint file...............................................................................................3 - 20
Upgrading setpoint files to a new revision .................................................................3 - 21
Printing setpoints and actual values .............................................................................3 - 22
Printing actual values from a connected device .....................................................3 - 23
Loading setpoints from a file.............................................................................................3 - 24
Upgrading relay firmware ...................................................................................................3 - 24
Loading new relay firmware..............................................................................................3 - 24
Advanced EnerVista SR3 Setup features ...................................................................... 3 - 27
Flexcurve editor .......................................................................................................................3 - 27
Transient recorder (Waveform capture).......................................................................3 - 28
Protection summary..............................................................................................................3 - 31
Password security ..................................................................................................................3 - 32
4. ACTUAL VALUES Actual values overview ...................................................................................................4 - 1
A1 Status................................................................................................................................4 - 3
Clock...............................................................................................................................................4 - 3
Contact inputs...........................................................................................................................4 - 4
Output relays .............................................................................................................................4 - 4
Logic elements ..........................................................................................................................4 - 4
Virtual inputs ..............................................................................................................................4 - 5
Remote inputs ...........................................................................................................................4 - 5
Remote outputs ........................................................................................................................ 4 - 5
Contact inputs summary......................................................................................................4 - 5
Output relays summary........................................................................................................4 - 5
Logic elements summary.....................................................................................................4 - 6
GOOSE status.............................................................................................................................4 - 6
GOOSE HDR status ..................................................................................................................4 - 6
A2 Metering ..........................................................................................................................4 - 7
Current..........................................................................................................................................4 - 7
Voltage..........................................................................................................................................4 - 8
Power.............................................................................................................................................4 - 8
Energy ...........................................................................................................................................4 - 9
Thermal capacity .....................................................................................................................4 - 9
Clear energy ...............................................................................................................................4 - 9
A3 Records............................................................................................................................4 - 10
Event records............................................................................................................................. 4 - 10
Transient records.....................................................................................................................4 - 28
Clear event record...................................................................................................................4 - 28
Clear transient record............................................................................................................4 - 28
Clear thermal capacity record...........................................................................................4 - 28
A4 Target messages.........................................................................................................4 - 29
Courtesy of NationalSwitchgear.com

350C FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5. QUICK SETUP -
FRONT CONTROL
PANEL
Quick Setup settings.........................................................................................................5 - 3
6. SETPOINTS Setpoints Main Menu........................................................................................................6 - 1
Setpoint entry methods.........................................................................................................6 - 2
Common setpoints ..................................................................................................................6 - 3
Logic diagrams..........................................................................................................................6 - 4
Setting text abbreviations....................................................................................................6 - 4
S1 Relay setup .....................................................................................................................6 - 6
Clock...............................................................................................................................................6 - 6
Password security....................................................................................................................6 - 8
Access passwords..................................................................................................................6 - 9
Communications ......................................................................................................................6 - 11
RS485 interface .......................................................................................................................6 - 11
Ethernet.......................................................................................................................................6 - 12
Modbus........................................................................................................................................6 - 12
IEC 60870-5-103 serial communication ......................................................................6 - 14
IEC60870-5-104 protocol....................................................................................................6 - 29
DNP communication.............................................................................................................6 - 30
IEC 61850 GOOSE communications...............................................................................6 - 44
Event recorder ...........................................................................................................................6 - 45
Transient recorder ...................................................................................................................6 - 46
Front panel ..................................................................................................................................6 - 47
Installation...................................................................................................................................6 - 48
S2 System Setup.................................................................................................................6 - 49
Current sensing.........................................................................................................................6 - 49
