GE 60-806-95R-16Z - Security Concord Express System Control... User manual

)
*(6HFXULW\
S t a t u s
F e a t u r e s
p r e s s b o t h
L i g h t s
S y s t e m
A w a y
Q u i c k E x i t
O f f
N o D e l a y
p r e s s b o t h
p r e s s b o t h
T e s t S y s t e m W e e k l y
S i l e n t
S t a y
D
*
7
0 #
8
B
A
4
1
56
23
B y p a s s
e n u
C9
P r o g r a m U s e r S e t t i n g s
p r e s s 0 - 9 f o r o t h e r e n t r i e s .
P r e s s 1 f o r O F F ; p r e s s 2 f o r O N ;
P r e s s # t o s e l e c t o p t i o n o r a c c e p t e n t r y .
0 6
0 7
0 5
0 4
1 3
1 4
1 2
1 1
A r m t o S T A Y
Q u i c k G u i d e
D i s a r m S y s t e m / C a n c e l A l a r m
i f d e s i r e d .
2
0 1
0 2
0 3
3
1
0 8
0 9
1 0
P r e s s t o d e s e l e c t o p t i o n o r c a n c e l e n t r y .
C l o s e a l l p r o t e c t e d d o o r s a n d w i n d o w s .
P r e s s 3 C O D E .
E x i t p r e m i s e s t h r o u g h d e l a y d o o r .
2
3
1
P r e s s 2 C O D E .
C l o s e a l l p r o t e c t e d d o o r s a n d w i n d o w s .
P r e s s 4 t o a r m d e l a y d o o r s i n s t a n t l y ,
A r m t o A W A Y
Z o n e / S e n s o r N u m b e r
P r e s s 1 C O D E . 2
1
P r e s s A o r B t o s c r o l l t h r o u g h m e n u s .
M a k e s u r e s y s t e m i s d i s a r m e d .
2
1
P r e s s 7 1 t o t u r n C H I M E o n o r o f f .
M a k e s u r e s y s t e m i s d i s a r m e d .
2
1
T u r n C H I M E O n / O f f
P r e s s B Y P A S S C O D E S e n s o r N o .
A r m s y s t e m t o d e s i r e d l e v e l .
y p a s s S e n s o r s
S y s t e m i s O K
S t a t u s
F e a t u r e s
p r e s s b o t h
L i g h t s
S y s t e m
A w a y
Q u i c k E x i t
O f f
N o D e l a y
p r e s s b o t h
p r e s s b o t h
T e s t S y s t e m W e e k l y
S i l e n t
S t a y
D*
7
0 #
8
B
A
4
1
56
23
B y p a s s
e n u
C9
A r m e d
R e a d y
Installation Instructions
466-1665 Rev G
June 2004
Concord Express
Part No:
60-806
60-806-95R
ZZZ*(6HFXULW\FRP

FCC Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by GE Interlogix can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the affected equipment and the panel receiver to separate outlets, on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
ACTA Part 68
This equipment complies with Part 68 of the FCC Rules. Located on this equipment is a label that contains, among other information, the FCC registration num-
ber and the ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
FCC Part 68 Registration No. B4ZUSA-27621-AL-E REN: 0.2B
The REN is used to determine the maximum number of devices that may be connected to your telephone line. Excessive RENs on a telephone line may result in
devices not ringing in response to an incoming call. In most areas, the sum of all device RENs should not exceed five (5.0). To be certain of the number of
devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2001, the
REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal
point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and require-
ments as adopted by ACTA. A compliant telephone cord and modular plug is provided with this product. It is designed to be connected to a compliant modular
jack that is also compliant. See the Installation Instructions for details.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment
(telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly
installed RJ31X jack that is electrically in series and ahead of all other equipment attached to the same telephone line. Proper installation is depicted in the fol-
lowing diagram. If you have any questions concerning these instructions, consult your local telephone company or a qualified installer about installing an RJ31X
jack and alarm dialing equipment for you.
If this equipment causes harm to the telephone network, the telephone company may temporarily disconnect your service. If possible, you will be notified in
advance. When advance notice is not practical, you will be notified as soon as possible. You will also be advised of your right to file a complaint with the FCC.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. You will be
given advance notice in order to maintain uninterrupted service.
If you experience trouble with this equipment, please contact the company that installed the equipment for service and/or repair information. The telephone com-
pany may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure that the equipment is not malfunctioning.
This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs
Patent Information
This product and the use of this product may be covered by one or more of the following patents: 5,805,063, 5,872,512, 5,942,981, 4,855,713. Except expressly
provided herein, the purchase of this product shall not constitute a license or otherwise provide a right to practice a method covered by any of the identified pat-
ents. GE Interlogix hereby grants the purchaser of this product a limited, non-exclusive license to practice the methods patented in the identified patents solely
with products manufactured, sold or licensed by GE Interlogix. This license grant does not extend to the use of unlicensed, third party products with this product.
N e t w o r k
S e r v i c e
P r o v i d e r ' s
F a c i l i t i e s
Telephone
L i n e
N e t w o r k
D e m a r c a t i o n
P o i n t
Telephone
A n s w e r i n g
S y s t e m
F a x a c h i n e
C o m p u t e r
Telephone
Telephone
A l a r m D i a l i n g
E q u i p m e n t
R J 3 1 X
J a c k
U n u s e d
R J - 1 1 J a c k
U n u s e d
R J - 1 1 J a c k
C u s t o m e r P r e m i s e s E q u i p m e n t a n W i r i n g

