manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GST
  6. •
  7. Marine Equipment
  8. •
  9. GST C-9402 User manual

GST C-9402 User manual

30306067 Issue 1.02
Features
Used as the base of detectors or as the sounder.
Description
C-9402 Conventional Base Mount Sounder (the
sounder) is an audible signal appliance in field, used
together with I-9308 module. When there is a fire, the
sounder gives alarming sound to warn people.
Connection and Cabling
Fig. 1 shows terminals of the sounder.
A
B
Mounting Hole
Fig. 1
Refer to Application for connection.
Recommended Cabling
1.0mm2or above fire cable, subject to local codes.
Installation
Warning: Before installing the sounder,
disconnect the power from loop and verify that all
the bases are securely installed and that the
cabling is correct on each base.
1 Before installation, first check the enclosure
without scrapes and distortion, the labels should be
complete.
2 Mounting of the sounder is shown in Fig. 2.
Back Cover
Base
Sounder
Top Cover
or Detector
Back Box
Fig.2
3 Fix the sounder to the back box with screws.
4 Align the orientation mark of the top cover to mark
A (refer to Fig.1), rotate the sounder to align the mark
with mark B, the top cover is installed. If it's used as
detector base, take down the top cover and install the
detector on it in the same method as mounting the top
cover.
Application
The sounder can be used as a base to install
intelligent heat or smoke detectors to combine
detection and alarm. It can also be used as a sounder.
The audible control part of the sounder has two wires.
Used as the sounder, it needs separate wiring to
connect with detectors.
The sounder can be directly connected to I-9308
module, which occupies two consecutive address
points. When there is fire alarm message, it activates
low address to give pre-alarm sound, activates high
address to give fire alarm sound. System wiring is
shown in Fig. 3.
Sounder
Sounder
24VDC
Fire Alarm Control Panel
4
6
3
5
4
6
5
2
3
2
I-9308
D2D1
Z1 L+
1
1
L-
Z2
ΩResistor
Fig. 3
"5" of the sounder connects to "L+" of I-9308 module.
"6" of the sounder connects to "L-" of I-9308 module.
The "5" and "6" of the last sounder in the system
should be connected with a 4.7kΩterminal resistor.
The sounder can also be used as detector base
to mount different detectors, which can both detect fire
and give audible alarm signal to realize combined
function. Remove the top cover and mount the
intelligent or conventional detector.
C-9402
Conventional Base Mount Sounder
All manuals and user guides at all-guides.com
all-guides.com
30306067 Issue 1.02
When mounting intelligent detector on the
sounder, first wire according to Fig. 3, then refer
to Fig.4.
Intelligent
Detector
3
1
1
Fire Alarm Control Panel
Intelligent
Detector
Z1
Z2
L+
I-9308L-
D2
D1
2
4
6
5
3
2
4
6
5
24VDC
Fig. 4
"1" and "3" of the sounder connect to loop,
polarity-insensitive.
"2" and "4" don't connect to any wire, but are used to
fix the detector accessorily.
When mounting conventional detectors on
the sounder, I-9319 Intelligent Zone Monitor Unit
should be added to the system and a P-9907
Active End of Line Unit connected to the end of
the loop. First wire according to Fig. 3, then refer
to Fig. 5.
Conventional
Detector
3
1
1
Fire Alarm Control Panel
Conventional
Detector
Z1
Z2
L+
I-9308L-
D2
D1
24VDC
2
4
6
5
3
2
4
6
5
I-9319
Z1 O-
Z2 O+
3
Diode
Diode
P-9907
Active End of Line Unit
Fig. 5
"1" of the sounder connects to "O+" of the zone
monitor unit.
"3" of the sounder connects to "O-" of the zonemonitor
unit.
An 1N5819 diode (please note polarity) should be
connected between 1 and 2 of the sounder.
"2" of the sounder connects to "1" of the next
equipment as anode of output power.
"2" and "3" of the last sounder connect to end of line
unit.
"4" of the sounder doesn't connect to any wire, but is
used to fix the detector accessorily
Specification
Operating Voltage
24VDC
Alarm Current
≤15mA
Sound Level
≥85dB (1m horizontally
ahead (A weighted))
Type of Alarm Signal
Pre-alarm: Intermittent
(0.5s on 1s off)
Fire Alarm: Continuous
(0.4s on 0.3s off)
Ingress Protection
Rating
IP31
Operating
Temperature
-10℃~+50℃
Relative Humidity
≤95%, non condensing
Material and Color of
Enclosure
ABS, white (RAL 9016)
Dimension
Diameter: 120mm
Height: 38.8mm(without top
cover)
Weight
About 130g
Accessories and Tools
Model
Name
Remark
I-9308
Addressable
Sounder Circuit
Module
Order separately
Top cover
Order separately
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during the warranty period.
This warranty shall not apply to any product that is
found to have been improperly installed or used in any
way not in accordance with the instructions supplied
with the product. Anybody, including the agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn
All manuals and user guides at all-guides.com