Voltage sensing.........................................................................................................................6 - 50
Power system.............................................................................................................................6 - 51
Breaker..........................................................................................................................................6 - 51
User curve....................................................................................................................................6 - 52
FlexCurves™ ...............................................................................................................................6 - 52
S3 Protection........................................................................................................................6 - 53
Current elements......................................................................................................................6 - 55
TOC curves.................................................................................................................................6 - 56
Phase timed overcurrent protection .............................................................................6 - 63
Phase instantaneous overcurrent protection ...........................................................6 - 66
Ground/Sensitive Ground timed overcurrent protection.....................................6 - 68
Ground/Sensitive Ground instantaneous overcurrent protection...................6 - 71
Ground directional .................................................................................................................6 - 73
Neutral timed overcurrent protection...........................................................................6 - 78
Neutral instantaneous overcurrent protection ........................................................6 - 81
Neutral directional..................................................................................................................6 - 84
Negative sequence instantaneous overcurrent protection ...............................6 - 88
Voltage elements......................................................................................................................6 - 90
Phase undervoltage ..............................................................................................................6 - 90
Phase overvoltage..................................................................................................................6 - 94
Neutral overvoltage...............................................................................................................6 - 96
Negative sequence overvoltage......................................................................................6 - 98
Auxiliary undervoltage .........................................................................................................6 - 100
Auxiliary overvoltage.............................................................................................................6 - 103
Underfrequency.......................................................................................................................6 - 105
Overfrequency..........................................................................................................................6 - 108
Cable Thermal Model..............................................................................................................6 - 110
Courtesy of NationalSwitchgear.com

350C FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S4 Controls............................................................................................................................6 - 114
Change setpoint group .........................................................................................................6 - 115
Virtual inputs ..............................................................................................................................6 - 117
Logic elements ..........................................................................................................................6 - 118
Breaker control .........................................................................................................................6 - 124
Cold load pickup.......................................................................................................................6 - 125
Breaker failure........................................................................................................................... 6 - 128
Autorecloser ...............................................................................................................................6 - 130
S5 Inputs/Outputs .............................................................................................................6 - 135
Contact inputs...........................................................................................................................6 - 135
Output relays .............................................................................................................................6 - 136
Output Relay 1 "Trip" .............................................................................................................6 - 137
Output Relay 2 "Close"..........................................................................................................6 - 139
Auxiliary Output Relays 3 to 6...........................................................................................6 - 141
Critical Failure Relay #7 .......................................................................................................6 - 142
Virtual inputs ..............................................................................................................................6 - 143
Remote inputs ...........................................................................................................................6 - 145
7. MAINTENANCE M1 Relay information.......................................................................................................7 - 3
M3 Breaker maintenance ..............................................................................................7 - 4
Trip coil..........................................................................................................................................7 - 4
Close coil ......................................................................................................................................7 - 6
Breaker trip counter................................................................................................................7 - 9
M4 Breaker monitor..........................................................................................................7 - 12
M5 Relay maintenance ...................................................................................................7 - 13
Ambient temperature ............................................................................................................ 7 - 13
APPENDIX. Change notes ...............................................................................................................Appendix - 1
Manual Revision history................................................................................................ Appendix - 1
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–1
350 Feeder Protection System
Chapter 1: Introduction
Digital Energy
Multilin
Introduction
Overview
The 350 is a microprocessor-based relay for primary and backup over-current protection
of medium and low voltage distribution feeders. The relay is also suitable for providing
over-current protection for small and medium size motors, transformers, generators, and
distribution bus-bars. The small footprint and the withdrawable option make the 350 relay
ideal for panel mounting on either new or retrofit installations. The combination of proven
hardware, a variety of protection and control features, and communications, makes the
relay ideal for total feeder protection and control. Equipped with serial (RS485), USB, and
Ethernet ports, and a wide selection of protocols such as Modbus, DNP3.0, IEC 60870-5-
103, 60870-5-104, GOOSE, the 350 relay is the best-in-class for MCCs, SCADA and inter-
relay communications. The 350 relay provides excellent transparency with respect to
power system conditions and events, through its four-line 20-character display, as well as
the EnerVista SR3 Setup program. Conveniently located LEDs provide indication of relay
operation, alarm, and pickup, as well as breaker, and relay status.
The 350 relay provides the following key benefits:
• Withdrawable small footprint – saves on rewiring and space.
• Multiple protection groups with the added flexibility of switching through a wide
selection of overcurrent protection and control features.