Canada Notice
The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunica-
tions network protective, operational, and safety requirements. The department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equip-
ment must also be installed using an acceptable method of connection. In some cases, the company’s inside wiring associated with a single-line individual ser-
vice may be extended by means of a certified connector assembly (telephone extension cord). The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the
user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
For your protection, make sure that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are
connected together
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device,
to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the LNs of all the
devices does not exceed 100. Load Number: .1 The term “IC:” before the certification/registration number only signifies that the Industry Canada technical
specifications were met. IC: 867A 787SIMON
“AVIS: - L ´étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme a cer-
taines normes de protection, d ´ exploitation et de sécurité des réseaux de télécommunications. Le ministère n ´ assure toutefois pas que le matériel fonctionnera
a la satisfaction de l ´ utilisateur.
Avant d ´ installer ce matériel, l ´ utilisateur doit s ´ assurer qu´ il est permis de le raccorder aux installations de l ´ enterprise locale de télécommunication. Le
matériel doit également etre installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l´ enterprise utilisés pour un service
individuel a ligne unique peuvent etre prolongés au moyen d´ un dispositif homologué de raccordement (cordon prolongateur téléphonique interne). L ´ abonné
ne doit pas oublier qu ´ il est possible que la conformité aux conditions énoncées ci-dessus n ´ empechent pas le dégradation du service dans certaines situations.
Actuellement, les enterprises de télécommunication ne permettent pas que l ´ on raccorde leur matériel a des jacks d ´ abonné, sauf dans les cas précis prévus pas
les tarrifs particuliers de ces enterprises.
Les réparations de matériel homologué doivent etre effectuées pas un centre d ´ entretien canadien autorisé désigné par le fournisseur. La compagne de télécom-
munications peut demander a l ´ utilisateur de débrancher un appareil a la suite de réparations ou de modifications effectuées par l ´ utilisateur ou a cause de mau-
vais fonctionnement.
Pour sa propre protection, l ´ utilisateur doit s ´ assurer que tous les fils de mise a la terre de la source d ´ énergie électrique, des lignes téléphoniques et des
canalisations d ´´ eau métalliques, s ´ il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissment. - L ´ utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d ´ inspection des installations électriques,
ou a electricien, selon le cas”.
Une note explicative sur les indices de charge (voir 1.6) et leur emploi, a l ´ intention des utilisateurs du matériel terminal, doit etre incluse dans l ´ information
qui accompagne le materiel homologué. La note pourrait etre rédigée selon le modèle suivant:
“L ´ indice de charge (IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un
circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n ´ import somme des indices de charge de l ´ ensem-
ble des dispositifs ne dépasse pas 100.”
L ´ Indice de charge de cet produit est ____________.
Do not attempt to make connections yourself. Contact the appropriate electrician or electric inspections
High sensitivity should only be used in extremely quiet environments where thermal
!
authority.
Caution
!
5HG)R[5RDG
$UGHQ+LOOV01
7HFKQLFDO6XSSRUW
)
*(6HFXULW\&RQFRUGLVDWUDGHPDUNRI*(6HFXULW\$OORWKHUWUDGHPDUNVDUH
SURSHUWLHVRIWKHLURZQHUV
$OOULJKWVUHVHUYHG
*(6HFXULW\

i
Contents
About This Manual 1
Special Installation Requirements 1
UL Listed Systems ......................................................................................................................................1
UL-Canada Listed Systems ........................................................................................................................3
Planning the Installation 3
Standard Panel ............................................................................................................................................3
Touchpads ...................................................................................................................................................3
SnapCard .....................................................................................................................................................3
Installing the System 4
Determine the Panel Location .....................................................................................................................4
Total System Power and Wire Length Guidelines ......................................................................................5
Mounting the Panel .....................................................................................................................................6
Identify Panel Components .........................................................................................................................7
Connecting the Panel to Earth Ground .......................................................................................................7
Installing Optional SnapCards ....................................................................................................................8
Installing Optional Hardwire Input Modules (HIMs) .................................................................................8
Connecting Detection Devices to Panel Zone Inputs .................................................................................9
Connecting Sirens .....................................................................................................................................12
Connecting Siren Drivers, Self-Contained Sirens, and Bells ...................................................................13
Connecting Touchpads ..............................................................................................................................14
Installing an RJ-31X Phone Jack (13-081) ...............................................................................................14
Connecting the Phone Line to the Panel with a DB-8 Cord .....................................................................15
Connecting the AC Power Transformer ...................................................................................................16
Powering Up the Panel .............................................................................................................................16
Programming the Panel 17
Entering Programming Mode ...................................................................................................................17
Touchpad Button Programming Functions ...............................................................................................18
Moving Through Program Mode Tiers and Menus ..................................................................................18
Programming Tier 1 Menu Items ..............................................................................................................19
Programming Tier 2 Menu Items ..............................................................................................................19
Exiting Programming Mode .....................................................................................................................42
Entering User Programming Mode ...........................................................................................................43
Downloader Programming ........................................................................................................................46
Testing the System 46
Basic System Commands ..........................................................................................................................47
Testing Zones/Sensors ..............................................................................................................................47
Testing Phone Communication .................................................................................................................48
Testing Central Station/Pager Communication .........................................................................................48
Testing Outputs/Sirens ..............................................................................................................................48

ii
Changing Fixed Display LCD Touchpad Chime and Trouble Beep Tones ..............................................49
Troubleshooting 50
Appendix A: System Configuration Worksheets 54
Cross-Zoning ............................................................................................................................................57
Appendix B: Programming Mode Menus and Settings 66
Specifications 68
Wiring Diagram Back Page

