manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Greystone Energy Systems
  6. •
  7. Temperature Controllers
  8. •
  9. Greystone Energy Systems TSAP Series User manual

Greystone Energy Systems TSAP Series User manual

Page 1
INTRODUCTION
The single point, all purpose duct/immersion temperature sensor utilizes a
precision sensor that is encapsulated in 6 mm (0.236”) OD, 304 series stainless
steel probe and is available in various lengths. All probes provide excellent heat
transfer, fast response and resistance to moisture penetration. A compact ABS
enclosure with a hinged and gasketed cover is provided for ease of installation.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning
the temperature sensor. Failure to follow these instructions may result in
product damage. Do not use in an explosive or hazardous environment, with
combustible or ammable gases, as a safety or emergency stop device or in
any other application where failure of the product could result in personal
injury. Do not exceed the device ratings.
MOUNTING (DUCT)
The duct temperature sensor installs directly into any air duct with several lengths
available for a wide range of duct widths/diameters. Please select a suitable installation
area in the middle of the duct wall. To achieve the best reading, do not place in an area
where air stratication may be present. Mount the sensor at least 1.5 m (5 ‘) in either
direction from elbows, dampers, lters or other duct restrictions. Avoid areas where the
sensor is exposed to vibrations or rapid temperature changes.
Once a suitable spot is selected, drill a 9.5 - 12 mm (3/8”- 1/2“) hole for the probe.
Slide the probe in the drilled hole until the enclosure is ush against the duct. The
airow direction is not important. Secure the enclosure to the duct with (2) #10 x 25
mm (1”) self tapping screws (not provided). Tighten screws until the enclosure is tight
against the duct and ensure there is no movement of the enclosure as shown in Figure 1.
A foam gasket on the back of the enclosure provides a tight seal against any air leaks.
MOUNTING (IMMERSION)
The temperature sensor must be installed into a thermowell. Failure to use a
thermowell will create leaks and could damage the sensor. Install the thermowell as
recommended in Figure 2. For complete thermowell installation instructions, please
refer to installation instructions provided with the thermowell.
It is recommended to use heat conductive compound. Prior to installing the sensor
inject a liberal amount into the thermowell and/or on the tip of the sensor. Slide the
probe into the thermowell until it makes contact with the bottom of the thermowell.
Tighten the set screw to secure the probe in the thermowell. See Figure 3.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on
the latch on the right side of the enclosure. At the same time pulling on the cover, as
illustrated in Figure 4.
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure.
Screw the EMT connector or cable gland connector in until tight. See Figure 5. It is
recommended that weatherproof conduit or cable gland ttings be used. The E style
enclosure includes 1/2" NPT to M16 thread adapter and cable gland tting.
Make wiring connections as per the “Wiring” illustrations on Page 2.
Swing door closed until securely latched. For added security, 2 screws are provided that
may be installed in the integrated screw tabs. See Figure 6.
Recommended thermowell placement
EMT Connector
Thread adapter and
cable gland tting
Set Screw
Figure 3
Figure 4 Figure 5 Figure 6
Figure 2
Figure 1
IN-GE-TSAPXXX-01 02/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
All Purpose Temperature Sensor
TSAP Series - Installation Instructions
Page 2
WIRING
• Use 18-24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive
loads such as motors. Make all connections in accordance with national and local codes.
• Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the wiring diagrams below.
• All thermistors and most RTD’s are a two wire hook up and are not polarity sensitive. See Figure 7.
• For RTD’s that are 3 wire connection see Figure 8.
SPECIFICATIONS:
Sensor Type: .................................. Various thermistors or RTD
Sensor Accuracy:......................... Thermistors: ±0.2˚C (±0.36˚F) @ 25˚C (77˚F)
Platinum RTD’s: ±0.3˚C (±0.54˚F) @ 0˚C (32˚F)
Nickel RTD’s: ±0.4˚C (±0.72˚F) @ 0˚C (32˚F)
Probe Sensing Range: .............. -40 to 100°C (-40 to 212°F)
Ambient Operating Range:.... -40 to 50°C (-40 to 122°F)
Wire Material:................................ PVC insulated, parallel bonded, 22 AWG
Probe Material:............................. 304 Series stainless steel
Probe Diameter:........................... 6 mm (0.236")
Standard lengths:........................ 50, 100, 150, 200, 300, and 400 mm
(2", 4", 6", 8", 12", and 18")
Enclosure:........................................ ABS - UL94-V0, IP65 (NEMA4X)
C - Terminal block
E - includes thread adapter (1/2" NPT to M16),
cable gland tting, and terminal block
Termination: .................................. A - pigtail, 2 or 3 wire
C & E - Terminal block, 2 or 3 wire
Country of Origin:....................... Canada
PRINTED IN CANADA
TYPICAL WIRE RESISTANCE VALUES
When using low resistance sensors, long wire runs can add
signicant error to the readings. Use the following chart to
determine errors due to wire resistance or consider using a
1000 ohm sensor or a transmitter for better accuracy. Locate
the type of wire being used. Multiply the total length of the
wire (distance from the controller to the sensor and back)
by the number found in the chart below for total resistance.
Figure 7 2 Wire Termination for Thermistor or RTD
Figure 8 3 Wire Termination for Thermistor or RTD
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI) or
Customer supplied
transmitter
ToController
Analog Input (AI) or
Customer supplied
transmitter
Green
Black
Red
EMT Connector
EMT Connector
Wiring for Enclosures C & E
*For illustrative purposes only, terminal block mounted on inside of cover
*
*
GAUGE WIRE TYPE 18 AWG 22 AWG 24 AWG
STRANDED (OHMS/FOOT) 5.85 mΩ 14.75 mΩ 23.29 mΩ
SOLID (OHMS/FOOT) 6.4 mΩ 15.85 mΩ 25.72 mΩ
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI)
(No Polarity)
ToController
Analog Input (AI) or
Customer supplied
transmitter
ToController
Analog Input (AI) or
Customer supplied
transmitter
Green
Red
Black
DIMENSIONS
EMT Connector
EMT Connector
82.5 mm
3.25"
69.8 mm
2.75"
Various Probe Lengths
See Specications
6 mm
(0.236")
76.2 mm
3.00"
0.5" NPT
Foam Gasket
304 Series S/S Probe
52.0 mm
2.05"
IN-GE-TSAPXXX-01 02/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com