• Fast setup (Quick Setup) menu for power-system setup and a simple overcurrent
protection configuration.
• Large four-line LCD display, LEDs, and an easy-to-navigate keypad.
• Multiple communication protocols for simultaneous access when integrated into
monitoring and control systems.
Courtesy of NationalSwitchgear.com

1–2 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CAUTIONS AND WARNINGS CHAPTER 1: INTRODUCTION
Cautions and warnings
Before attempting to install or use this device, it is imperative that all caution and danger
indicators in this manual are reviewed to help prevent personal injury, equipment damage,
or downtime. The following icons are used to indicate notes, cautions, and dangers.
Figure 1: Note icons used in the documentation
The standard note icon emphasizes a specific point or indicates minor problems that may
occur if instructions are not properly followed.
The caution icon indicates that possible damage to equipment or data may occur if
instructions are not properly followed.
The danger icon provides users with a warning about the possibility of serious or fatal
injury to themselves or others.
NOTE
CAUTION
DANGER
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–3
Description of the 350 Feeder Protection System
CPU
Relay functions are controlled by two processors: a Freescale MPC5554 32-bit
microprocessor measures all analog signals and digital inputs and controls all output
relays; a Freescale MPC520B 32-bit microprocessor controls all the Ethernet
communication protocols.
Analog Input Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the
source instrument transformers. The analog signals are then passed through a 960 Hz low
pass anti-aliasing filter. All signals are then simultaneously captured by sample and hold
buffers to ensure there are no phase shifts. The signals are converted to digital values by a
12-bit A/D converter before finally being passed on to the CPU for analysis.
Both current and voltage are sampled thirty-two times per power frequency cycle. These
‘raw’ samples are scaled in software, then placed into the waveform capture buffer, thus
emulating a fault recorder. The waveforms can be retrieved from the relay via the EnerVista
SR3 Setup software for display and diagnostics.
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings
of the Bus VT phase A voltage . The signals are passed through a low pass filter to prevent
false zero crossings. Sampling is synchronized to the Va-x voltage zero crossing which
results in better co-ordination for multiple 350 relays on the same bus.
Phasors, Transients, and Harmonics
Current waveforms are processed twice every cycle with a DC Offset Filter and a Discrete
Fourier Transform (DFT). The resulting phasors have fault current transients and all
harmonics removed. This results in an overcurrent relay that is extremely secure and
reliable; one that will not overreach.
Processing of AC Current Inputs
The DC Offset Filter is an infinite impulse response (IIR) digital filter, which removes the DC
component from the asymmetrical current present at the moment a fault occurs. This is
done for all current signals used for overcurrent protection; voltage signals bypass the DC
Offset Filter. This filter ensures no overreach of the overcurrent protection.
The Discrete Fourier Transform (DFT) uses exactly one sample cycle to calculate a phasor
quantity which represents the signal at the fundamental frequency; all harmonic
components are removed. All subsequent calculations (e.g. RMS, power, etc.) are based
upon the current and voltage phasors, such that the resulting values have no harmonic
components.
Protection Elements
All protection elements are processed twice every cycle to determine if a pickup has
occurred or a timer has expired. The protection elements use RMS current/voltage, based
on the magnitude of the phasor. Hence, protection is impervious to both harmonics and DC
transients.
