GFA TS 970 User manual

Installation instructions
Door control
TS 970
Automatic control
Version: 51171582
-en-
Version: f / 06.2016
0000000 0000 51171582 XXXXX

2
GfA ELEKTROMATEN GmbH & Co. KG
Wiesenstraße 81 • 40549 Düsseldorf
www.gfa-elektromaten.de
info@gfa-elektromaten.de

3
Contents
1General safety information ............................................................................................ 6
2Technical data .............................................................................................................. 7
3Mechanical installation .................................................................................................. 8
4Electrical installation ..................................................................................................... 9
Connection cable connection overview ........................................................................... 10
Limit switch configuration, screwable version up to year of construction in 1997 ............ 11
Limit switch configuration, single limit switches ............................................................... 11
Carrying out the electrical installation .............................................................................. 12
Mains supply ................................................................................................................... 13
Mains connection to control ............................................................................................ 13
Completing the electrical installation ............................................................................... 13
Overview of control ......................................................................................................... 14
5Starting up the control ................................................................................................. 15
DES: Rapid adjustment of final limit positions ................................................................. 15
NES: Rapid adjustment of final limit positions ................................................................. 16
6Electrical installation – control accessories .................................................................. 17
External supply X1 .......................................................................................................... 17
Emergency stop X3 ......................................................................................................... 17
Automatic closing, On/Off X4 .......................................................................................... 17
External Control device X5 .............................................................................................. 17
Photo cell X6 ................................................................................................................... 17
Light curtain X6 ............................................................................................................... 18
Radio receiver X7............................................................................................................ 18
Pull switch X7 .................................................................................................................. 18
Intermediate open X8 ...................................................................................................... 18
Traffic light X20 ............................................................................................................... 18
Magnetic brake X20 ........................................................................................................ 18
Connection of spiral cable ............................................................................................... 19
Completing the electrical installation ............................................................................... 20
7Control programming .................................................................................................. 21
8Table menu items ....................................................................................................... 22
Door operating modes ..................................................................................................... 22
Door positions ................................................................................................................. 23

4
Door functions ................................................................................................................. 24
Safety functions ............................................................................................................... 27
DI / FI settings ................................................................................................................. 28
Maintenance cycle counter .............................................................................................. 29
Readout of Data memory ................................................................................................ 30
Deleting of all settings / Readout GfA stick ..................................................................... 30
9Safety devices ............................................................................................................ 31
X2: Input, door safety switch function .............................................................................. 31
X2: Input, safety edge system ......................................................................................... 32
Installation of the spiral cable .......................................................................................... 33
EMERGENCY operation ................................................................................................. 36
X3: Input, emergency stop .............................................................................................. 36
10Functional description ................................................................................................. 37
X: 24 VDC voltage supply ............................................................................................... 37
X1: Mains supply of the control and supply of external devices ...................................... 37
X4: Input, automatic closing Off/On ................................................................................. 38
X5: Input, control device .................................................................................................. 38
X6: Input „Through / reflective photo cell“ resp. light curtain ........................................... 39
X7: Input pull switch/radio receiver .................................................................................. 42
X8: Input, intermediate stop On/Off ................................................................................. 43
Potential-free X20 relay contact ...................................................................................... 44
Force monitoring (DES only) ........................................................................................... 44
Travel time monitoring (NES only)................................................................................... 45
UBS system .................................................................................................................... 46
UBS connection .............................................................................................................. 46
Reversing duration adjustment ........................................................................................ 46
Maintenance cycle counter .............................................................................................. 47
Short-circuit/overload display .......................................................................................... 47
Standby function ............................................................................................................. 4 7
11Status display ............................................................................................................. 48
12Explanation of symbols ............................................................................................... 55
13Declaration of Incorporation/Declaration of Conformity ................................................ 57

5
Symbols
Warning - Risk of injury or danger to life!
Warning - Danger to life from electrical current!
Note - Important information!
▶ Prompt - Required action!
Illustrations show example products. Differences from the delivered product are possible.

