•Out
•InP
Lo.S ... Hi.S
Type of probe, signal and scale of main input
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
0 J (Fe-CuNi) C 0 / 1000 0,0 / 999,9
1 J (Fe-CuNi) F 32 / 1832 32,0 / 999,9
2 K (NiCr-Ni) C 0 / 1300 0,0 / 999,9
3 K (NiCr-Ni) F 32 / 2372 32,0 / 999,9
4 R (Pt13Rh - Pt) C 0 / 1750 not available
5 R (Pt13Rh - Pt) F 32 / 3182 not available
6 S (Pt10Rh - Pt) C 0 / 1750 not available
7 S (Pt10Rh - Pt) F 32 / 3182 not available
8 T (Cu-CuNi) C -200 / 400 -199,9 / 400,0
9 T (Cu-CuNi) F -328 / 752 -199,9 / 752,0
10 B (Pt30Rh - Pt6Rh) C 44 / 1800 not available
11 B (Pt30Rh - Pt6Rh) F 111 / 3272 not available
12 E (NiCr-CuNi) C -100 / 750 -100,0 / 750,0
13 E (NiCr-CuNi) F -148 / 1382 -148,0 / 999,9
14 N (NiCrSi-NiSi) C 0 / 1300 0,0 / 999,9
15 N (NiCrSi-NiSi) F 32 / 2372 32,0 / 999,9
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
16 PT100 C -200 / 600 -199,9 / 600,0
17 PT100 F -328 / 1112 -199,9 / 999,9
SENSOR: RTD 3 wires (CAL = 2)
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
18 PTC C -55 / 120 -55.0 / 120.0
19 PTC F -67 / 248 -67.0 / 248.0
SENSOR: PTC (on request) [alternate to RTD 3 wires] (CAL = 3)
tYP Signal type Scale Max. scale range
20 0...60mV linear -1999 / 9999
21 12...60mV linear -1999 / 9999
SENSOR: VOLTAGE 60Mv (CAL = 4)
tYP Signal type Scale Max. scale range
22 0...20mA linear -1999 / 9999
23 4...20mA linear -1999 / 9999
SENSOR: CURRENT 20mA or TRANSMITTER (CAL = 5)
tYP Signal type Scale Max. scale range
24 0...10V linear -1999 / 9999
25 2...10V linear -1999 / 9999
SENSOR: VOLTAGE 10V or TRANSMITTER (CAL = 6)
InP Input settings
Digital filter
on main input
Digital filter on display of
process variable; acts as
hysteresis
Decimal point position for
main input scale
(*) not available for
TC, RTD, PTC scales
Minimum limit of main
input scale
Maximum limit of main
input scale
Main input offset
correction
Lower limit for local setpoint
and absolute alarms
SENSOR: TC (CAL = 1)
0.0 to 20.0 sec
0.0 to 9.9
scale points
dP.S Format
0 xxxx
1 xxx.x
2xx.xx (*)
3x
.xxx (*)
min…max scale of input
selected in t.P
min…max scale of input
selected in t.P
-999…999
scale points
Lo.S ... Hi.S
Upper limit for local setpoint
and absolute alarms
Type of control
[0...27]
CtrL Type of control
0 P heat
1 P cool
2 P heat / cool
3 PI heat
4 PI cool
5 PI heat / cool
6 PID heat
7 PID cool
8 PID heat / cool
9 ON-OFF heat
10 ON-OFF cool
11 ON-OFF heat / cool
0
0
0
1000
22
Default Custom
Configurat.
Out Output settings
to disable on power-up until first alarm
AL.x Direct Absolute Normal
(max.) Relative Symmetrical
Inverse to previous (window)
(min.)
0 direct absolute normal
1 inverse absolute normal
2 direct relativo normal
3 inverse relativo normal
4 direct absolute symmetrical
5 inverse absolute symmetrical
6 direct relativo symmetrical
7 inverse relativo symmetrical
0 ... 3
Number of alarms
Alarm
type 1
Alarm
type 2
Alarm
type 3
Default Custom
Configurat.
0
+16 disable parameters
CFG: rst, PrE, SoF, Lbt, Lbp, FAP,
HY.2, HY.3
InP: FLt, FLd, oFS, LoL, HIL
Out: ALn, A2t, A3t, rEL.
FLt, FLd, oFS stay at set value.
All other parameters are considered 0.
14