Groen DH User manual

OPERATOR MANUAL &
SERVICE MANUAL
IMPORTANT INFORMATION, KEEP FOR OPERATOR
This manual provides information for:
MODELS DH-CE Mark
& DHT-CE Mark International
STEAM JACKETED
KETTLES
· Self-Contained
· Stainless Steel
· Gas Heated
· Floor Mounted
· Tilting
PART NUMBER 128417, REV. H (08/11)
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE.
READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS
AND WARNINGS CONTAINED IN THIS MANUAL (THE SERVICE
MANUAL AND OPERATOR MANUAL SECTIONS).
NOTIFY CARRIER OF DAMAGE AT ONCE
It is the responsibility of the consignee to inspect the container upon receipt
of same and to determine the possibility of any damage, including concealed
damage. Unified Brands suggests that if you are suspicious of damage to make
a notation on the delivery receipt. It will be the responsibility of the consignee to
file a claim with the carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
DH
DHT
Information contained in this document is known to be current and accurate at the time
of printing/creation. Unified Brands recommends referencing our product line websites,
unifiedbrands.net, for the most updated product information and specifications.
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
unifiedbrands.net

2 OM/SM-DH CE
OM-SM-DH-CE
2
OM/SM-DH-CE
2
IMPORTANT — READ FIRST — IMPORTANT
IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS AND THE OPERATOR AND SERVICE
MANUALS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THE APPLIANCE.
FAILURE TO COMPLY WITH SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED
FOR A SERVICE CALL.
THESE APPLIANCES HAVE BEEN CE MARKED ON THE BASIS OF COMPLIANCE WITH THE GAS
APPLIANCE DIRECTIVE, EMC AND LOW VOLTAGE DIRECTIVE FOR THE COUNTRIES, GAS TYPES
AND PRESSURES AS STATED ON THE DATA PLATE.
THESE APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON IN CONFORMITY WITH
INSTALLATION AND SERVICING INSTRUCTIONS AND NATIONAL REGULATIONS IN FORCE AT
THE TIME. PARTICULAR ATTENTION MUST BE PAID TO THE FOLLOWING:
I. E. E. REGULATIONS FOR ELECTRICAL INSTALLATIONS
ELECTRICITY AT WORK REGULATIONS
GAS SAFETY (INSTALLATION AND USE) REGULATIONS
HEALTH AND SAFETY AT WORK ACT
LOCAL AND NATIONAL BUILDING REGULATIONS
FIRE PRECAUTIONS ACT
DETAILED RECOMMENDATIONS ARE CONTAINED IN INSTITUTE OF GAS ENGINEERS
PUBLISHED DOCUMENTS: IGE/UP/1, IGE/UP/2, BS6173 AND BE5440. FURTHERMORE, IF A NEED
ARISES TO CONVERT THE APPLIANCE FOR USE WITH ANOTHER GAS, A COMPETENT PERSON
MUST BE CONSULTED. THOSE PARTS WHICH HAVE BEEN PROTECTED BY THE
MANUFACTURER MUST NOT BE ADJUSTED BY THE USER.
USERS SHOULD BE CONVERSANT WITH THE APPROPRIATE PROVISIONS OF THE FIRE
PRECAUTIONS ACT AND THE REQUIREMENTS OF THE GAS SAFETY REGULATIONS. IN
PARTICULAR THEY SHOULD BE AWARE OF THE NEED FOR REGULAR SERVICING BY A
COMPETENT PERSON TO ENSURE THE CONTINUED SAFE AND EFFICIENT PERFORMANCE OF
THE APPLIANCE.
WARNING: TO PREVENT SHOCKS, ALL APPLIANCES GAS OR ELECTRIC, MUST BE
EARTHED.
UPON COMPLETION OF THE INSTALLATION, THE OWNERS MANUAL SHOULD BE HANDED TO
THE USERS AND THE INSTALLER SHOULD INSTRUCT THE RESPONSIBLE PERSON(S) IN THE
CORRECT OPERATION AND MAINTENANCE OF THE APPLIANCE.
THIS EQUIPMENT IS ONLY FOR PROFESSIONAL USE, AND SHALL BE OPERATED BY QUALIFIED
PERSONS. IT IS THE RESPONSIBILITY OF THE SUPERVISOR OR EQUIVALENT TO ENSURE THAT
USERS WEAR SUITABLE PROTECTIVE CLOTHING AND TO DRAW ATTENTION TO THE FACT
THAT SOME PARTS BY NECESSITY WILL BECOME VERY HOT, AND WILL CAUSE BURNS IF
TOUCHED ACCIDENTALLY.
WARNING: BEFORE REMOVING ANY PARTITION OR PANEL, ALWAYS TURN OFF THE
ELECTRIC POWER AND ALLOW THE FAN TO STOP ROTATING. BEFORE
WORKING ON ANY ELECTRICAL COMPONENT, DISCONNECT THE POWER
SOURCE FROM THE UNIT.
NOTE: IT IS IMPORTANT THAT THE END-USER ROUTINELY EXAMINE THE FLUE OUTLET
ON A REGULAR BASIS. DEBRIS COVERING THE FLUE OUTLET CAN CAUSE A
POTENTIALLY HAZARDOUS CONDITION. REMOVE ANY FOREIGN MATERIAL
BEFORE USING THIS PIECE OF EQUIPMENT.
WARNINGS AND CAUTIONS PROVIDED IN THIS OPERATOR AND SERVICE MANUAL MUST BE
COMPLIED WITH.