About This Manual
1
About This
Manual
This manual provides information for planning, installing, programming, and testing
this security system. When necessary, this manual refers you to other documentation
included with compatible devices.
Planning sheets are included for you to record hardware layout and software program-
ming settings.
Special
Installation
Requirements
This security system can be used as a wire warning system, an intrusion alarm system,
an emergency notification system, or any combination of the three.
Some installations may require configurations dictated by city or state codes, insur-
ance, or Underwriter’s Laboratories (UL). This section describes the various compo-
nent and configuration listings.
UL Listed Systems
This section describes the requirements for UL Listed systems.
Basic System
• Control Panel (60-806, 60-806-95R)
• Backup Battery, 12 VDC, 4 AH (60-681)
• SuperBus 2000 2x16 LCD Touchpad (60-746-01), SuperBus 2000 Fixed Display
Touchpad (60-820), SuperBus 2000 2x20 LCD Touchpad (60-803), or SuperBus
2000 2x20 VFD Touchpad (60-804)
• Standard Class II 16.5 VAC, 25 VA Power Transformer; manufacturer—Tech Elec-
tro Ind, Inc. Part No. 48A0164 (60-822)
• 15-Watt, Dual Tone Siren (13-469) or Hardwire Siren (13-046)
Household Burglary Alarm System Unit (UL 1023)
Basic system, plus:
• Hardwire Magnetic Contact (Sentrol part # 1075-N or 1038T-N) or Wireless Learn
Mode Door/Window Sensor (60-362), Wireless Learn Mode PIR Motion Sensor
(60-703-95, 60-511, or 60-639)
• IMMEDIATE TROUBLE BEEPS set to on
• UL 98 OPTIONS set to on
• RECEIVER FAILURE set to on
• EXIT DELAY set to 60 seconds or less
• QUICK EXIT set to off
• SIREN TIMEOUT set to 4 minutes or more
• SIREN VERIFY set to on
• ENTRY DELAY set to 45 seconds or less
• RF TX TIMEOUT set to 24 hours
• EXTENDED DELAY set to off
• TWO TRIP ERROR set to off
• ALARM VERIFY set to off
• DISABLE TROUBLE BEEPS set to off
• SYSTEM TAMPER set to on
Household Fire Warning System (UL 985)
Basic system plus:

Special Installation Requirements 2
• Hardwire Smoke Detector:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, or 2400TH learned into Sen-
sor Group 26 Sentrol (ESL) models 429AT, 521B, or 521BXT learned into sensor group 26
• Wireless Smoke Sensor 60-506-319.5 or 60-645-95 learned into sensor group 26
• IMMEDIATE TROUBLE BEEPS set to on
• UL 98 OPTIONS set to on
• RECEIVER FAILURE set to on
• SIREN VERIFY set to on
• RF TX TIMEOUT set to 4 hours
• ALARM VERIFY set to off
• DISABLE TROUBLE BEEPS set to off
UL 1023 & 985 24-Hour Backup
• For 24-hour backup, the total current draw for all connected devices is limited to 90 mA con-
tinuous using a 4.0 AH battery.
SIA System Requirements
Note
UL requirements take prior-
ity over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic System on page
1, plus:
• If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
The following table describes non-programmable (hard coded) system operation as required to
meet ANSI-SIA CP-01 and is provided only for your reference.
Shortcut
#
Function Programming
Page Reference
Testing Page
Reference
Default
Setting
Required Setting
0003 SIA False Alarm
Reduction
21 46 On On
0013 Exit Extension 22 46 On On
0014 Auto Stay Arming 22 46 On On
0016 Duress Code 23 46 Disabled Disabled
02005 Dialer Abort 28 46 On On
02006 Dialer Abort Delay 28 46 30 Sec. 15-45 sec.
02007 Cancel Message 28 46 On On
02009 Call Wait Cancel 28 46 Disabled On if reporting to central station and
customer has call waiting service
0310 Entry Delay 31 46 30 sec. 30-240 sec.
0311 Exit Delay 31 46 60 sec. 45-184 sec.
05014 Swinger Limit 35 46 1 1
0900 Smoke Verify 42 46 Off On if smoke alarms are programmed
into system
N/A Cross Zoning 57 46 Disabled Enabled for zones with a high
probability of false alarms
Function Operation
Disarm During Entry Delay Enter Code Only (or 1 + CODE)
Cancel Alarm Enter Code Only (or 1 + CODE)
Abort Annunciation Enabled

