• ERROR MESSAGE
The error messages below will be displayed on SolarGo App or report by Email if the error really happen.
4.2 ERROR MESSAGE AND TROUBLESHOOTINGS
ERROR MASSAGE EXPLANATION REASON SOLUTIONS
Check use multi-meter if there is voltage (normally should be close to 0V) between earth & inverter frame.
If the is a voltage, it means the neutral & ground cable are not connected well on AC side. If it happened only
at early morning, dawn or on rainy days with higher air humidity, and recover soon, it should be normal.
Check use multi-meter if there is high voltage (normally should be lower than 10V) between N & PE cable on AC side.
If the voltage higher than 10V, it means the Neutral & ground cable are not connected well on AC side or restart inverter.
1. Check (use multi-meter) if AC side has voltage . Make sure grid power is available.
2. Make sure AC cables are connected tightly and right well.
3. If all is well, please try to turn off AC breaker and turn on again after 5 mins.
1. Make sure safety country of the inverter is set right.
2. Check (use multi-meter) if AC voltage (Between L & N) is within a normal range (Also on AC breaker side)
a. if AC voltage is high, then make sure AC cable complies with that required on user manual and AC cable is not too long
b. if voltage is low, make sure AC cable is connected well and the jacket of AC cable is not compressed into AC terminal
3. Make sure the grid voltage of your area is stable and within normal range.
1. Make sure safety country of the inverter is set right.
2. If safety country is right, then please check on inverter display if AC frequency (Fac) is within a normal range.
3. If FAC failure only appear a few times and resolved soon, it should be caused by occasional grid frequency unstability.
1. Try to decrease surrounding temperature.
2. Make sure the installation complies with the instruction on inverter user manual.
3. Try to close inverter for 15 mins, then start up again.
Check PV string VOC is lower than Max PV Input Voltage of the inverter
If VOC of PV string is high, please decrease panels to make sure VOC is with the max DC input voltage of the inverter.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Decrease Back-Up loads to make sure the total load power is lower than Back-Up nominal output power
(please refer to page 12).
Not available of public grid power (power
lost or on-grid connection fails)
Utility Loss
VAC Failure
FAC Failure
Over Temperature
PV Over Voltage
Ground leakage current is over-high
Relay Check Failure
DC Injection High
EEPROM R/W Failure
SPI Failure
DC Bus High
Back-Up Over Load
Grid voltage is not within permissible range
Grid Efficiency is not within permissible range
Temperature inside of the inverter is too high
DC total voltage of PV string is too high
Self checking of relay fails
Internal communication fails
BUS voltage is over-high
Back-up side is over loaded
Inverter detects that AC voltage is beyond the normal
range required by the safety country
Inverter does not detect the connection of grid
Inverter detects that Grid frequency is beyond the normal
range required by the safety country
Inverter working environment leads to a high
temperature condition
The total voltage (short-circuit voltage) of each PV string is
higher than the max DC input voltage of the inverter.
1.Use multi meter to check if the resistance between earth & inverter frame is about zero. If it’s not, Please make the
connection between earth & inverter frame well.
2. If the humidity is very high, there maybe Isolation Failure occur.
3. Check the resistance between PV1+/PV2+/BAT+/PV- to earth, if the resistance is lower than 33.3k, check the system
wiring connection.
4. Try to restart the inverter, check if the fault is still happens, if not, means it is just an occasional situation, or contact
GoodWe.
Isolation Failure Ground insulation impedance of PV string is
too low
Isolation failure could be caused by multi reasons like PV
panels are not grounded well, DC cable is broken, PV
panels are aged or surrounding humility is comparatively
heavy,etc.
Neutral & ground cable are not connected well on AC
side or just occasional failure
Inverter detects a higher DC component in AC output
Caused by a strong external magnetic field etc.
Caused by a strong external magnetic field etc.
Total Back-Up load power is higher than the nominal
backup output power
Ground 1 Failure
Ground I failure could be caused by multi reasons like
neutral cable on AC side is not connected well or
surrounding humidityis comparative heavy, etc.
/
/
/
NOTE: All the errors about battery happen only on Lithium battery with BMS communication.