Other GST Marine Equipment manuals

GST C-9403 User manual

GST

GST C-9403 User manual

GST DC-M9416 Series Assembly instructions

GST

GST DC-M9416 Series Assembly instructions

GST I-9404 User manual

GST

GST I-9404 User manual

GST C-9404(Ex) User manual

GST

GST C-9404(Ex) User manual

GST I-9403 User manual

GST

GST I-9403 User manual

GST C-9404 User manual

GST

GST C-9404 User manual

GST C-9402 User manual

GST

GST C-9402 User manual

GST I-9404 User manual

GST

GST I-9404 User manual

GST I-9404 User manual

GST

GST I-9404 User manual

GST C-9402 User manual

GST

GST C-9402 User manual

GST DC-9404(IS) User manual

GST

GST DC-9404(IS) User manual

GST C-9404(Ex) User manual

GST

GST C-9404(Ex) User manual

Popular Marine Equipment manuals by other brands

AC MARINE KUM400 Series installation guide

AC MARINE

AC MARINE KUM400 Series installation guide

Zenitel Marine Master Clock 70000 Technical  user's manual

Zenitel

Zenitel Marine Master Clock 70000 Technical user's manual

Dual MXD55 Installation & owner's manual

Dual

Dual MXD55 Installation & owner's manual

Kongsberg EA440SP Quick installation guide

Kongsberg

Kongsberg EA440SP Quick installation guide

E2S BExA120D instruction manual

E2S

E2S BExA120D instruction manual

Garmin Reactor 40 Kicker Configuration guide

Garmin

Garmin Reactor 40 Kicker Configuration guide

Furuno DSC-6A installation manual

Furuno

Furuno DSC-6A installation manual

Pfannenberg DS5-SIL Instruction Manual/Safety Manual

Pfannenberg

Pfannenberg DS5-SIL Instruction Manual/Safety Manual

TRIGA TR-LOC2100 Product Installation

TRIGA

TRIGA TR-LOC2100 Product Installation

Simrad FU80 user guide

Simrad

Simrad FU80 user guide

Furuno GP-3500F installation manual

Furuno

Furuno GP-3500F installation manual

Simrad AP20 manual

Simrad

Simrad AP20 manual

Scosche ACM3 quick start guide

Scosche

Scosche ACM3 quick start guide

Furuno FELCOM18 installation manual

Furuno

Furuno FELCOM18 installation manual

Marine Instruments M3P-T user manual

Marine Instruments

Marine Instruments M3P-T user manual

Zenitel Vingtor VSS Installation & service manual

Zenitel

Zenitel Vingtor VSS Installation & service manual

Raymarine AXIOM PRO installation instructions

Raymarine

Raymarine AXIOM PRO installation instructions

TradeQuip PORTA POWER KIT owner's manual

TradeQuip

TradeQuip PORTA POWER KIT owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.