OM/SM-DH CE 3
OM-SM-DH-CE
3
OM/SM-DH-CE
Contents
Regulations and Safety Precautions............................................ 4
1 Installation............................................................... 5
1.1 Model Numbers, Net Weights & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Siting ................................................................... 5
1.3 Clearances ............................................................... 5
1.4 Ventilation ............................................................... 5
1.5 Electrical Supply .......................................................... 5
1.6 Gas Supply .............................................................. 6
1.7 Total Gas Rate - Natural and Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.8 Injector Diameters-Natural and Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.9 Gas Pressure Adjustment ................................................... 6
1.10 Burner Adjustment ......................................................... 6
2 Assembly and Conditioning ................................................... 7
2.1 Assembly ................................................................ 7
2.2 Gas Supply .............................................................. 7
2.3 Electrical Supply .......................................................... 7
2.4 JacketWater Level/Jacket Pressure ........................................... 7
2.5 Pre-Commissioning Check .................................................. 7
2.6 Instruction to Installer
.........................................................
8
3 Servicing and Conversion ..................................................... 9
3.1 Conversion .............................................................. 12
3.2 Jacket Vacuum .......................................................... 12
3.3 Jacket Filling ............................................................ 12
3.4 Water Treatment Procedure ................................................ 13
3.5 Removal of Control Panels ................................................. 13
3.6 Removal of Spark Ignition Module ............................................ 14
3.7 Removal of Low Water Level Control, Transformer and Fuse . . . . . . . . . . . . . . . . . . . . . . . 14
3.8 Removal of Tilt Switch ..................................................... 14
3.9 Removal of Gas Control Valve .............................................. 14
3.10 ON/OFF Switch and Reset Button ............................................ 15
3.11 Removal of Neons ........................................................ 15
3.12 Removal of Thermostat .................................................... 15
3.13 Removal of Pressure Switch ................................................ 16
3.14 LowWater Level Sensor ................................................... 16
3.15 Removal of the Burners ................................................... 16
3.16 Spark Electrode/Flame Sensing Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.17 Removal of Pressure Gauge ................................................ 17
3.18 Removal of Sight Glass .................................................... 17
3.19 Steam Safety Valve
.............................................................
18
3.20 Filling Valve.............................................................. 18
4 Troubleshooting ............................................................. 19
5 User Instructions ............................................................ 19
5.1 Equipment Description ..................................................... 21
5.2 Lighting and Operation ..................................................... 23
5.3 Cleaning and Maintenance .................................................. 25
Parts List ...................................................................... 27
Wiring Diagram ................................................................. 31
Service Log .................................................................... 32
Warranty ...................................................................... 33

4 OM/SM-DH CE
OM-SM-DH-CE
4
OM/SM-DH-CE
4
Regulations and Safety Precautions
These Appliances have been CE marked on the basis of compliance with the Gas Appliance Directive,
EMC and Low Voltage Directive for the Countries, Gas Types and Pressures as stated on the Data Plate.
These appliances MUST BE installed by a competent person in conformity with the INSTALLATION AND
SERVICING INSTRUCTIONS and National Regulations in force at the time.
Particular attention MUST be paid to the following:
I.E.E. Regulations for Electrical Installations
Electricity at Work Regulations
Gas Safety (Installation & Use) Regulations
Health and Safety at Work Act
Fire Precautions Act
Local and National Building Regulations
Furthermore, if a need arises to convert the Appliance for use with another gas, a competent person must
be consulted. Those parts which have been protected by the manufacturer MUST NOT be adjusted by the
User.
Users should be conversant with the appropriate provisions of the Fire Precautions Act and the
requirements of the Gas Safety Regulations. In particular the need for regular servicing by a competent
person to ensure the continued safe and efficient performance of the Appliance.
WARNING
TO PREVENT SHOCKS, ALL APPLIANCES WHETHER GAS OR ELECTRIC, MUST BE EARTHED.
Upon completion of the installation, the Owners Manual should be handed to the users and the installer
should instruct the responsible person(s) on the correct operation and maintenance of the Appliance. This
equipment is ONLY FOR PROFESSIONAL USE, and shall be operated by QUALIFIED persons. It is the
responsibility of the Supervisor or equivalent to ensure that users wear SUITABLE PROTECTIVE
CLOTHING and to draw attention to the fact that, some parts will, by necessity, become VERY HOT and
will cause burns if touched accidentally.
IMPORTANT - READ FIRST - IMPORTANT The Groen Steam Jacketed Kettle you have just purchased
has been handcrafted from the finest materials, meticulously inspected, and carefully tested to ensure that
you receive the best possible product. With reasonable care and periodic maintenance, it will provide
years of faithful service. It is recommended that you establish a timetable for periodic maintenance as
outlined in this manual. Space is provided in the Service Log at the back of this manual.