Courtesy of NationalSwitchgear.com

1–4 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM CHAPTER 1: INTRODUCTION
Figure 2: Single line diagram
Table 1: Protection functions
898742A1.CDR
350 RELAY
TRIP
BUS
LOAD
3
1
52
CLOSE
50G/
51G
50P 50N
79
50G 51G
22
21
METERING
TRANSIENT RECORDER
EVENT RECORDER
51N51P 50_2
111
49
1
1
27P 59P 27X 59X 59_2 59N81U 81O
CLP 50BF 79
11111 12 2
MONITORING
BUS VT
67N
67G
1
1
ANSI Device Description
27P Phase Undervoltage
27X Auxiliary Undervoltage
49 Thermal Model
50P Phase Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50G Ground/Sensitive Ground Instantaneous Overcurrent
50BF Breaker Failure
50_2 Negative Sequence Overcurrent
51P Phase Timed Overcurrent
51G Ground Timed Overcurrent
51N Neutral Timed Overcurrent
59P Phase Overvoltage
59X Auxiliary Overvoltage
59N Neutral Overvoltage
59_2 Negative Sequence Overvoltage
67G Ground Directional Element
67N Netural Directional Element
79 Autoreclose
81U Underfrequency
81O Overfrequency
CLP Cold Load Pickup
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–5
Figure 3: Main Menu structure
ACTUAL VALUES
QUICK SETUP
SETPOINTS
MAINTENANCE
ACTUAL VALUES
A1 STATUS
A2 METERING
A3 RECORDS
A4 TARGET MESSAGES
QUICK SETUP
RELAY STATUS
NOMINAL FREQUENCY
PH CT PRIMARY
[SENS] GND CT
VT SEC. VOLTAGE
VT RATIO
AUX VT SECONDARY
AUXVTRATIO
PH TOC FUNCTION
GND TOC FUNCTION
NTRL TOC FNCTN
PH IOC1 FUNCTION
GND IOC1 FNCTN
NTRL IOC1 FNCTN
PRIMARY
▼
SETPOINTS
S1 RELAY SETUP
S2 SYSTEM SETUP
S3 PROTECTION
S4 CONTROLS
S5 INPUTS/OUTPUTS
▼
MAINTENANCE
M1 RELAY INFO
M3 BKR MAINTENANCE
M5 RELAY MAINT
M6 FACTORY SERVICE
M4 BKR MONITOR
▼
898756A1.cdr
PHASE TOC
PH TOC PICKUP
PH TOC CURVE
PH TOC TDM
▼
GROUND TOC
GROUND TOC PICKUP
GROUND TOC CURVE
GROUND TOC TDM
▼
NEUTRAL TOC
NTRL TOC PICKUP
NTRL TOC CURVE
NTRL TOC TDM
▼
PHASE IOC1
PH IOC1 PICKUP
GROUND IOC1
GND IOC1 PICKUP
NEUTRAL IOC1
NTRL IOC1 PICKUP
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–7
Specifications
NOTE
NOTE: Specifications are subject to change without notice.
Password security
PASSWORD SECURITY
Master Reset Password: ..................................8 to 10 alpha-numeric characters
Settings Password:.............................................3 to 10 alpha-numeric characters for local and remote
access
Control Password:...............................................3 to 10 alpha-numeric characters for local and remote
access
Protection
PHASE/NEUTRAL/GROUND TIME OVERCURRENT (51P/51N/51G)
Pickup Level:..........................................................0.05 to 20.00 x CT in steps of 0.01 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I < 1 x CT
Curve Shape:.........................................................ANSI Extremely/Very/Moderately/Normally Inverse
Definite Time (0.1 s base curve)
IEC Curve A/B/C/Short
IAC Extreme/Very/Inverse/Short
User Curve, FlexCurve™A/B (programmable curves)
Curve Multiplier:...................................................0.05 to 20.00 in steps of 0.01
Reset Time: ............................................................Instantaneous, Linear
Time Delay Accuracy:.......................................±3% of expected inverse time or 1 cycle, whichever is
greater
Level Accuracy:....................................................per CT input
SENSITIVE GROUND TIME OVERCURRENT (51SG)
Pickup Level:..........................................................0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.002 x CT @ I < 0.1 x CT
Curve Shape:.........................................................ANSI Extremely/Very/Moderately/Normally Inverse
Definite Time (0.1 s base curve)
IEC Curve A/B/C/Short Inverse
IAC Extreme/Very/Inverse/Short Inverse
User Curve, FlexCurve™A/B
Curve Multiplier:...................................................0.05 to 20.00 in steps of 0.01
Reset Time: ............................................................Instantaneous, Linear
Time Delay Accuracy:.......................................±3% of expected inverse time or 1 cycle, whichever is
greater
Level Accuracy:....................................................per CT input
PHASE/NEUTRAL/GROUND/NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT
(50P/50N/50G/50_2)
Pickup Level:..........................................................0.05 to 20 x CT in steps of 0.01 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I <1 x CT
Time Delay:............................................................0.00 to 300.00 sec in steps of 0.01
Operate Time:.......................................................<30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
<35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
Time Delay Accuracy: .......................................0 to 1 cycle (Time Delay selected)
Level Accuracy:....................................................per CT input
Courtesy of NationalSwitchgear.com

1–8 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG)
Pickup Level (Gnd IOC):.....................................0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.002 x CT @ I < 0.1 x CT
Time Delay:............................................................ 0.00 to 300.00 sec in steps of 0.01
Operate Time: ......................................................<30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
<35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
Time Delay Accuracy:.......................................0 to 1 cycle (Time Delay selected)
Level Accuracy:.................................................... per CT input
GROUND DIRECTIONAL
Directionality:........................................................Co-existing forward and reverse
Operating: .............................................................. Ground Current (Ig)
Polarizing Voltage:..............................................-V0calculated using phase voltages (VTs must be connected
in “Wye”)
- V0measured from Vaux input. (3V0provided by an external
open delta connection).
MTA:...........................................................................From 0ºto 359ºin steps of 1°
Angle Accuracy:...................................................±4º
Operational Delay: .............................................20 to 30 ms
NOTE
NOTE: The selection of the “P” or “R” option from “350 OTHER OPTIONS” in the order code table,
will enable the Ground directional element. The polarizing voltage used for this element is
the computed V0from the measured phase voltage inputs.
NEUTRAL DIRECTIONAL
Directionality:........................................................Forward and reverse
Polarizing:............................................................... Voltage, Current, Dual
Polarizing Voltage:..............................................- V0calculated using phase voltages (VTs must be
connected in “Wye”)
- V0measured by Vaux input (3V0provided by an external
open delta connection).
Polarizing Current:..............................................IG
MTA:...........................................................................From 0ºto 359ºin steps of 1°
Angle Accuracy:...................................................±4º
Operational Delay: .............................................20 to 30 ms
NOTE
NOTE: The selection of the “P” or “R” option from “350 OTHER OPTIONS” in the order code table will
enable the Neutral directional element. The polarizing voltage used for this element is the
computed V0from the measured phase voltage inputs. The ground polarizing current, IG, is
also available for selection.
CABLE THERMAL MODEL (49)
Current:.................................................................... Fundamental phasor
Pickup Accuracy:.................................................per current inputs
Timing Accuracy:................................................See graph below
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–9
The graph shows the trip time error with respect to the ratio of cable load and thermal
model pickup setting. With a smaller I/Ipkp ratio, the time error tends to be higher, as
accumulated through the logarithmic formula, the measurement error, and the time of
measurement. For higher I/Ipkp ratios, the time to trip is substantially more accurate. Each
point on the graph represents a trip time error, with the I/Ipkp ratio kept constant during
the test.
