INTRODUCTION
The high accuracy single point outside air temperature sensor utilizes a
precision sensor. All probes are constructed to provide excellent heat transfer,
fast response and are potted to resist moisture penetration. A sun and wind
shield is integrated into a weatherproof compact polycarbonate enclosure with
a hinged and gasketed cover for ease of installation.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning
the temperature sensor. Failure to follow these instructions may result in
product damage. Do not use in an explosive or hazardous environment, with
combustible or ammable gases, as a safety or emergency stop device or in
any other application where failure of the product could result in personal
injury. Do not exceed the device ratings.
MOUNTING
Select a suitable mounting spot on an exterior wall where the sensor is best protected from
direct exposure to sunlight, wind, etc. preferably on a north facing wall. Do not mount the
sensor near opening windows, supply/exhaust air louvres or other known air disturbances.
Avoid areas where the sensor is exposed to vibrations or rapid temperature changes.
The sensor provides a connection hole for 22.7 mm (0.895") conduit on the back side of
enclosure. Run a length of conduit through exterior wall and seal. Use 18-22 AWG shielded
wiring for all connections and do not locate the device wires in the same conduit with wiring
used to supply inductive loads such as motors. Make all connections in accordance with
national and local codes.
The sensor installs directly on an exterior wall using the four integrated mounting holes
provided on the enclosure. Select the best mounting technique based on the exterior wall
material. The two mounting holes are suitable for a #10 size screw (not supplied). The sensor
hub must be pointing down. See Figure 1.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch
on the right side of the enclosure. At the same time pulling on the cover, as illustrated in Figure
2.
A 1/2" NPT connection hole is provided in the back of the enclosure. Connect the EMT
connector with a locknut. See Figure 3. It is recommended that weatherproof conduit be used.
An optional cable gland tting is available. See Figure 4.
Make wiring connections as per the “wiring”illustrations on Page 2.
Swing door closed until securely latched. For added security, two screws are provided that
may be installed in the integrated screw tabs. See Figure 5.
Conduit style connector Cable gland style connector
Figure 1
Figure 2
Figure 3 Figure 4 Figure 5
IN-GE-HATSOBXXX-01 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
High Accuracy Outside Air
Temperature Sensor with
Sun and Windshield
HATSOB Series - Installation Instructions
Page 2
WIRING
• Use 18 - 24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive
loads such as motors. Make all connections in accordance with national and local codes.
• Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the wiring diagrams below. All
connections should be made using either butt-splices or soldering. The use of wire nuts is not recommended.
• Thermistors are a 2 wire hook up and are not polarity sensitive. See Figure 6.
• RTD’s are a 3 wire hook up. Figure 7.
SPECIFICATIONS
Sensor Type: .................................. Various thermistors or RTD
Sensor Accuracy:..........................RTD Class A: ±0.15°C (±0.27°F) @ 0°C (32°F)
RTD 1/3 DIN: ±0.1°C (±0.18°F) @ 0°C (32°F)
RTD 1/10 DIN: ±0.03°C (±0.054°F) @ 0°C (32°F)
NTC Thermistor Type 39: ±0.05°C (±0.09°F),
0 to 70°C (32 to 158°F)
NTC Thermistor Type 55: ±0.03°C (±0.054°F),
0 to 70°C (32 to 158°F)
NTC Thermistor Type 40/46: ±0.1°C (±0.18°F),
0 to 70°C (32 to 158°F)
Probe Sensing Range:................-40 to 50°C (-40 to 122°F)
Probe Material:..............................Machined Aluminum
Ambient Operating Range:.....-40 to 50°C (-40 to 122°F)
Wire Material:.................................RTD: FT-4, 22 AWG, 3 Wire
Thermistor: PVC insulated, parallel bonded,
22 AWG, 2 Wire
Enclosure:.........................................A: Polycarbonate, UL94-V0, IP65 (NEMA4X)
C: Same as A, with terminal block
E: Same as C, with cable gland tting
Termination: ...................................A: Pigtail, 2 or 3 wire
C & E: Terminal block, 2 or 3 wire
Country of Origin:........................Canada
PRINTED IN CANADA
TYPICAL WIRE RESISTANCE VALUES
When using low resistance sensors, long wire runs can add signicant error to the
readings. Use the following chart to determine errors due to wire resistance or consider
using a 1000 ohm sensor or a transmitter for better accuracy. Locate the type of wire
being used. Multiply the total length of the wire (distance from the controller to the
sensor and back) by the number found in the chart below for total resistance.
Figure 6 2 Wire Termination for Thermistor
Figure 7 3 Wire Termination for RTD
Wiring for Enclosures C & E
*For illustrative purposes only, terminal block mounted on inside of cover
*
*
NOTE: The sensor accuracies listed in the specications section apply to the sensing
element only prior to product assembly and may not be reected in the complete
assembly.
Due to the measurement uncertainty, it is possible, that the true resistance value of the
single delivered sensor at 0°C can be out of the dened tolerance class. Proling each
assembly to take into consideration lead wire and the attachment method should be
completed.
GAUGE WIRE TYPE 18 AWG 22 AWG 24 AWG
STRANDED (OHMS/FOOT) 5.85 mΩ 14.75 mΩ 23.29 mΩ
SOLID (OHMS/FOOT) 6.4 mΩ 15.85 mΩ 25.72 mΩ
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI) or
Customer supplied
transmitter
ToController
Analog Input (AI) or
Customer supplied
transmitter
Green
Red
Black
DIMENSIONS
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI) or
Customer supplied
transmitter
ToController
Analog Input (AI) or
Customer supplied
transmitter
Green
Black
Red
132 mm
5.19"
82.5 mm
3.25"
69.8 mm
2.75"
52.0 mm
2.05"
92.0 mm
3.62"
38.0 mm
1.5"
76.2 mm
3.00" 0.5" NPT
IN-GE-HATSOBXXX-01 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com