6
1General safety information
Specified normal use
The door control is intended for a power-operated door with a drive unit (NES/DES GfA limit
switch system).
The safe operation is only guaranteed with specified normal use. The drive unit is to be
protected from rain, moisture and aggressive ambient conditions. No liability for damage
caused by other applications or non-observance of the information in the manual.
Modifications are only permitted with the agreement of the manufacturer. Otherwise the
Manufacturer’s Declaration shall be rendered null and void.
Safety information
Installation and commissioning are to be performed by skilled personnel only.
Only trained electrical craftsmen are permitted to work on electrical equipment. They must
assess the tasks assigned to them, recognise potential danger zones and be able to take
appropriate safety measures.
Installation work is only to be carried out with the supply off.
Observe the applicable regulations and standards.
Coverings and protective devices
Only operate with corresponding coverings and protective devices.
Ensure that gaskets are fitted correctly and that cable glands are correctly tightened.
Spare parts
Only use original spare parts.

7
2Technical data
Series TS 970
Dimensions W x H x D 155 x 386 x 90 mm
Installation Vertical, free of vibration
Operating frequency 50 / 60 Hz
Supply voltage (+/- 10%)
1 N~230 V, PE
3 N~230 / 400 V, PE
3~230 / 400 V, PE
Output power for drive unit, maximum 3 kW
Protection per phase, on-site 10-16 A
External mains supply:
(internal electronic protection)
24 V DC
0.18 A
External mains supply: X1/L, X1/N
(protection via F1 micro-fuse)
1 N~230 V
1.6 A time-lag
Control inputs 24 V DC
Type 10 mA
Relay contacts 1 potential-free
changeover contact
Load of the relay contact
ohmic/inductive
230 V AC, 1 A
24 V DC, 0,4 A
Control power consumption 11 W
Temperature range Operation: -10..+50
Storage: +0..+50 °C
Air humidity up to 93 %
non-condensing
Protection class of housing IP54
Compatible GfA limit switch NES (mechanical limit switch)
DES (digital limit switch)

8
3Mechanical installation
Control installation!
Indoor use only
Mounting only on even ground that is free of vibration
Only mount in the vertical position
Door must be in clear view from place of installation
Requirements
The permissible loads on walls, mountings, connection and transmission elements must not
be exceeded.
Mounting
The control is mounted via 4 elongated holes

9
4Electrical installation
Warning - Danger to life due to electrical current!
Disconnect the cables (mains OFF) and check that the supply is off
Observe the applicable regulations and standards
Ensure proper electrical connection
Use suitable tools
On-site backup fuse and disconnector unit!
Only use current sensitive earth leakage circuit breakers type B for FI-drive units
Connection to the indoor installation via an all-pole disconnector unit, with current
≥ 10 A as per EN 12453 (e.g. CEE plug connector, main switch)
Observe the installation instructions of the drive unit!

10
Connection cable connection overview
Ⓐ DES → Ⓑ X12 DES ⒸMOT → Ⓓ X13
Pin Core Pin Description: Pin Core Term. Description:
① 5/wh ① +24 V safety circuit ①3W Phase W
② 6/bn ② Channel B (RS485) ②2V Phase V
③ 7/gn ③ Ground ③1U Phase U
④ 8/ye ④ Channel A (RS485) ④4N Neutral conductor (N)
⑤ 9/gy ⑤ Safety circuit ⑤PE PE
⑥ 10/pk ⑥ 8 V DC supply voltage
Ⓐ NES → Ⓔ X12 NES
Pin Core Term. Description:
① 5/wh 11 Limit switch common +24 V, wire link to: 7, 9, 5, 14
② 6/bn 12 S5 Auxiliary limit switch
③ 7/gn 6 S3 Open limit switch
④ 8/ye 15 S6 Auxiliary limit switch
⑤ 9/gy 8 S4 CLOSE limit switch
⑥ 10/pk 4 Safety circuit