PHASE/AUXILIARY UNDERVOLTAGE (27P, 27X)
Minimum Voltage:...............................................Programmable from 0.00 to 1.25 x VT in steps of 0.01
Pickup Level:..........................................................0.00 to 1.25 x VT in steps of 0.01
Dropout Level: ......................................................101 to 104% of pickup
Curve: .......................................................................Definite Time, Inverse Time
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Operate Time:.......................................................Time delay ±30 ms @ 60Hz (V < 0.85 x PKP)
Time delay ±40 ms @ 50Hz (V < 0.85 x PKP)
Time Delay Accuracy: .......................................±3% of expected time or 1 cycle, whichever is greater
Level Accuracy:....................................................Per voltage input
PHASE/AUXILIARY/NEUTRAL/NEGATIVE SEQUENCE OVERVOLTAGE (59P, 59X, 59N, 59_2)
Pickup Level:..........................................................0.00 to 1.25 x VT in steps of 0.01
Dropout Level: ......................................................96 to 99% of pickup
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Operate Time:.......................................................Time delay ±35 ms @ 60Hz (V > 1.1 x PKP)
Time delay ±40 ms @ 50Hz (V > 1.1 x PKP)
Time Delay Accuracy: .......................................0 to 1 cycle
Level Accuracy:....................................................Per voltage input
UNDERFREQUENCY (81U)
Minimum Voltage:...............................................0.00 to 1.25 x VT in steps of 0.01
Pickup Level:..........................................................40.00 to 70.00 Hz in steps of 0.01
Dropout Level: ......................................................Pickup +0.03 Hz
Time Delay:............................................................0.0 to 600.0 s in steps of 0.1
Time Delay Accuracy: .......................................0 to 6 cycles (Time Delay selected)
Operate Time:.......................................................Typically 10 cycles @ 0.1Hz/s change
Level Accuracy:....................................................±0.01 Hz
OVERFREQUENCY (81O)
Minimum Voltage:...............................................0.3 x VT
Pickup Level:..........................................................40.00 to 70.00 Hz in steps of 0.01
Dropout Level: ......................................................Pickup -0.03 Hz
Time Delay:............................................................0.0 to 600.0 s in steps of 0.1
Time Delay Accuracy: .......................................0 to 6 cycles (Time Delay selected)
Operate Time:.......................................................Typically 10 cycles @ 0.1Hz/s change
Level Accuracy:....................................................±0.01 Hz
Metering
NOTE
NOTE: Full scale for CT Input is 3 x CT
PARAMETER ACCURACY RESOLUTION RANGE
3-Phase Real Power (MW) ±1% of full scale 0.1 MW ±3000 MW
3-Phase Reactive Power (Mvar) ±1% of full scale 0.1 Mvar ±3000 Mvar
3-Phase Apparent Power (MVA) ±1% of full scale 0.1 MVA 3000 MVA
Power Factor ±0.05 0.01 -0.99 to 1.00
Frequency ±0.05 Hz 0.01 Hz 40.00 to 70.00 Hz
Courtesy of NationalSwitchgear.com

1–10 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Data capture
TRANSIENT RECORDER
Buffer size: ............................................................. 3 s
No. of buffers:......................................................1x192, 3x64, 6x32
No. of channels:..................................................14
Sampling rate:......................................................32 samples per cycle
Triggers: ..................................................................Manual Command
Contact Input
Virtual Input
Logic Element
Element Pickup/Trip/Dropout/Alarm
Data: .........................................................................AC input channels
Contact input state
Contact output state
Virtual input state
Logic element state
Data storage:........................................................ RAM - battery backed-up
EVENT RECORDER
Number of events:..............................................256
Header:.................................................................... relay name, order code, firmware revision
Content:...................................................................event number, date of event, cause of event, per-phase
current, ground current, sensitive ground current, neutral
current, per-phase voltage (VTs connected in “Wye”), or
phase-phase voltages (VTs connected in “Delta”), system
frequency, power, power factor, thermal capacity
Data Storage: .......................................................Retained for 3 days
CLOCK
Setup: ....................................................................... Date and time
Daylight Saving Time
IRIG-B: ......................................................................Auto-detect (DC shift or Amplitude Modulated)
Amplitude modulated: 1 to 10 V pk-pk
DC shift: 1 to 10 V DC
Input impedance: 40 kOhm ± 10%
RTC Accuracy: ± 1 min / month at 25°C
Control
LOGIC ELEMENTS
Number of logic elements:.............................16
Trigger source inputs per element:............3
Block inputs per element: ...............................3