Other Greystone Energy Systems Temperature Controllers manuals

Greystone Energy Systems TSOB Series User manual

Greystone Energy Systems

Greystone Energy Systems TSOB Series User manual

Greystone Energy Systems HATSSO Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSSO Series User manual

Greystone Energy Systems HATSRC Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSRC Series User manual

Greystone Energy Systems TE200AD Series User manual

Greystone Energy Systems

Greystone Energy Systems TE200AD Series User manual

Greystone Energy Systems TSAP Series User manual

Greystone Energy Systems

Greystone Energy Systems TSAP Series User manual

Greystone Energy Systems HATSAP Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSAP Series User manual

Greystone Energy Systems TSRC Series User manual

Greystone Energy Systems

Greystone Energy Systems TSRC Series User manual

Greystone Energy Systems NTDAMOD User manual

Greystone Energy Systems

Greystone Energy Systems NTDAMOD User manual

Greystone Energy Systems TSSO Series User manual

Greystone Energy Systems

Greystone Energy Systems TSSO Series User manual

Popular Temperature Controllers manuals by other brands

Omega DP26-TC user manual

Omega

Omega DP26-TC user manual

Omron E5C2 datasheet

Omron

Omron E5C2 datasheet

Danfoss ECL Comfort 300 quick guide

Danfoss

Danfoss ECL Comfort 300 quick guide

Dimplex SOLCU Installation and operating instructions

Dimplex

Dimplex SOLCU Installation and operating instructions

Elesta DOMOTESTA RDO353A series user manual

Elesta

Elesta DOMOTESTA RDO353A series user manual

RKC INSTRUMENT RB900 installaiton instructions

RKC INSTRUMENT

RKC INSTRUMENT RB900 installaiton instructions

Omron E5AN-H user manual

Omron

Omron E5AN-H user manual

DEVI devireg 530 instruction manual

DEVI

DEVI devireg 530 instruction manual

Smart temp SMT-200 rev3 owner's manual

Smart temp

Smart temp SMT-200 rev3 owner's manual

BriskHeat SDX instruction manual

BriskHeat

BriskHeat SDX instruction manual

Honeywell C7189A installation instructions

Honeywell

Honeywell C7189A installation instructions

Azbil Neosensor Series Specifications & instructions

Azbil

Azbil Neosensor Series Specifications & instructions

Kamstrup MULTICAL 403 Installation and user guide

Kamstrup

Kamstrup MULTICAL 403 Installation and user guide

Autonics TK Series user manual

Autonics

Autonics TK Series user manual

Amada MR-130B Operation manual

Amada

Amada MR-130B Operation manual

MEIER-BRAKENBERG D-Line + MBWeich 4 Assembly instructions and operator's manual

MEIER-BRAKENBERG

MEIER-BRAKENBERG D-Line + MBWeich 4 Assembly instructions and operator's manual

emz smart Sol plus Assembly and operating instructions

emz

emz smart Sol plus Assembly and operating instructions

KNX 70662 Installation and adjustment

KNX

KNX 70662 Installation and adjustment

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.