Other Greystone Energy Systems Temperature Controllers manuals

Greystone Energy Systems NTDAMOD User manual

Greystone Energy Systems

Greystone Energy Systems NTDAMOD User manual

Greystone Energy Systems HATSOB Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSOB Series User manual

Greystone Energy Systems TSOB Series User manual

Greystone Energy Systems

Greystone Energy Systems TSOB Series User manual

Greystone Energy Systems HATSSO Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSSO Series User manual

Greystone Energy Systems TSRC Series User manual

Greystone Energy Systems

Greystone Energy Systems TSRC Series User manual

Greystone Energy Systems TSSO Series User manual

Greystone Energy Systems

Greystone Energy Systems TSSO Series User manual

Greystone Energy Systems HATSRC Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSRC Series User manual

Greystone Energy Systems HATSAP Series User manual

Greystone Energy Systems

Greystone Energy Systems HATSAP Series User manual

Greystone Energy Systems TE200AD Series User manual

Greystone Energy Systems

Greystone Energy Systems TE200AD Series User manual

Popular Temperature Controllers manuals by other brands

paratronic LHC installation instructions

paratronic

paratronic LHC installation instructions

Decagon Devices 5TE Operator's manual

Decagon Devices

Decagon Devices 5TE Operator's manual

Sensor Partners I-Tec Mini Series Operator's guide

Sensor Partners

Sensor Partners I-Tec Mini Series Operator's guide

Hanyoung TH500 manual

Hanyoung

Hanyoung TH500 manual

REGLOPLAS 90M operating instructions

REGLOPLAS

REGLOPLAS 90M operating instructions

Solo SL4896-RRE quick start guide

Solo

Solo SL4896-RRE quick start guide

alre FTRFB-080 Series manual

alre

alre FTRFB-080 Series manual

Auber TH102 instruction manual

Auber

Auber TH102 instruction manual

TREND T/PI installation instructions

TREND

TREND T/PI installation instructions

Fancom IVM-TOUCH manual

Fancom

Fancom IVM-TOUCH manual

PCE Instruments PCE-RE21R user manual

PCE Instruments

PCE Instruments PCE-RE21R user manual

Vaillant VRT 230 Operating and manual

Vaillant

Vaillant VRT 230 Operating and manual

MISSION CONTROLS Supersilent User instructions

MISSION CONTROLS

MISSION CONTROLS Supersilent User instructions

Johnson Controls A419 Series Product/Technical Bulletin

Johnson Controls

Johnson Controls A419 Series Product/Technical Bulletin

Ekinex 71 Series Applications manual

Ekinex

Ekinex 71 Series Applications manual

Full Gauge Controls TC-920Ri manual

Full Gauge Controls

Full Gauge Controls TC-920Ri manual

Golander GL102B user guide

Golander

Golander GL102B user guide

Kiwi Lora Alliance Member LAS-603V1 user manual

Kiwi

Kiwi Lora Alliance Member LAS-603V1 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.