OM/SM-DH CE 5
OM-SM-DH-CE
5
OM/SM-DH-CE
5
Section 1
Installation
UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE
MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER.
1.1 Model Numbers, Net Weights and
Dimensions
MODEL•DH-20 DH-40 DH-60
WIDTH
mm (inch) 890 (34.9) 1190 (46.8) 1190 (46.8)
DEPTH
mm (inch) 790 (31.0) 930 (36.5) 990 (38.9)
HEIGHT
mm (inch) 1040 (40.9) 1150 (45.2) 1240 (48.7)
WEIGHT
Kg 245 295 400
WEIGHT
lbs 535 645 880
1.2 Siting
The appliance should be installed on a level floor
in a well lit and draught free position.
The installation of the appliance must be
executed in accordance with local and/or
national regulations as listed in this manual.
1.3 Clearances
Minimum clearances of 150 mm (5.9 in) from the
sides of the appliance and 250 mm (9.8 in) from
the rear of the appliance are required if the
appliance is installed next to combustible
surfaces. A vertical clearance of 750 mm (29.6
in) minimum should be allowed between the top
rim of kettle and any overlying surface.
1.4 Ventilation
The unit must be installed in an adequately
ventilated room with a provision for adequate air
supply to the unit. The area directly around the
appliance must be cleared of all combustible
material. For multiple installations, the
requirements for individual appliances should be
added together. Installation should be made in
accordance with local and / or national
regulations applying at the time. A competent
installer must be employed.
WARNING
THE UNIT MUST BE INSTALLED BY
PERSONNEL QUALIFIED TO WORK WITH
ELECTRICITY AND GAS. IMPROPER
INSTALLATION CAN CAUSE INJURY TO
PERSONNEL AND/OR DAMAGE TO
EQUIPMENT. THE UNIT MUST BE
INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE CODES.
CAUTION
THE APPLIANCE FLUE DISCHARGES
VERTICALLY FROM THE TOP OF THE UNIT
AT THE REAR. IT MUST NOT BE DIRECTLY
CONNECTED TO ANY FLUE, MECHANICAL
EXTRACTION SYSTEM, OR DUCTING
LEADING OUTSIDE THE BUILDING. THE
APPLIANCE IS BEST DISCHARGED UNDER
AN OPEN CANOPY WHICH CONNECTS
WITH A VENTILATING SYSTEM.
Recommendations for ventilation for catering
appliances are given in BS 5440:2 and are
shown in the table below.
Equipment
(Unit Type)
Ventilation Rate Required
m³ /min ft³ /min
Range 17 600
Pastry Oven 17 600
Fryer 26 900
Grill 17 600
Steak Grill 26 900
Boiling Pan 17 600
Steamer 17 600
Sterilizing Sink 14 500
Bains Marie 11 400
Tea/Coffee
Machine 8.5-14 300-500
1.5 Electrical Supply
This unit is designed for connection to fixed
wiring. A suitably rated isolating switch with
contact separation of at least 3 mm (0.12 in) on

6 OM/SM-DH CE
OM-SM-DH-CE
OM/SM-DH-CE
both poles must be fitted to the installation and
the wiring executed in accordance with the
regulations listed in this manual.
Cable entry is at the lower rear on the right side
of the appliance. Access is gained by removing
relevant panels as described in Paragraphs
3.5.1 and 3.5.2.
Provide 230 VAC, 50 Hz, 1 Phase, 1 AMP or 40
Watts service. The electrical schematic is in the
service compartment and this manual.
WARNING
THIS APPLIANCE MUST BE EARTHED.
1.6 Gas Supply
Incoming service must be of sufficient size to
supply full rate without excessive pressure drop.
A gas meter is connected to the service pipe by
the Gas Supplier. Any existing meter should be
checked by the Gas Supplier to ensure that it
has capacity to pass the required rate of gas for
the kettle in addition to other installed gas
equipment.
The appliance governor is incorporated in the
gas control valve which is in the control cabinet.
The control valve governor is suitable for both
natural and propane gases without conversion.
Installation pipe work should be fitted in
accordance with IEGE/UP/2. The pipe work
should not be smaller than the gas inlet
connection on the kettle, i.e. Rp � (� '' B.S.P.)
An isolating cock must be located near the
appliance to allow shut down during emergency
or servicing. Test for gas soundness and purged
as specified in IGE/UP/1.
Water Supply-Not applicable.
1.7 Total Gas Rate - Natural (G20)
and Propane (G31) Gas
G20 Models Kw BTU/hr
DH-20 18.98 64,800
DH/1-40 26.35 90,000
DH-60 3 108,000
G31 Models Kw BTU/hr
DH-20 19.40 66,240
DH/1-40 24.25 82,800
DH-60 110,400
Gas and Electrical Connections are made at the rear of the unit.
1.63
32.33
Equipotential
Terminal
Electric Power
Supply Inlet
Gas Inlet
Water Level
Gauge &
Sight Glass

OM/SM-DH CE 7
OM-SM-DH-CE
7
1.8 Injector Diameters-Natural and Propane
Gas (See Note, Paragraph 1.10 at right)
Model DH-20 DH/1-40 DH-60
Number of
Injectors 15 20 25
Natural
Gas G20 1.10 mm 1.15 mm 1. mm
Propane
Gas G31 0.65 mm 0.65 mm 0. mm
1.9 Gas Pressure Adjustment
A pressure test point is fitted on the burner
manifold and on the gas control valve.
DH-20 DH/1-40 DH-60
Natural
Gas-G20
mBar 8.75 8.75 8.75
WCI* 3.5 3.5 3.5
Propane
Gas-G31
mBar 25 25 25
WCI* 10.0 10.0 10.0
*WCI = Water Column Inches
NOTE: With reference to gas rate, pressure
adjustments and conversions, this appliance
is CE-approved for use with the following
gases:
a) G20 natural gas may be supplied to the
appliance in Austria, Denmark,
Finland, Greece, Iceland, Ireland,
Italy, Luxembourg, Norway, Portugal,
Spain, Sweden, Switzerland and the
United Kingdom.
b) G31 propane gas may be supplied to the
appliance in Germany, Ireland,
the Netherlands, Portugal, Spain,
Switzerland, and the United Kingdom.
Use of the appliance with non-approved
gases in a listed country, or use in other
countries, will void CE certification.
1.10 Burner Adjustment
The burners are fixed aeration type and have no
provision for adjustment of air inlet.
10
65