11
Limit switch configuration, screwable version up to year of construction in 1997
56710 93214(N)
S6 S5 S3 S1 S2 S4
S10 F1
G1
Y1
1
3
2
4
5
X12
W1
M1
F1 Thermal contact X12 Limit switch board
G1 Rectifier S1 Emergency OPEN limit switch
M1 Motor S2 Emergency CLOSE limit switch
S10 Emergency manual operation S3 OPEN limit switch
W1 Connection cable S4 CLOSE limit switch
Y1 Spring-loaded brake S5
A
uxiliary limit switch
S6
A
uxiliary limit switch
Limit switch configuration, single limit switches
5 671093214PE
M1 S10 F1S4S3 S5 S6
W1
A1
A
1 Terminal box S3 OPEN limit switch
F1 Thermal contact S4 CLOSE limit switch
M1 Motor S5
A
uxiliary limit switch
S10 Emergency manual operation S6
A
uxiliary limit switch
W1 Connection cable

12
Carrying out the electrical installation
▶ Remove covers. ▶ Open cable entry ① or ②.
▶ Insert and connect connection cable in the open cable entry ① (from below) or ② (from
above).
▶ Properly tighten cable glands.
Avoid damage to parts!
Open cable entry with suitable tool

13
Mains supply
3~, N, PE
230 / 400 V
50 / 60 Hz
3~, PE
230 / 400 V
50 / 60 Hz
1~, N, PE, sym.
230 V
50 / 60 Hz
1~, N, PE, asym.
230 V
50 / 60 Hz
L1L2L3 NPE
L1 L2L3 PE
NPE
SI 25.15 WS, SI 45.7 WS
NPE
SI 25.15 WS, SI 45.7 WS
3 x 400 V 1 x 230 V / 3 x 230 V
20.1
1.5
1.8
1.9
20.2
1.6
20.3
1.7
230V
400V
20.1
1.5
1.8
1.9
20.2
1.6
20.3
1.7
230V
400V
Mains connection to control
3
Completing the electrical installation
Install and tighten cable entries and/or cable glands.
For commissioning of the control, leave the covers open.

14
Overview of control
20.1
1.5
1.8
1.9
20.2
1.6
20.3
1.7
F1 = 1,6At
230V
400V
2.1
2.3
2.5
2.2
2.4
V1
MOT
DES/
NES S11
S12
S13
X20
X3
X2
X4 X5 XX6 X7 X8
F1
UBS S
X1
970
DES/
NES DES or NES limit switch socket X24 V mains supply, external devices
X1 Mains supply
F1 Micro-fuse 1.6 A time-lag X2 Safety edge and
door safety switch
MOT Motor socket
S Selector switch X3 Emergency STOP control device
S11 OPEN push-button X4
A
utomatic closing On/Off
S12 STOP push-button X5 Control device, external three push-button
S13 CLOSE push-button X6 Through / reflective photo cell
UBS Universal command sensor socket X7 Pull switch
V1 Display X8 Intermediate stop On/Off
X20 Potential-free relay contact

15
5Starting up the control
▶ Supply cables
Insert / switch on
DES: Rapid adjustment of final limit positions
1. Check output rotating direction
2. Move to OPEN final limit position 3. Save OPEN final limit position
4. Move to CLOSE final limit position 5. Save CLOSE final limit position
Note!
The rapid adjustment is complete, "Hold-to-run" door operating mode is active
Change of OPEN/CLOSE final limit positions via menu items "1.1" to "1.4"
Pre-limit switch Safety edge is set automatically
Changing the pre-limit position is possible via menu item "1.5"

16
Observe the installation instructions of the drive unit!
For adjusting the mechanical limit switch, see the drive unit installation
instructions
NES: Rapid adjustment of final limit positions
1. Check output rotating direction
2. Move to OPEN final limit position and adjust S3 OPEN limit switch
3. Move to CLOSE final limit position 5cm above the ground and adjust S5 pre-limit switch
4. Move to CLOSE final limit position and adjust S4 CLOSE limit switch