Supported operations: .....................................AND, OR, NOT, Pickup / Dropout timers
Pickup timer: .........................................................0 to 60000 ms in steps of 1 ms
Dropout timer:......................................................0 to 60000 ms in steps of 1 ms
BREAKER CONTROL
Operation: ..............................................................Asserted Contact Input, Logic Element, Virtual Input, Manual
Command
Function:.................................................................Opens / closes the feeder breaker
AUTORECLOSE
Reclose attempts:............................................... Up to 4 shots
Time Delay Accuracy:.......................................0 to 3 cycles (AR Dead Time selected)
Elements:................................................................ Inputs, Outputs, Breaker Status (52 status)
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–11
BREAKER FAILURE
Pickup Level:..........................................................0.05 to 20.00 x CT in steps of 0.01
Dropout Level: ......................................................97 to 98% of pickup
Time Delay Accuracy: .......................................0 to 1 cycle (Timer 1, Timer 2)
Level Accuracy:....................................................per CT input
BREAKER TRIP COUNTER
Trip Counter Limit (Pickup):.............................1 to 10000 in steps of 1
COLD LOAD PICKUP BLOCKING
Operation:...............................................................Automatically (current level), or by command (asserted input)
Function: .................................................................Block IOC functions, raise TOC pickup, for selected period of
time
Time Delay Accuracy: .......................................0 to 1 cycle (block Time)
±50 ms (outage time ≤5 min)
±1 s (outage time > 5 min)
AMBIENT TEMPERATURE
High Temperature Pickup:..............................20°C to 80°C in steps of 1°C
Low Temperature Pickup: ...............................-40°C to 20°C in steps of 1°C
Time Delay:............................................................1 to 60 min in steps of 1 min
Temperature Dropout:......................................Configurable 90 to 98% of pickup
Temperature Accuracy: ...................................±10°C
Timing Accuracy: ................................................±1 second
Inputs
CONTACT INPUTS
Inputs:.......................................................................10[8]
Selectable thresholds: ......................................17, 33, 84, 166 VDC
Recognition time:................................................1/2 cycle
Debounce time: ...................................................1 to 64 ms, selectable, in steps of 1 ms
Maximum input voltage & continuous
current draw:...................................................300 VDC, 2 mA, connected to Class 2 source
Type:..........................................................................opto-isolated inputs
External switch: ...................................................wet contact
NOTE
NOTE: The number of contact inputs - 8 or 10 - is dependent on the order code selected.
PHASE & GROUND CURRENT INPUTS
CT Primary:.............................................................1 to 6000 A
Range: ......................................................................0.02 to 20 × CT
Input type: ..............................................................1 A or 5 A (must be specified with order)
Nominal frequency: ...........................................50/60 Hz
Burden: ....................................................................<0.1 VA at rated load
Accuracy:................................................................±1% of reading at 1× CT
±3% of reading from 0.2 to 20 × CT
±20% of reading from 0.02 to 0.19 × CT
CT withstand: ........................................................1 second at 100 × rated current
2 seconds at 40 × rated current
continuous at 3 × rated current
Courtesy of NationalSwitchgear.com

1–12 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
SENSITIVE GROUND CURRENT INPUT
CT Primary: ............................................................1 to 600 A
Range:......................................................................0.002 to 3 × CT
Input type:.............................................................. 1 A or 5 A (must be specified with order)
Nominal frequency:........................................... 50/60 Hz
Burden: ....................................................................<0.1 VA at rated load
Accuracy:................................................................±1% of reading at 0.1× CT
±3% of reading from 0.02 to 3 × CT
±20% of reading from 0.002 to 0.019 × CT
CT withstand:........................................................ 1 second at 100 × rated current
2 seconds at 40 × rated current
continuous at 3 × rated current
PHASE/AUX VOLTAGE INPUTS
Source VT: ..............................................................0.12 to 65 kV / 50 to 220 V
VT secondary range:.........................................50 to 240 V
VT ratio: ................................................................... 1 to 5000 in steps of 1
Nominal frequency:........................................... 50/60 Hz
Accuracy:................................................................±1.0% throughout range