8 OM/SM-DH CE
OM-SM-DH-CE
8
Before operation, check the water level and
jacket pressure.
Section 2
Assembly and Commissioning
2.1 Assembly
d) Unpack the appliance
b) Place on a firm, level floor. Adjust and fix the
feet.
CAUTION
SHIPPING STRAPS ARE UNDER TENSION
AND CAN SNAP BACK WHEN CUT. TAKE
CARE TO AVOID PERSONAL INJURY OR
DAMAGE FROM STAPLES LEFT IN THE
WALLS OF THE CARTON.
2.2 Gas Supply
Connect the unit to the gas supply and test for
gas soundness. For gas supply down stream of
the gas valve, leak detection spray or soap
solution may be used with the burners lit.
CAUTION
ENSURE THAT THE KETTLE CONTAINS
LIQUID WHEN THE BURNERS ARE ALIGHT.
2.3 Electrical Supply
Before commissioning the appliance, ensure that
the electrical installation has been carried out to
the relevant regulations (Paragraph 1.5).
WARNING
THIS APPLIANCE MUST BE EARTHED.
2.4 Jacket Water Level/Jacket Pressure
a) Ensure the water level in the jacket is
correct, by confirming that it is between the
sight glass marks. If it is low, follow
instructions in Paragraph 3.3.
b) Check the pressure gauge. If it does not
show 20 or more inches of vacuum (that is,
a reading of 20 to 30 below zero) see
"Jacket Vacuum" (Paragraph 3.2).
2.5 Pre-Commissioning Check
a) Prior to operation, clean out kettle pan
thoroughly using hot water and detergent.
Rinse pan thoroughly.
b) Remove all literature and packing materials
from the interior and exterior of the unit.
c) Ensure the open end or the elbow at the
outlet of the safety valve is directed down. If
not, turn the elbow to the correct position.
See detailed Instructions on Page 11 for
Safety Valve installation and operation.
2.5.1 Lighting Sequence
From Initial Start Up:
a) Put a small amount of water in kettle pan.
b) Ensure gas and electricity mains are “on.”
c) Switch the toggle switch to the "on" position.
d) Turn thermostat dial to desired setting.
e) Verify that spark igniter lights the burners.
Water Level
Gauge &
Sight Glass
Pressure
Gauge
Gas Valve
Access Cover

OM/SM-DH CE 9
OM-SM-DH-CE
9
OM/SM-DH-CE
f) If the unit does not light, it will lock-out after 50-70
seconds. Turn it off and wait five minutes before
attempting to switch the unit on again.
g) To switch unit off, switch toggle (On/Off)
switch to the "Off" position.
h) Turn gas and electricity mains off.
2.5.2 Setting The Gas Pressure
a) It is necessary to check the gas pressure
during commissioning. A pressure gauge must
be connected to the pressure test point on the
gas manifold. See above figure for test points.
b) Turn the main gas and electricity supply on.
c) Light the burners (Paragraph 2.5.1).
d) Remove cover plate on the round skirt at
bottom of kettle (see photo on page 8).
e) Remove governor cap screw from control
valve. See figure for position on valve.
f) Governor adjustment is suitable for both
natural and propane gas.
g) To increase pressure turn the screw inside
the governor turret clockwise; anti-clockwise
to reduce pressure. Check the burner
pressure again after 15 minutes operation
and adjust if necessary.
h) Disconnect the pressure gauge from the test
point. Re-seal the pressure test point and
test for gas soundness.
i) Replace governor cap screw and replace
cover plate.
2.5.3 Checking Performance of Controls
a) Light the unit. Check that controls quickly
and smoothly produce a healthy spark from
the electrode to the earthing post.
b) Turn thermostat off and then on. Check that
burners go out and reignite smoothly and
quickly when switched back on. Repeat
several times.
c) If the unit fails to respond as described, it
should be serviced by an authorized Groen
service agent.
2.6 Instruction to Installer
Important: After installing and
commissioning the appliance, the user's
instructions should be handed to the user or
purchaser. Ensure that the instructions for
lighting, turning off, correct use and cleaning
are properly understood. The location of the
main gas isolating valve should be
emphasized and the emergency shut down
procedure should be demonstrated.
On/Off Toggle
Switch
Low Water
Indicator
Thermostat
Gas Pressure
Test Nipple
Capscrew for
Governor Pressure
Adjustment
Gas Inlet

10 OM/SM-DH CE
OM-SM-DH-CE
10
OM/SM-DH-CE
Section 3
Servicing and Conversion
IMPORTANT
BEFORE ATTEMPTING ANY SERVICING, ENSURE THAT THE ISOLATING COCK IS TURNED OFF
AND CANNOT BE INADVERTENTLY TURNED ON.
ENSURE ALSO THAT THE ELECTRICITY SUPPLY IS DISCONNECTED.
AFTER ANY MAINTENANCE TASK, CHECK THE APPLIANCE TO ENSURE THAT IT PERFORMS
CORRECTLY AND CARRY OUT ANY NECESSARY ADJUSTMENTS AS DETAILED IN SECTION 1.
ALWAYS CHECK FOR GAS SOUNDNESS AFTER CARRYING OUT ANY SERVICING OR EXCHANGE
OF GAS CARRYING COMPONENTS.
NOTE:1. When replacing wiring connections refer to the wiring diagram contained on the unit and within
this manual.
2. When any threaded gas connection is disturbed for any reason, the threads must be resealed with
appropriate gas leak prevention sealant that is suitable for the type of gas. Unified Brands/Groen
recommends gas sealant compound such as Locktite® 243 or Unified Brands part number 122002.
After Servicing
a) Test for gas soundness as specified in
IGE/UP1 as appropriate after any gas
connection has been disturbed.
c) Check for correct operation, as appropriate
b) If leaks are found, disconnect the mating parts,
clean the threads and apply recommended
sealant as specified in Note 2 above.
(see commissioning of appliance).
WARNING - Do not leave any wood splinter
or bristles from brush in the burner or injector.
Fire could result.
Regular Servicing Procedures
The following must be serviced at regular intervals.
Burners
The burner should be cleaned periodically to
maintain maximum performance. Burners are
best cleaned with a wire brush and any blocked
parts are best cleaned with a metal broach,
taking care not to damage the burner head.
The injector orifice should be cleaned with a
wooden splinter. Metal reamers may distort or
increase the orifice size and should be avoided.
WARNING - Do not leave any wood splinter
or bristles from brush in the burner or injector.
Fire could result.
Gears
The gear housing has fitting for proper
lubrication of moving parts. The gears do not run
in oil, periodic lubrication with grease is
necessary. Frequency of lubrication will depend
on operating conditions, but it should be
performed at least once every 6 months. It is
liberal amount of grease on the gear to cover the
arc that is in contact with the worm gear.
Safety Valve (Steam)
At least twice a month the safety valve requires
checking to make sure it works correctly. When
the gauge pressure is about five PSI, lift the
valve lever enough to vent steam, then quickly
let it snap back into place.
WARNING
AVOID ANY EXPOSURE TO THE STEAM
BLOWING OUT OF THE SAFETY VALVE.
This procedure should be explained to the user,
since it is to be carried out at least twice a
month. Safety procedures and requirements
should also be explained to the user when
carrying out the procedure.
Safety Valve Operating Instructions
If adding water to the boiling pan jacket,
DO NOT ALLOW
water to flow through safety valve as sediment or
debris may be deposited on seating surface.
To achieve topmost performance and maximum
service life, it is necessary to maintain a proper
pressure margin between set pressure of the
safety valve and equipment operating pressure.
recommended that a #2 grade LGI lithium
grease be used. Add grease through the Zerk
fittings on the gear housing until grease flows out
of bearings around the trunnion shaft. Place a