Planning the Installation
3
UL 1635 Digital Alarm Communicator System
Note
For UL 1635 installations,
Entry Delay plus Dialer
Abort Delay must not
exceed 60 seconds.
Same as UL 1023 & 985 plus:
• AC FAILURE set to on
• PHONE NUMBER must be programmed
• HIGH LEVEL REPORTS set to on.
• LOW LEVEL REPORTS set to on
• PHONE TEST set to on
• AUTO PHONE TEST set to on
• PHONE TEST FREQ. set to 1
• NEXT PHONE TEST set to 1
• LOW CPU BATTERY set to on
• COMM FAILURE set to on
• RF TX TIMEOUT set to 4 hours
Central Station Reporting
The panel has been tested with the following central station receivers using SIA and Contact ID
reporting formats:
• ITI CS-5000 Central Station Receiver
• Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2
UL-Canada Listed Systems
This section describes the requirements for ULC (UL Canada) Listed systems.
• CSA Certified Accessories
The UL-Canada Basic System is nearly the same as the “UL Basic System” described previ-
ously, the only difference being that you must use the ITI 60-679-CN Class II transformer
(Basler part number BE 116250-AAA) to power the panel.
• Residential Burglary Alarm System Unit
(CAN/ULC-S309)
Same as “UL Basic System and Household Burglary Alarm System Unit (UL 1023)”
described previously and siren timeout must be set to 5 minutes or more.
Residential Fire Warning System Control Unit (CAN/ULC-S545-M89)
Same as “UL Basic System and Household Fire Warning System (UL 985)” described previ-
ously.
Note
For 24-hour backup, exter-
nal power drain is limited to
90 mA continuous using a
4.0AH battery.
California State Fire Marshall Listed Systems
Same as Household Fire Warning System (UL 985), plus:
• SMOKE VERIFY must be set to off
Planning the
Installation
This section describes the system capabilities to help you get familiar with the system. To help
you prepare for system installation, Appendix A provides planning sheets with tables that let you
record the hardware and programming configuration of the system.
Standard Panel
The following describes the basic panel (out-of-box) hardware capabilities.
•Power: Input for an AC step-down, plug-in style transformer.
•Auxiliary Power Output: Output that supplies up to 750 mA (90 mA for UL Listed systems)
at 12 VDC for bus devices and hardwired detectors, such as touchpads and motion detectors.
Cancel Report Annunciation Enabled
Function Operation

Installing the System 4
•Bus A and B: Input and output that provide communication between bus devices and the
panel.
•2 Onboard Outputs: One 12-volt and one open-collector output that can be set up to activate
other signalling devices, based on system events.
•6 Supervised Hardwire Zones: Factory programmed inputs for various hardwired detectors
(see “Accessory Modules Menu” on page 40 for a list of factory programmed settings). Zone
6 can be set up in programming to accept 2-wire smoke detectors.
•Built-In Radio Receiver: Allows use of GE Security 319.5 MHz. crystal and/or SAW Learn
Mode wireless sensors and touchpads.
•Phone Line Connection: Allows the panel to communicate with central monitoring stations
and pagers.
Touchpads
The following describes the different touchpads that can be used for system programming and
operation.
•SuperBus 2000 2x16 LCD Alphanumeric Touchpad: Provides complete system program-
ming and operation control. Displays system messages, and indicates system status.
•SuperBus 2000 2x20 LCD/VFD Alphanumeric Touchpads: Provide complete system pro-
gramming and operation control, display system messages and indicate system status.
•SuperBus 2000 Fixed Display LCD Touchpad: Provides operation control and user pro-
gramming access (not installer or dealer programming). Displays system messages and indi-
cates system status.
SnapCard™
The following SnapCards expand the system as described:
•8Z Input SnapCard: Provides eight additional hardwire zone inputs, of which two are dedi-
cated for 2-wire smoke detectors.
•4 Output SnapCard: Provides four form C relay outputs that can be set up to activate other
signalling devices, based on system events.
•4Z Input/2 Output Combo SnapCard: Provides three standard hardwire zone inputs, one
2-wire smoke detector loop input, and two outputs that can be set up to activate other signal-
ling devices that are based on system events.
Installing the
System
This section describes how to install the system control panel. Before starting the installation,
plan your system layout and programming using the worksheets provided in Appendix A.
Installing the system consists of the following steps:
• Determining the Panel Location
• Identifying Total System Power and Wire Length Guidelines
• Mounting the Panel
• Identifying Panel Main Components
• Installing Optional SnapCards
• Installing Optional HIMs
• Connecting Detection Devices to Panel Zone Inputs
• Connecting Sirens
• Connecting Touchpads
• Installing an RJ-31X Phone Jack
• Connecting the Phone Line to the Panel with a DB-8 Cord
• Connecting the AC Power Transformer
• Powering Up the Panel
Determine the Panel Location
Before permanently mounting the panel, determine the location using the following guidelines:

Installing the System
5
• To help reduce wire run lengths and labor, centrally locate the panel with relation to detection
devices whenever possible.
• Avoid running wires parallel with electrical wiring or fixtures, such as fluorescent lighting, to
prevent wire runs from picking up electrical noise.
• Mount the panel at a comfortable working height (about 45 to 55 inches from the floor to the
bottom of the panel, as shown in Figure 1).
• Leave space to the left and right of the panel for wiring, phone jack, and optional modules.
• For installations that include wireless sensors, allow at least 10 inches above the panel cabi-
net for the antenna.
• Allow at least 24 inches in front of the panel for opening the panel door.
Figure 1. Determining Panel Location
Total System Power and Wire Length Guidelines
Note
A) Class 2, Class 3, and
power-limited fire alarm cir-
cuits must be installed using
FPL, FPLR, FPLP, or substi-
tute cable permitted by the
National Electrical Code
ANSI/NFPA 70. Wire that
extends beyond the cable
jacket must be separated
from all other conductors by
a minimum of 1/4-inch or by
a nonconductive barrier.
OR
(B) Class 2, Class 3, and
power-limited fire alarm cir-
cuit conductors must be
installed as Class 1 or higher
circuits.
Table 1 describes panel voltage/current output ranges. See Appendix A for maximum and
standby device current draw.
Total system wire allowed varies depending on devices powered by the panel, wire length
between devices and the panel, and the combined wire length of all devices.
Table 2 describes the maximum wire length allowed between compatible devices and the panel.
1 6 . 2 5 "
9 "
11"
21"
45-55"
10"
Floor
Antenna
Area
Phone Jack and
Optional Module
Mounting Area
Note:
Allow at Least 24’ in Front
of Panel to Allow for Opening
Cabinet Door and Access to
Table 1: Panel Voltage/Current Output Ranges
Panel
Terminal Voltage Range Max. Current
4 (+12V) 8.5 - 14.2 VDC
9.1 - 14.2 VDC (UL)
750 mA—non-UL Listed systems
90 mA—UL Listed systems
7 (OUT1/+12) 8.5 - 14.2 VDC 1.25 A at default configuration—non-UL Listed systems
650 mA—UL Listed systems
17 (Z6/2W+) 8.9 - 13.7 VDC 80 mA
Table 2: Maximum Device Wire Lengths
Device Max. Wire Length to Panel Wire Type
AC Power Transformer 18 AWG—25 ft. Stranded
Earth Ground 16 AWG—25 ft. Solid
Telephone (RJ-31X) as required Stranded
Detection Devices 22 or 18 AWG—300 ohms maximum loop
resistance + 2k end-of-line
Stranded

Installing the System 6
Mounting the Panel
Use the following procedure to mount the panel to the wall or wall studs.
Make sure you are free of static electricity whenever you work on the panel with the
cover open. To discharge any static, first touch the metal panel chassis, then stay in con-
tact with the chassis when touching the circuit board. Using an approved grounding
strap is recommended.
¾To mount the panel cabinet and circuit board:
1. Open the panel door and slide it up to remove it from the cabinet. Set the door aside.
2. Remove the knockout to provide access for system wiring (see Figure 2).
3. Feed all device wires through the knockout and place the panel in position against the wall.
4. Level the panel and mark the top and bottom mounting holes (see Figure 2).
Figure 2. Mounting Holes
5. Install anchors where studs are not present.
6. Partially insert screws into the two top mounting hole locations, then hang the panel on the
two screws.
7. Recheck for levelness, insert the two lower screws, and tighten all four mounting screws.
2-Wire Smoke Detectors 22 AWG—330 ft.
18 AWG—830 ft.
(based on 10 ohms maximum loop resistance
+ 2k end-of-line)
Stranded
Sirens 22 AWG—80 ft.
18 AWG—200 ft. when using ITI siren models
13-469 or 13-046
Stranded
SuperBus 2000 2x16 LCD
Alphanumeric Touchpad
22 AWG—300 ft.
18 AWG— 750 ft.
Stranded
SuperBus 2000 Fixed Display
LCD Touchpad
22 AWG—300 ft.
18 AWG— 750 ft.
Stranded
SuperBus 2000 2x20 LCD
Alphanumeric Touchpad
22 AWG—250 ft.
18 AWG— 600 ft.
Stranded
SuperBus 2000 2x20 VFD
Alphanumeric Touchpad
22 AWG—250 ft.
18 AWG— 600 ft.
Stranded
SuperBus 2000 Hardwire Input
Module
22 AWG—1,800 ft.
18 AWG— 4,500 ft.
Stranded
Table 2: Maximum Device Wire Lengths (Continued)
Device Max. Wire Length to Panel Wire Type
Caution
!
Knockout
Mounting Holes

Installing the System
7
8. Install the antenna housing (included with the panel) by pushing it down into the top left hole
of the cabinet until it snaps into place (see Figure 3).
9. Install the circuit board into the cabinet, inserting the loop antenna loop up into the antenna
housing (see Figure 3), then secure the circuit board with the four mounting screws
(included).
Figure 3. Installing the Antenna Housing and the Circuit Board
Identify Panel Components
Before installing devices and making wiring connections, familiarize yourself with the main
components of the panel. Figure 4 shows the main component locations on the circuit board.
Figure 4. Main Component Locations
Connecting the Panel to Earth Ground
For maximum protection from lightning strikes and transients, connect the lower-right circuit
board screw to earth ground as shown in Figure . Use 16-gauge, solid copper wire from an earth
grounded cold water pipe clamp to the panel.
6 0 8 0 6 G 3 2 D D S F
Antenna Housing Insert Antenna Loop
Up Into Antenna Housing
Antenna Loop
Backup
Battery
Connections
Terminal Strip
EEPROM
Micro
Processor
SnapCard
Header
Programming
Touchpad
Header
Black
Red

Installing the System 8
Note
For best results, it is recom-
mended that you crimp a
spade lug on the wire end at
the panel and secure the lug
under the circuit board
screw as shown in Figure .
Figure 5. Connecting the Panel to Earth Ground
Installing Optional SnapCards
The SnapCard Header on the lower-left side of the panel accepts one of the following SnapCard
models:
• 8Z Input SnapCard—60-757
• 4 Output SnapCard—60-758
• 4Z Input/2 Output Combo SnapCard—60-756
Install the desired SnapCard onto the panel SnapCard Header and secure it in place with two
screws, included with the card (Figure 6).
Connect all necessary input/output wiring using the installation instructions included with the
SnapCard.
Figure 6. Installing a SnapCard
Note
Use of the HIM with the
Concord™ Express panel
has not been investigated by
UL.
Installing Optional Hardwire Input Modules (HIMs)
Each SuperBus 2000 8-Zone Input Module (60-774) adds eight supervised hardwire zones to the
system. Both normally open and normally closed detectors can be wired to module inputs (see
Figure 8).
Connect all necessary input/output wiring using the installation instructions included with the
HIM.
Pipe
Water Pipe
Ground Clamp
Knockout
Antenna Loop
Push SnapCard Connector
Onto Panel Header
Secure SnapCard with
Two Screws