Voltage withstand:.............................................260 VAC continuous
Outputs
FORM-A RELAYS
Configuration: ......................................................2 (two) electromechanical
Contact material:................................................ silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive): ...........................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive):............................................277 VAC / 10 A
FORM-A VOLTAGE MONITOR
Applicable voltage: ............................................20 to 250 VDC
Trickle current: .....................................................1 to 2.5 mA
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–13
FORM-C RELAYS
Configuration:.......................................................5 (five) electromechanical
Contact material:................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive):............................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................277 VAC / 10 A
TRIP / CLOSE SEAL-IN
Relay 1 trip seal-in:.............................................0.00 to 9.99 s in steps of 0.01
Relay 2 close seal-in:.........................................0.00 to 9.99 s in steps of 0.01
Power supply
HIGH RANGE POWER SUPPLY
Nominal:..................................................................120 to 240 VAC
125 to 250 VDC
Range: ......................................................................60 to 300 VAC (50 and 60 Hz)
84 to 300 VDC
Ride-through time: .............................................35 ms
LOW RANGE POWER SUPPLY
Nominal:..................................................................24 to 48 VDC
Range: ......................................................................20 to 60 VDC
ALL RANGES
Voltage withstand: .............................................2 × highest nominal voltage for 10 ms
Power consumption: .........................................15 W nominal, 20 W maximum
20 VA nominal, 28 VA maximum
Communications
SERIAL
RS485 port: ............................................................Opto-coupled
Baud rates:.............................................................up to 115 kbps
Response time:.....................................................1 ms typical
Parity:........................................................................None, Odd, Even
Protocol: ..................................................................Modbus RTU, DNP 3.0, IEC 60870-5-103
Maximum distance: ...........................................1200 m (4000 feet)
Isolation:..................................................................2 kV
ETHERNET (COPPER)
Modes:......................................................................10/100 MB (auto-detect)
Connector:..............................................................RJ-45
Protocol: ..................................................................Modbus TCP, DNP3.0, iec 60870-5-104, IEC 61850 GOOSE
Courtesy of NationalSwitchgear.com

1–14 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
ETHERNET (FIBER)
Fiber type: .............................................................. 100 MB Multi-mode
Wavelength:..........................................................1300 nm
Connector: .............................................................MTRJ
Protocol:..................................................................Modbus TCP, DNP3.0, iec 60870-5-104, IEC 61850 GOOSE
Transmit power: ..................................................-20 dBm
Receiver sensitivity: ...........................................-31 dBm
Power budget:...................................................... 9 dB
Maximum input power:....................................-11.8 dBm
Typical distance: .................................................2 km (1.25 miles)
Duplex:.....................................................................half/full
USB
Standard specification:....................................Compliant with USB 2.0
Data transfer rate: .............................................115 kbps
Testing and certification
APPROVALS
Applicable Council Directive According to
Low voltage directive EN60255-5 / EN60255-27 / EN61010-1
CE compliance EMC Directive EN60255-26 / EN50263
EN61000-6-2
UL508
North America cULus UL1053
C22.2.No 14
ISO Manufactured under a registered
quality program
ISO9001
TYPE TESTS
Test Reference Standard Test Level
Dielectric voltage withstand 2.3KV
Impulse voltage withstand EN60255-5 5KV
Damped Oscillatory IEC61000-4-18IEC60255-22-1 2.5KV CM, 1KV DM
Electrostatic Discharge EN61000-4-2/IEC60255-22-2 Level 4
RF immunity EN61000-4-3/IEC60255-22-3 Level 3
Fast Transient Disturbance EN61000-4-4/IEC60255-22-4 Class A and B
Surge Immunity EN61000-4-5/IEC60255-22-5 Level 3 & 4
Conducted RF Immunity EN61000-4-6/IEC60255-22-6 Level 3
Power Frequency Immunity EN61000-4-7/IEC60255-22-7 Class A & B
Voltage interruptionand Ripple DC IEC60255-11 15% ripple, 200ms
interupts
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal Vibration IEC60255-21-1 Class 1
Shock & Bump IEC60255-21-2 Class 1
Siesmic IEC60255-21-3 Class 2
Power magnetic Immunity IEC61000-4-8 Level 5
Pulse Magnetic Immunity IEC61000-4-9 Level 4
Courtesy of NationalSwitchgear.com
Other manuals for ML Series 350
3
Table of contents
Other GE Relay manuals