OM/SM-DH CE 11
OM-SM-DH-CE
11
OM/SM-DH-CE
Test the operation of the safety valve on a
regular basis.
The minimum required pressure margin for this
type of valve is 10% of the safety relief valve set
pressure, but not less than five PSI. UNDER NO
CIRCUMSTANCES SHOULD THIS MARGIN
BE LESS THAN 5 PSI. Failure to maintain this
operating margin may result in water leakage
past the seat and accumulation of deposits on
the seating surface. Excessive deposits may
prevent the valve from operating properly, and a
dangerous pressure build-up and equipment
rupture may result.
Maintenance and Testing
CAUTION
BEFORE TESTING, MAKE CERTAIN
DISCHARGE PIPE IS PROPERLY
CONNECTED TO VALVE OUTLET AND
ARRANGED TO CONTAIN AND SAFELY
DISPOSE OF BOILER DISCHARGE (SEE
“INSTALLATION INSTRUCTIONS”).
Under normal operating conditions a “try lever
test” must be performed every two months.
Under severe service conditions, or if corrosion
and/or deposits are noticed within the valve
body, testing must be performed more often. A
“try lever test” must also be performed at the end
of any non-service period.
Test at or near maximum operating pressure by
holding the test lever fully open for at least 5
seconds to flush the valve seat free of sediment
and debris. Then release lever and permit the
valve to snap shut.
If lift lever does not activate, or there is no
evidence of discharge, discontinue use of
equipment immediately and contact a licensed
contractor or qualified service personnel.
Neither Conbraco Industries, Inc. nor its agents
assume any liability for valves improperly
installed or maintained.
This quality Conbraco safety relief valve, along
with proper installation, use, and maintenance,
will provide many years of reliable service and
protection against excessive pressure build-up of
water/steam. Use of this valve for any other
purpose or media places all responsibility upon
the user. Before installing valve or operating
equipment to which it is installed, read
instructions carefully. Always wear proper safety
equipment.
INSTALLATION OF SAFETY VALVE (STEAM)
a) Installation must be performed by qualified
service personnel only.
b) The BTU/hr or lb/hr rating of this valve must
equal or exceed that of the equipment to
which it is attached.
c) DO NOT use this valve on a coal or wood
boiler having an uncontrolled heat input.
d) Ensure that all connections, including the
valve inlet, are clean and free from any
foreign material.
e) Use pipe compound sparingly, or tape, on
external threads only.
f) DO NOT USE A PIPE WRENCH! Use
proper type and size wrench on wrench pads
only.
g) This valve must be mounted in a vertical,
upright position directly to a clean, tapped
opening in the top of the boiler or equipment.
Under no circumstances should there be a
flow restriction or valve of any type between
the safety relief valve and the pressure
vessel
h) WARNING! During operation, this valve
may discharge large amounts of steam
and/or hot water. To reduce the potential for
bodily injury and property damage, a
discharge line MUST be installed that:

12 OM/SM-DH CE
OM-SM-DH-CE
OM/SM-DH-CE
1. is connected from the valve outlet with
no intervening valve and directed
downward to a safe point of discharge.
2. allows complete drainage of both the
valve and the discharge line
3. is independently supported and securely
anchored so as to avoid applied stress
on the valve.
4. is as short and straight as possible.
5. terminates freely to atmosphere where
any discharge will be clearly visible and
is at no risk of freezing.
6. terminates with a plain end that is not
threaded.
7. is constructed of a material suitable for
exposure to temperatures of 375º F or
greater.
8. is, over its entire length, of a size equal
to or greater than the valve outlet.
Use only schedule 40 pipe for discharge.
(Do not use schedule 80, extra strong pipe
or connections). DO NOT CAP, PLUG, OR
OTHERWISE OBSTRUCT DISCHARGE
PIPE OUTLET!
I) See appropriate ASME Boiler and Pressure
Vessel Code for additional installation
instructions.
3.1 Conversion
See Paragraphs 1.8 and 1.9 for important
information for gas conversion. Verify the
type of gas to be used.
To change the type of gas used (e.g. G20 to
G31 or inverse) change the following:
a) Burner injectors. See instruction 3.15 on page 16.
b) Gas valve spring. Install per instructions supplied
with the spring package as shown below.
3. Insert G31 orifice marked BBR14.
4. Reconnect pilot gas line.
d) Data plate with correct rate and gas manifold
pressure information.
ALL CONVERSIONS MUST BE FOR
APPROVED GAS IN THE COUNTRIES LISTED
IN PARAGRAPH 1.9.
c) Pilot orifice. The pilot orifice for correct gas must
be used. See photo below.
1. Remove the gas line and the connector
to the pilot.
2. Remove G20 orifice from the pilot.
It is marked BCR18.
IMPORTANT
THIS APPLIANCE WAS FITTED AT THE
FACTORY WITH GAS INJECTORS FOR TYPE
OF GAS SPECIFIED ON DATA PLATE. PRIOR
TO INSTALLING EQUIPMENT, OR WHEN
CONVERTING TO ANOTHER GAS, VERIFY THAT
THE INJECTOR SIZE MARKING ON THE GAS
INJECTOR MATCHES THE INFORMATION ON
THE DATA PLATE FOR THE TYPE OF GAS
BEING USED.
3.2 Jacket Vacuum
When the kettle is cold, a positive reading or a
reading around zero on the pressure vacuum
gauge indicates an excess of air in the jacket. Air
in the jacket slows down kettle heating.
To remove air:
a) Light the unit. (Paragraph 2.5.1 )
b) When the pressure/vacuum gauge reaches
a positive pressure reading of 5 PSI, release
air and steam by lifting the lever on the
safety valve for about one second. Repeat
this a few times. Then let the lever snap
back to the closed position.
See detailed Instructions on Page 11 pertaining
to Safety Valve installation and operation.
WARNING
AVOID EXPOSURE TO
STEAM BLOWING
OUT OF THE SAFETY
VALVE.
3.3 Jacket Filling
(TURN OFF GAS AND ELECTRICITY MAINS)
The jacket has been charged at the factory with
the proper amount of treated, distilled water. You
may need to restore jacket water to its proper
level, either because it was lost as steam during
venting or by draining.
Gas Inlet Tube
Connector
Pilot
G20 Orice BCR18
G31 Orice BCR14