Installing the System
9
Figure 7. Installing and Connecting the HIM in the Concord Express
Connecting Detection Devices to Panel Zone Inputs
The panel comes with six factory programmed onboard hardwire zones (see “Accessory Modules
Menu” on page 40 for factory settings). Zone inputs 1 through 6 are supervised using a 2k-ohm,
end-of-line resistor (included with panel) at the last device on the circuit.
Note
Install an end-of-line resis-
tor on all unused, factory
programmed, onboard panel
zones.
All six zones accept either normally open (N/O) or normally closed (N/C) detection devices (see
Figure 8).
The maximum loop resistance for each zone input is 300 ohms, plus the 2k end-of-line (EOL)
resistor.
Connecting Intrusion Detection Devices
Figure 8 shows the typical wiring for N/C and N/O door/window intrusion detection.
Figure 8. Connecting N/C and N/O Intrusion Detection Circuits
Figure 9 shows the typical wiring for Optex model RX-040 (PI) PIR motion detectors. The mini-
mum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.1 VDC for UL
Listed systems).
8642137A.DSF
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6
Z O N E C O O N
Z O N E 1
Z O N E 2
+ 1 2 V D C ( R E D )
B U S A ( G R N )
B U S B ( W H T )
G N D ( B L K )
Z O N E 3
Z O N E 4
Z O N E 5
Z O N E C O O N
Z O N E C O O N
Z O N E 6
Z O N E 7
Z O N E C O O N
Z O N E 8
3 4 5 6
+ 1 2 V AB
G N D B U S
To Zone Input Device
(Shared Commons)
Panel Terminals
9 1 0 1 1
Z O N E
1
Z C O Z O N E
2
60806G 06D .D S4
Panel Terminals
Normally
Closed
(N/C)
Contacts
in Series
Normally
Open
(N/O)
Contacts
in Parallel
2k Ohm
EOL Resistor
(49-454)
2k Ohm
EOL Resistor
(49-454)

Installing the System 10
Figure 9. Connecting a PIR Motion Detector
Note
When using 2-wire smoke
detectors on Zone 6, the
Two-Wire Smoke setting (in
program mode) must be
turned on before entering
the LEARN SENSORS menu.
See ONBOARD OPTIONS—
INPUTS in the section “Pro-
gramming the Panel” (17) for
complete details.
Connecting 2-Wire Smoke Detectors
Zone input 6 can be set up (in program mode) to accept 12 VDC, 2-wire smoke detectors by the
following manufacturers:
• System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH
• Sentrol (ESL) models 429AT, 521B, 521BXT—models 521B and 521BXT require the
following dip switch settings: 1-on, 2-off.
When set up for 2-wire smoke detectors, zone 6 can handle up to 10 smoke detectors with 120
µA maximum idle current per detector. Maximum total loop current allowed in an alarm condi-
tion is 80 mA. The maximum loop resistance for 2-wire smoke detectors connected to zone input
6 is 10 ohms, plus the 2k end-of-line resistor.
Connect one or more 2-wire smoke detectors to the panel as shown in Figure 10.
1 2 1 3
Z O N E
3
Z C O
3 4
+ 1 2 V
G N D
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
Use only the 2-wire smoke detector models described above. Alarm signals from other
detectors may not be processed correctly if the panel has lost AC power and is operating
only from the backup battery.
Warning
!
Panel terminal 16 (ZCOM/2W-) cannot be used as a common loop connection for any
other zones, when using Zone 6 for 2-wire smoke detectors.
Caution
!

Installing the System
11
Figure 10. Connecting 2-Wire Smoke Detectors
Connecting 4-Wire Smoke Detectors
Zone inputs 1 through 6 can be used with 4-wire smoke detectors that latch and remain in the
alarm state until power is removed and then restored to the detector.
The panel provides this power interruption from panel terminal 8 (OUT2/OC) provided that the
output configuration number is set (in program mode) to 01500.
For more information on output configuration numbers, see the section “Programming the Panel”
and the tables in Appendix A. Use only 4-wire smoke detectors that operate on 8.5 to 14.2 VDC.
Note
The Two-Wire Smoke set-
ting (in program mode) must
be off when connecting
4-wire smoke detectors to
zone 6.
For UL Listed systems,
4-wire smoke detectors can-
not be connected to onboard
panel zone inputs.
Connect up to five Sentrol (ESL) model 449AT (ITI part no. 13-360) smoke detectors to panel
power input as shown in Figure 11.
1 6 1 7
Z C O /
2 W -
Z 6 /
2 W +
+
-
+
-
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
Panel
Terminals