17
6Electrical installation – control accessories
Exter nal s uppl y X 1
Emer genc y stop X 3
Automatic closi ng, O n/Off X4
External supply
X1
Emergency stop
X3
A
utomatic closing, On/Off
X4
X1
A1
X3
A2
2
1
S15
X4
A3
12
4
3
S17
A
1 External device
A
2 Control device
A
3Control device
Emergency stop Key switch
Exter nal C ontr ol dev ice X 5
External Control device X5
X5
P
1
S17
2
A4
X5
3
2
1
S14
4
3
2
1
S16
2
1
S15
A6 X5
A
4 Key push-button
A
6Three push button
Photo cell X6
Photo cell X6
12345
24V
X6
A8
X6
12
24V
A9
12345
24V
A10
X6
12
24V
A11
12 3
24V
A12
PNP
A
8 Reflective
photo cell
Through-beam
photo cell
Through-beam
photo cell
A9 Transmitter A11 Transmitter
A10 Receiver A12 Receiver

18
Light cur tai n X 6
Light curtain X6
X20
20.1
20.2
20.3
24V
24V*
X6
12
24V
A25
12345
24V
A26
24V
24V*
PNP
X6
12
24V
A27
12 3
24V
A28
24V
24V*
X20 Function relay Light curtain Light curtain
Test light curtain A25 Transmitter A27 Transmitter
A26 Receiver A28 Receiver
Radi o r eceiv er X7
Pull switch X7
Interme diate o pen X8
Radio receiver X7 Pull switch X7 Intermediate open X8
1234
24V
X7
A13
A14
4
3
X7
S19
A15
12
4
3
S17
X8
Traffic li ght X20
Magnetic brake X20
Traffic light X20 Magnetic brake X20
20.1
20.2
20.3
H1
1.9
1.8
X20
20.1
20.2
20.3
1.9
1.8
Y1
G1
C1
H1 Traffic-light G1 Rectifier
Y1 Magnetic brake

19
Conn ecti on of spi ral c able
Connection of spiral cable
Electrical safety edge
234
2.1
2.3
2.5
2.2
2.4
X2
1
2
3
4
ST+
ST
SK1
SK2
A18
B1
8K2
R1
A18 Junction box
ST+ Mains supply
ST Input for door safety switch
SK1 Input electrical safety edge
SK2
B1 Electrical safety edge
R1 End of line resistor (8k2)
X2 Door control socket
Pneumatic safety edge
234
2.1
2.3
2.5
2.2
2.4
X2
1
2
3
4
ST+
ST
SK1
SK2
A18
DW
1K2
R2
A18 Junction box
ST+ Mains supply
ST Input for door safety switch
SK1 Input pneumatic safety edge
SK2
DW Pneumatic switch
R2 End of line resistor (1k2)
X2 Door control socket
Optical safety edge
234
2.1
2.3
2.5
2.2
2.4
X2
1
2
3
4
ST+
ST
SK/b
SK/g
SK/w
A19
br
gn
w
B3
B2
A19 Junction box
ST+ Mains supply
ST Input for door safety switch
SK/b Mains supply (brown)
SK/g Output (green)
SK/w Earth (white)
B2 Optical transmitter
B3 Optical receiver
X2 Door control socket
Door safety switch
ST
A18/A19
A20
2
1
S30/
S31
A18 Junction box
A
19
A20 Junction box switch
S30 Pass-door switch
(NC contact)
S31 Slack-rope switch
(NC contact)
Door safety switch, crash switch
ST
A18/A19
A21
2
1
S38
ST
A18/A19
A22
2
1
S39
A18 Junction box
A
19
A21 Junction box switch
S38 Crash switch
(NC contact)
A22 Junction box switch
S39 Crash switch
(NO contact)

20
Note!
Use of a safety edge only possible via menu item "0.1",
door operating mode “.3”, “.4” or “.6”
Completing the electrical installation
Connect and tighten up other electrical equipment and/or safety devices and cable entries
and cable glands, as required.
Table of contents
Other GFA Controllers manuals
Popular Controllers manuals by other brands

ACT
ACT ACTPRO PRODUCT RANGE Operating & installation instructions

Praxair
Praxair 3710 Operator's manual

Hyster
Hyster H2.00-3.20XM Safety Precautions Maintenance And Repair

Aprimatic
Aprimatic ApricolorVARIA 230V manual

Addonics Technologies
Addonics Technologies AD2U31PX2 user guide

National Instruments
National Instruments cRIO-9063 user manual