OM/SM-DH CE 13
OM-SM-DH-CE
13
OM/SM-DH-CE
13
The procedure for adding water follows:
a) If you are replacing water lost as steam, use
distilled water. If you are replacing treated
water that ran out of the jacket, prepare
more treated water as directed below.
b) Allow the kettle to cool completely. Using the
proper size spanner, remove the pipe plug
from above the globe valve.
c) Open the globe valve and pour distilled or
treated water into the pipe plug orifice. Hold
the safety valve open while you pour to let air
escape from the jacket.
d) Air introduced to the jacket during the filling
operation must be removed to obtain
efficient heating. See Paragraph 3.2.
See detailed Instructions on Page 11 pertaining
to Safety Valve installation and operation.
3.4 Water Treatment Procedure
WARNING
READ AND FOLLOW WATER TREATMENT
COMPOUND LABEL PRECAUTIONS TO
AVOID INJURY.
a) Fill the mixing container with the measured
amount of water required. (See Table). Use
distilled water only.
Model Kettle Capacity Jacket Capacity
DH-20 75.7 Litres 6.6 Litres
DH-40 151.4 Litres 7.1 Litres
DH-60 227.1 Litres 11.3 Litres
b) Hang a strip of pH test paper on the rim of
the container, with about 1" of the strip below
the surface of the water.
c) Measure the water treatment compound you
will be using. (One way to do this is to add
the compound to the water from a small
measuring cup).
d) Stir the water continuously, while you slowly
add water treatment compound, until the
water reaches a pH between 10.5 and 11.5.
Judge the pH by frequently comparing the
color of the test strip with the color chart
provided in the pH test kit.
e) Record the exact amounts of water and
treatment compound used. These amounts
may be used again, if the same sources of
water and compound are employed.
However, it is advisable to check the pH
every time water is prepared. For optimum
performance, use correctly treated, distilled
water.
3.5 Control Panels
3.5.1 Control Cabinet Lid
a) Remove the four screws around the edge of
the lid securing it to the control cabinet.
b) Remove the lid.
c) Replace in reverse order.
3.5.2 Control Cabinet Side Panel
a) Remove lid (Para 3.5.1).
b) Remove the four screws securing the side
panel to the control cabinet.
c) Remove panel.
d) Replace in reverse order.
3.5.3 Supporting Column Access Panels
a) Remove the four screws securing the two
panels to the supporting column.
b) Remove both panels.
c) Replace in reverse order.

14 OM/SM-DH CE
14
OM/SM-DH-CE
3.6 Removal of Spark Ignition Module (Turn
the gas and electricity mains off)
a) Remove supporting column (trunnion arm)
access panels (Paragraph 3.5.3).
b) Remove screws on ignition module box and
remove cover carefully so as not to damage
the water gasket.
c) Disconnect electrical leads from spark
ignition module.
d) Remove retaining screws securing module.
e) Withdraw spark ignition module from control
cabinet.
f) Replace in reverse order.
g) NOTE : When replacing spark ignition module,
verify that the high voltage cable to the pilot is
not damaged or frayed. If damaged, replace the
cable and route it the same as original placement.
3.7 Removal of Low Water Level Control,
Transformer or Fuse Replacement (Turn
the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1).
b) Remove control cabinet side panel as in
Para 3.5.2.
c) Remove low water level control transformer
or the fuse.
d)
e)
Replace in reverse order.
Ensure the low water level control relay is
correctly oriented when re-positioned.
3.8 Removal of Tilt Switch (Turn the gas and
electricity mains off)
a) Remove control cabinet lid (Para 3.5.1).
b) Remove control cabinet side panel (Para 3.5.2).
c) Disconnect electrical leads from tilt switch.
d) Remove screws securing the tilt switch.
e) Withdraw tilt switch from control cabinet.
f) Replace in reverse order.
g) Verify that the tilt switch shuts off the burner
gas supply when the kettle is tilted.
Adjustment range is 5° to 10°.
3.9 Removal of Gas Control Valve (Turn the
gas and electricity mains off)
a) Remove panel from kettle base by removing the
three (3) retaining screws (see photo below).
b) Undo the gas line fittings on inlet and outlet
side of gas valve.
c) Disconnect the electrical leads from the gas valve.
d) Remove the fasteners holding the gas bracket to
the kettle body.
e) Carefully tilt the gas valve assembly to access
the pilot gas connection.
f) Undo the pilot gas tube connection.
g) Remove the gas valve from kettle.
h) Replace in reverse order.
Spark Ignition
Control Module
Module Box
Trunnion Arm
Tilt Switch
Low Water Level Control
Terminal Block
Fuse
Transformer
Water Splash Guard
Kettle Bottom Cover
Pilot Gas Line
Gas Line
Valve Support Bracket
Gas Valve
Flexible Gas Connector