Installing the System 12
Figure 11. Connecting 4-Wire Smoke Detectors
Connecting Sirens
Note
Install all sirens/speakers
indoors, in a concealed loca-
tion.
Two onboard programmable outputs allow for siren connections when using the default setting
of each output. For more information on output configuration numbers, see the section “Pro-
gramming the Panel” and the tables in Appendix A.
The following describes siren connections using the default settings of each onboard output.
Note
If the backup battery is not
connected, or if the configu-
ration of panel terminal 7 is
programmed to anything
other than the default
(00410), then the combined
currents of terminal 7 (OUT
1/+12) and terminal 4 (+12V)
must not exceed 750 mA.
15-Watt, Dual Tone Siren (13-469)
Panel terminal 7 (OUT1/+12V) is a +12V programmable output. At the default configuration
setting (00410), this output can provide up to 1.25 A during an alarm (650 mA for UL Listed
systems) if the backup battery is connected.
The default configuration setting (00410) activates the output during any audible alarm, allow-
ing for a siren connection without changing the output configuration number.
Note
For UL Listed systems,
Siren Verify must be on.
Figure 12. Connecting 15-Watt, Dual-Tone Siren 13-469
91 0
Z O N E
1
Z C O
8
O U T 2 /
O C
+
C
O
. . . . . . . .
+--
C
O
N
O
N
O
+
C
O
. . . . . . . .
+- -
C
O
N
O
N
O
4
+ 1 2 V
Panel Terminal 8 (OUT2/OC)
Must be Set to Configuration
Number 01500 for Connected
Smoke Detectors to Reset
After Canceling a Fire Alarm
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
Model
449AT
Model
449AT
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
6 0 8 0 6 G 1 0 0 D D S F
3
G N D
7
O U T 1 /
+ 1 2 V
Black (Common)
Yellow (Steady)
Red
(Not Used)
Concord
Express
Panel
Terminals

Installing the System
13
Note
Some versions of this siren
may have two wires of each
color. Only one black wire
and one yellow wire are
needed for panel connec-
tions.
For UL Listed installations, you can connect only one 15-Watt, Dual-Tone Siren to panel termi-
nals 3 and 7 as shown in Figure 12. For all other installations, connect up to two sirens. This siren
does not require an end-of-line resistor.
Hardwire Siren (13-046)
Connect one or two sirens to the panel with supervision as shown in Figure 13. If Siren Verify is
turned off (see the section “Programming the Panel”), the 2k end-of-line resistor is not required.
Note
For UL Listed systems,
Siren Verify must be on and
the 2k end-of-line resistor
installed.
Figure 13. Connecting Hardwire Siren 13-046
Note
Piezo siren connections to
terminal 8 require a 2k
end-of-line resistor that can
be located at the panel since
it does not supervise the cir-
cuit.
Interior Piezo Siren (30-006)
Panel terminal 8 (OUT2/OC) is an open-collector (switched path-to-ground), programmable out-
put that can handle up to a 200 mA current.
The default setting (01710) activates the output for status and alarm tones, which allows for a
piezo siren connection without changing the output configuration number.
Connect the piezo siren to the panel terminals with a 2k end-of-line resistor as shown in
Figure 14.
Note
If using an external power
supply instead of panel ter-
minal 4, the supply voltage
must be limited to 9.5 VDC
maximum and the negative
side of the power supply
must be connected to panel
ground (terminal 3).
Figure 14. Connecting an Interior Piezo Siren
Connecting Siren Drivers, Self-Contained Sirens, and Bells
Power for a siren driver, self-contained siren, or bell can be connected to panel terminals 7
(OUT1/+12V) and 3 (GND).
Panel terminal 7 (OUT1/+12V) is a +12-volt programmable output. At the default configuration
setting (00410), this output can provide up to 1.25 A during an alarm (650 mA for
UL Listed systems) if the backup battery is connected.
Note
If the backup battery is not
connected, or if the configu-
ration of panel terminal 7 is
programmed to anything
other than the default
(00410), then the combined
currents of terminal 7 (OUT
1/+12) and terminal 4 (+12V)
must not exceed 750 mA.
The default configuration setting (00410) activates the output during any audible alarm.
The following siren drivers, self-contained sirens, and bells have been tested and found compati-
ble for use with the panel:
• Moose Models MPI-11 (use only 8-ohm speaker loads), MP-47, MP-47B
• Altronix Model ALSD2 (4- or 8-ohm speaker loads)
• ATW Models DT-24, DS508 (both self-contained)
• Wheelock MB-G6-12 Six-inch, 12V Bell
Refer to the manufacturer’s documentation for installation details.
37
G N D O U T 1 /
+ 1 2 V
Panel
Te r m in a l s
2k Ohm EOL Resistor 49-454
(Locate at Siren)
Red
Black
37
G N D O U T 1 /
+ 1 2 V
Red
Black
2k Ohm EOL Resistor 49-454
(Locate at Last Siren)
Panel
Terminals
48
+ 1 2 V O U T 2 /
O C
2k Ohm
Resistor
49-454
Black
Red
Panel
Terminals

Installing the System 14
Connecting Touchpads
• SuperBus 2000 2x16 LCD Alphanumeric Touchpad (60-746-01)
• SuperBus 2000 2x20 LCD Alphanumeric Touchpads (60-803, 60-809)
• SuperBus 2000 2x20 VFD Alphanumeric Touchpad (60-804, 60-810)
• SuperBus 2000 Fixed Display LCD Touchpad (60-820)
Alphanumeric touchpads can be used for installer programming, system operation, and user pro-
gramming. Fixed display touchpads can be used for system operation and user programming but
not for installer programming.
Note
Be sure to have an alphanu-
meric (programming) touch-
pad on hand for on-site
programming in installations
that do not include one as
part of the final system con-
figuration. This programming
touchpad can be connected
to the Programming Touch-
pad Header (see Figure 15)
using a Programming
Touchpad Cable (part no.
60-791).
Connect 2x16 and fixed display LCD touchpads to the panel power output and bus terminals as
shown in Figure 15.
The 2x20 LCD/VFD touchpads include a supervised hardwire input for connection to a hardwire
detection device (see Figure 15 for an example of a normally closed connection).
Connect 2x20 LCD/VFD touchpads to the panel power output and bus terminals as shown in
Figure 15.
Figure 15. Connecting 2x16 Alphanumeric, Fixed Display LCD Touchpads and 2x20
LCD/VFD Touchpads
Note
The panel cannot be used
on a digital or PBX phone
line. These systems are
designed only for digital type
devices that operate any-
where from 5 volts DC and
up. The panel uses an ana-
log modem and does not
have a digital converter,
adapter, or interface to oper-
ate with such systems.
Installing an RJ-31X Phone Jack (13-081)
Use the following guidelines when installing an RJ-31X phone jack for system control by phone
and central station monitoring.
• Locate the RJ-31X jack (CA-38A in Canada) no further than five feet from the panel.
• The panel must be connected to a standard analog (loop-start) phone line.
• For full line seizure, install an RJ-31X phone jack on the premises phone line so the panel is
ahead of all phones and other devices on the line. This allows the panel to take control of the
phone line when an alarm occurs even if the phone is in use or off-hook.
• If an analog line is not available, contact your customers’ telecommunications specialist and
tell him/her you need an analog line off the phone switch (PBX mainframe) or a 1FB (stan-
dard business line).
¾To connect a phone line to the panel using an
RJ-31X/CA-38A jack:
1. Run a 4-conductor cable from the TELCO protector block to the jack location (see A in
Figure 16).
2. Connect one end of the cable to the jack (see B in Figure 16).
34 5 6
G N D + 1 2 V B U S B
B U S A
3 4 5 6
+ 1 2 V AB
G N D B U S
SuperBus 2000
2x16 LCD Alphanumeric
or
SuperBus 2000
Fixed English
LCD Touchpad
+12V/Red
BUS A/Green
Bus B/White
GND/Black
Panel Terminals
Optional Switch
with Magnet
2k Ohm EOL
Resistor 49-454
(Locate at Last Device)

Installing the System
15
Figure 16. Installing an RJ-31X Phone Jack
3. At the TELCO protector block, remove the premises phone lines (lines from phone jacks on
premises) from the block and splice them to the black and white (or yellow) wires of the
4-conductor cable (see C in Figure 16).
Note
Connecting the panel to an
analog line off the phone
switch places the panel
ahead of the phone system
which prevents panel access
from phones on the pre-
mises. However, the panel
can still be accessed from
off-site phones.
4. Connect the green and red wires from the 4-conductor cable to the TIP (+) and RING (-) posts
on the block (see D in Figure 16).
5. Check the phones on the premises for dial tone and the ability to dial out and make phone
calls. If phones do not work correctly, check all wiring and make corrections where neces-
sary. Proceed to the “Troubleshooting” section of this manual if problems persist.
Connecting the Phone Line to the Panel with a DB-8 Cord
After installing the RJ-31X jack, you are ready to connect the phone line to the panel. A DB-8
cord (not included) uses a plug at one end for connecting to the RJ-31X module and flying leads
on the other end for panel terminal connections.
¾To connect the DB-8 cord to the panel terminals and RJ-31X jack:
1. Connect the green, brown, gray, and red flying leads from the DB-8 cord to panel terminals
18, 19, 20, and 21 (see Figure 17).
2. Insert the DB-8 cord plug into the RJ-31X (see Figure 17).
Figure 17. Connecting the DB8 Cord
( - )
( + )
A
B
C
D
Lines From
Phones on
Premises
Brn Gry
Grn
Black
Green
Red
White
(or Yellow)
Red
RJ-31X
Jack
Te l c o
Protector
Block
Tip Ring
Green
Green
Black
Red
White (or Yellow)
RJ-31X
Phone
Line
Wire
Run
Red
1 9 2 0 2 1
1 8
RedGryBrnGrn
House
Tel c o
Gry
Brn
Plug
DB-8 Cord
Grn Red
RJ-31X
Jack
Green
Brown
Gray
Red
This manual suits for next models
3
Table of contents
Other GE Security System manuals

GE
GE Concord Ultra User manual

GE
GE Concord 4 Instruction manual

GE
GE 45413 User manual

GE
GE 4 Series User manual

GE
GE Concord express Guide

GE
GE SIMON XT User manual

GE
GE Allegro 60-874-95R User manual

GE
GE Telligence Patient-Staff Communications... User manual

GE
GE AL-1291 Point ID User manual

GE
GE Choice-Alert 45136 User manual
Popular Security System manuals by other brands

DSC
DSC New Classic PC585 user manual

Risco
Risco LightSYS Installation and programming manual

Phonetics
Phonetics Sensaphone ISACC 5000 Operator's manual

Swann
Swann SWIFI-ISIREN quick start guide

TECHVIEW
TECHVIEW QV-3028 user manual

Ness Security Products
Ness Security Products SecurityGuardII owner's manual