OM/SM-DH CE 15
OM-SM-DH-CE
15
OM/SM-DH-CE
3.10 Removal of ON/OFF Switch
(Turn the gas and electricity mains off)
a) Remove control cabinet lid. (Para 3.5.1).
b) Remove control cabinet side panel (Para
3.5.2).
c) Disconnect electrical leads from the On/Off
switch.
d) Undo and remove retaining collar which
secures the On/Off switch to the outer
surface of the control cabinet.
e) Withdraw the On/Off switch.
f) Replace in reverse order.
3.11 Removal of Neons (Turn the gas and
electricity mains off)
a) Remove control cabinet lid (Para 3.5.1)
b) Remove control cabinet side panel (Para
3.5.2)
c) Disconnect the electrical leads to the neon.
d) Undo and remove the retaining collar which
secures the neon to the control cabinet.
e) Withdraw the neon from the control cabinet.
f) Replace in reverse order.
3.12 Removal of Thermostat (Turn the gas
and electricity mains off)
a) Remove supporting column access panels
(Para 3.5.3).
b) Remove panel from kettle base by undoing
the retaining screws.
c) Drain kettle by tilting kettle slightly and
undoing phial boss connection. Allow kettle
to drain into a suitably sized container.
WARNING
ENSURE THAT THE OTHER ELECTRICAL
LEADS AND CONNECTIONS SITUATED IN
THE KETTLE BASE DO NOT GET WET.
REMOVE THEM IF NECESSARY.
Important: Drained water from kettle jacket
should be retained. Jacket was charged at
the factory with the correct amount of treated
water. This water should be used to refill the
kettle. However, if water is lost during
drainage see Paragraph 3.3, Jacket Filling.
d) Remove thermostat control knob and
disconnect electrical leads.
e) Undo and remove thermostat retaining
screws securing the thermostat to the
supporting column.
f) Feed thermostat phial through supporting
column and withdraw the thermostat.
g) Replace in reverse order.
h) Ensure an adequate sealant is used to seal
the replacement thermostat phial boss.
i) Once the thermostat is in place, the jacket
should be refilled. (Para 3.3)
Always refer to wiring diagram when re-
connecting leads. (See Page 31)
On/Off Toggle
Switch
Low Water
Indicator
Thermostat

16 OM/SM-DH CE
16
3.13 Removal of Pressure Switch (Turn
the gas and electricity mains off)
a) Remove panel from base of kettle by
undoing the retaining screws.
b) Disconnect the electrical leads from the
pressure switch.
c) Drain kettle by tilting kettle slightly and
undoing the compression fitting at the
pressure switch. Allow kettle to drain into a
suitably sized container.
d) Remove and withdraw the pressure switch
from the kettle base by undoing the
compression fitting.
e) Replace in reverse order.
f) Once the pressure switch is in place, the
kettle jacket should be refilled. (Para 3.3)
Always refer to wiring diagram when
reconnecting electrical leads. (See Page 30)
3.14 Removal of Low Water Level Sensor
(Turn gas and electricity mains off)
a) Remove panel from base of kettle by
undoing the retaining screws.
b) Disconnect the electrical leads from the
water sensor.
c) Drain the kettle by tilting it slightly and
undoing the low water level sensor. Allow the
kettle to drain into a suitably sized container.
d) Remove the low water sensor from the kettle
base.
e) Replace in reverse order.
f) Ensure a suitable sealant is used to seal the
low water level sensor Boss.
g) When the low water level sensor is in place,
the jacket should be filled. (Para 3.3)
3.15 Removal of Burners (Turn the gas
and electricity mains off)
b) Undo compression fitting at gas pipe to
a) Remove water splash guards around the
burner.
burner manifold and to the pilot.
c) Disconnect electrical leads to the pilot.
d) Remove the four retaining nuts securing the
burner and igniter assembly to the
combustion chamber. Carefully support the
weight of the burner manifold and lower the
assembly to a safe position.
e) The burners are now accessible and can be
removed as required. Ensure adequate
sealant is used to seal the burners.
f) Replace in reverse order.
Always check for gas soundness when any
part of the gas circuit has been disturbed.
3.16 Removal Of Pilot (Turn the gas and
electricity mains off)
a) Remove water splash guards around the burner.
b) Disconnect the high voltage spark cable from
the pilot.
c) Disconnect the ground connection cable from
the pilot mounting screw.
d) Remove the second pilot mounting screw.
e) Remove pilot assembly and install new pilot.
f) Replace in reverse order.
Water Level
Sensor
Pressure Switch

OM/SM-DH CE 17
OM-SM-DH-CE
17
OM/SM-DH-CE
Recommended spacings are shown in this drawing.
DH-20 shown
g) Ensure that there is an adequate spark at
the sparking electrode and that the burners
light smoothly and without delay.
h) As the burners ignite, ensure that the
sparking sequence stops and that the
burners remain lit.
3.17 Removal of Pressure Gauge (Turn the
gas and electricity mains off)
a) Using the correctly sized spanner remove
the pressure gauge from top of the sight
glass.
b) Replace with new pressure gauge ensuring
that an adequate sealing compound is used.
c) Once the pressure gauge has been
replaced, the kettle jacket will require
venting. (Para 3.2)
3.18 Removal of Sight Glass (Turn the gas
and electricity mains off)
a) Remove sight glass protection bars.
b) Undo top and bottom compression fittings.
c) Allow the water in the sight glass to drain.
d) Remove the sight glass.
e) Replace in reverse order.
15 mm
13 mm
High Voltage
Spark Cable Pilot
Ground
Connector
Burner
Gas Line

18 OM/SM-DH CE
18
OM/SM-DH-CE
f) Once the sight glass has been replaced, the
lost jacket water requires replacement. (Para
3.3)
3.19 Removal of Steam Safety Valve (Turn
the gas and electricity mains off)
a) Remove the elbow from the safety valve.
b) Remove the steam safety valve from kettle
jacket pipework.
c) Replace in reverse order.
d) Ensure an adequate sealing compound is
used to seal the safety valve.
e) Once the steam safety valve has been replaced
the jacket will need to be vented. (Para 3.2)
See detailed Instructions on Page 11 pertaining to
Steam Safety Valve installation and operation.
3.20 Removal of Filling Valve (Turn the
gas and electricity mains off)
a) Remove filling valve from kettle jacket pipe-
work.
b) Replace in reverse order.
c) Ensure adequate sealing compound is used
to seal the valve.
d) Once the fill valve has been replaced the
jacket will need to be vented. (Para 3.2)

OM/SM-DH CE 19
OM-SM-DH-CE
19
4. Troubleshooting
Your Groen kettle is designed to operate smoothly and efficiently if properly maintained. However, the
following are checks to make in the event of a problem. Wiring diagrams are inside the service panel.
USE OF ANY REPLACEMENT PARTS OTHER THAN THOSE SUPPLIED BY GROEN OR THEIR
AUTHORIZED DISTRIBUTORS CAN CAUSE INJURY TO THE OPERATOR AND DAMAGE TO THE
EQUIPMENT AND WILL VOID ALL WARRANTIES.
SYMPTOM WHO WHAT TO CHECK
Kettle is hard to tilt. User a. Gears for foreign materials, lubrication and alignment.
Burners will not light. User a. Is main gas valve open (handle in line with gas pipe)?
b. Gas supply to your building.
c. That kettle body is not tilted.
d. Is electric power turned on at the circuit breaker or
fuse box, and is power being supplied to the
appliance
e. Thermostat operation.
Kettle continues heating after it
reaches the desired temperature.
User a. Thermostat dial setting.
Auth
Service
Rep Only
b. Thermostat calibration.
c. Thermostat operation. Thermostat should click when
the dial is rotated above and below a setting.
Kettle stops heating before it reaches
the desired temperature.
User a. Thermostat dial setting.
Auth
Service
Rep Only
b. Thermostat calibration.
c. Thermostat. Thermostat should click when the dial is
rotated above and below a setting.
Kettle heats slowly User a. Air in jacket - pressure/vacuum gauge (20 to 30
below zero when the kettle is cold?)
Safety valve pops. User a. Air in jacket - pressure/vacuum gauge (20 to 30
below zero when the kettle is cold?)
b. Whether kettle was being heated while empty.
Auth
Service
Rep Only
c. If high pressure limit switch is set too high.
d. Thermostat. Thermostat should click when the dial is
rotated above and below a setting.
e.
Safety valve. If valve pops below 40 PSIG (2.75 bars), replace.
System does not produce a spark Auth
Service
Rep Only
a. Thermostat. Close the contacts if they are open
b. AC voltage between terminals “L1" and “GR.” If it is
not 230 Volt, check the high limit switch, which
should be closed.
c. That the high tension cable is firmly attached and in
good condition. If cracked or brittle, replace the pilot.
e. Electrode ceramic for crack or break.
f. Electronic spark ignition module. Replace if needed.
Spark is present but the pilot will not
light.
Auth
Service
Rep Only
a. That the gas valve is opening.
b. That pressure meets the control manufacturer’s
specifications.
c. For gas at the pilot. If it is not flowing:
(1) Check pilot gas line for kinks or obstructions.
(2) Clean orifice, if necessary.
(3) Replace the pilot valve.
Pilot lights, but main burner will not
come on and spark does not stay
on.
Auth
Service
Rep Only
a. That the gas pressure meets the control
manufacturer’s specifications.
b. Replace spark ignition module.
c. Check pilot ground wire connections and grounding.

20 OM/SM-DH CE
OM-SM-DH-CE
20
OM/SM-DH-CE
SYMPTOM WHO WHAT TO CHECK
Pilot lights, but main burner will not
come on, the spark stays on.
Auth
Service
Rep Only
a. Spark igniter cable, to make certain that there are
secure attachments to the ignition module and pilot.
a. Pilot ceramic for cracks.
b. That high voltage cable is not grounded out. If it is,
replace connections.
c. Ground wire for continuity and condition of
insulation.
d. (1) Check the gas pressure.
(2) Clean the pilot orifice.
(3) Tighten mechanical and electrical connections.
Pilot lights, but main burner will not
come on, and spark does not stay
on.
Auth
Service
Rep Only
a. That gas pressure complies with nameplate ratings.
b. Electronic spark ignition module. Replace if
necessary.
c. That both gas solenoids are staying open.
Main burner comes on but will not
stay lit.
Auth
Service
Rep Only
a. Check burner ground for bad wire or connection.
Replace with high temperature wire if necessary.
b. Check for low gas supply pressure. If necessary,
replace ignition control module.
c. Ceramic insulator on pilot for cracks.
Replace pilot if cracked.
This manual suits for next models
2
Table of contents
Other Groen Kettle manuals

Groen
Groen EE Domestic User manual

Groen
Groen TDHC Series User manual

Groen
Groen EE Domestic User manual

Groen
Groen EE-20 User manual

Groen
Groen TDB/6 User manual

Groen
Groen DEE/4-20 Series User manual

Groen
Groen AH/1 User manual

Groen
Groen OM-TDB/7 User manual

Groen
Groen TDH User manual

Groen
Groen DEES-40 User manual