Gtec MUST400T User manual

Quick Start
Modular UPS MUST400T

Quick start_MUST400T_ENG_REV00 2
Safety Precautions
This manual contains information concerning the installation and operation of Modular UPS. Please carefully read this
manual prior to installation.
The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its
agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty.
The UPS has been designed for commercial or industrial use only, and is not intended for use in any life support application.
This is a CLASS C Uninterruptible Power Supply (UPS) product. In a domestic environment, this product may cause radio
interference, in which case, the user may be required to take additional measures.
Conformity and standards
This product complies with 2006/95/EC ,CE73/23 & 93/68 (low voltage safety) and 2004/108/EC, 89/336 (EMC), and the
following UPS product standards:
*IEC62040-1 General and safety requirements for use in operator access area
*IEC/EN62040-2 EMC requirements CLASS C
*IEC62040-3 Performance requirements and test methods
Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories
only.
WARNING: high earth leakage current
Earth connection is critical before connecting the input supply (include both utility supply and battery).
"Earth leakage current introduced by the UPS, in any configuration from 10kW to 200kW, exceeds 3.5 mA and is less than 1000
mA and complies with the requirements of IEC/EN 62040-1 / IEC/EN 60950-1" Transient and steady-state earth leakage currents,
which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers ( RCCBs) must be selected sensitive to DC (class B) and insensitive to transient current pulses
Type S.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with local electrical authority codes of practice.
WARNING: backfeeding protection
This system has a control signal available for use with an automatic device, externally located, to protect against backfeeding
voltage through the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass
circuit, a label must be added to the switchgear to advise service personnel that the circuit is connected to a UPS system.
The text has the following meaning or is equivalent to: Isolate the UPS before working on the circuit of this UPS.
警告
危险
警告
危险
警告
危险

Quick start_MUST400T_ENG_REV00 3
Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools and should be carried out
only by trained personnel. The components that can only be accessed by opening the protective cover with tools cannot be
maintained by user.
This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator access area UPS”. Dangerous
voltages are present within the battery box. However, the risk of contact with these high voltages is minimized for non-service
personnel. Since the component with dangerous voltage can only be touched by opening the protective cover with a tool, the
possibility of touching high voltage component is minimized. No risk exists to any personnel when operating the equipment in the
normal manner, following the recommended operating procedures in this manual.
Battery voltage higher than 400Vdc
All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out
only by trained personnel.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS
EQUIPMENT.
WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 400Vdc AND IS
POTENTIALLY LEATHAL.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large
bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the
recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting
facilities.
THE NON-COMPLIANCE WITH THE REQUIREMENTS PRESENT IN THIS MANUAL WILL VOID THE
WARRANTY.
THE WARRANTY IS VOID IF THE INTERVENTIONS AND/OR MODIFICATIONS ARE EXECUTED BY
UNAUTHORIZED PERSONNEL.
警告
危险
警告
危险

Quick start_MUST400T_ENG_REV00 4
1.1 Introduction
This chapter introduces the relevant requirements for positioning and cabling of the Modular UPS and related
equipment. Because each site has its requirements, it is not the aim of this chapter to provide step-by-step
installation instructions, but to act as a guide for the general procedures and practices that should be
observed by the installing engineer.
Warning: installation can only be done by authorized engineers
Do not apply electrical power to the UPS equipment before the commissioning engineer arrives at installation site.
The UPS should be installed by a qualified engineer in accordance with the information contained in this chapter. All the
equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information.
Note: 3-Phase 4-Wire Input Power is required
The standard UPS system can be connected to TN, TT AC distribution system (IEC60364-3) of 3-phase
4-wire, and a 3-wire to 4-wire conversion transformer is provided as an optional part.
WARNING: battery hazards
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH
THIS EQUIPMENT.
After battery connection, the battery terminals voltage will exceed 400Vdc and is potentially lethal.
Follow the suggested actions here below:
Eye protection must be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a
container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with
water.
1.2 Initial Checking
Before installing UPS, please check these items as below:
1. Visually examine if there is any damage inside and outside the UPS rack and battery equipment due to the
transportation. Report any such damage to the shipper immediately.
2. Verify the product label and confirm the correctness of the equipment. The equipment label is attached on
the back of front door. The UPS model, capacity and main parameters are marked on the label.
1.3 Location
1.3.1 UPS Location
The UPS is intended for indoor installation and should be located in a cool, dry and clean environment with
adequate ventilation to keep the environmental parameters within the specified operating range (see
Table.9-2).
Improper use of UPS and in condition out of the operating range invalid the warranty.
Avoid to install the UPS in room which are exposed directly under sunlight or near sources of hot air.
警告
危险
警告
危险
警告
危险

Quick start_MUST400T_ENG_REV00 5
The Modular series UPS uses forced convection cooling by internal fans. Cooling air enters the module
through ventilation grills located at the front part of the cabinet and exhausted through grills located in the rear
part of the cabinet. Please do not block the ventilation holes.
If necessary, an extractor fans system should be installed to aid cooling-air flow.
An air filter should be used when the UPS is to operate in a dirty environment and should be regularly
cleaned to maintain proper airflow.
The cooling capacity of air conditioner should be selected according to the power loss data of UPS specified
in Table.9-8: Normal mode (VFI SS 111 double-conversion UPS)
Note 1 : The UPS should be installed on a concrete surface or other surface that is not combustible.
Note 2 : Ensure that the capacity of the floor is greater than the weight of the UPS and battery cabinet (if
present), and verify that the floor is flat.
1.3.2 External Battery Room
The battery will generate some amount of hydrogen and oxygen at the end of charging, so the fresh air
volume of the battery installation environment must meet EN50272-2001 requirements.
The environmental temperature of the battery must be stable. Ambient temperature is a major factor in
determining the battery capacity and lifetime.
The rated operating temperature of battery is 20°C. Operating above this temperature will reduce the battery
life, and operation below this temperature will reduce the battery capacity. If the average operating
temperature of battery is increased from 20ºC to 30ºC, then the service life of the battery will be reduced by
50%. If the operating temperature of the battery is above 40ºC, then the battery service life will decrease in
exponential rate.
In a normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away
from heat sources or air outlets.
If external batteries are used, the battery circuit breakers (or fuses) must be mounted as close as possible to
the batteries, and the connecting cables should be as short as possible.
(*): The standard EN 50272-2 for air change envisages that the minimum opening must satisfy the following equation:
A = 28 x Q = 28 x 0.05 x n x Igas x C10 (1/10³) [cm²]
where: A = free opening for air intake and outlet
Q = flow of air to be removed [m³/h]
n = number of battery elements;
C10 = battery capacity over 10 hours [Ah]
Igas = current that produces gas [mA//Ah]
in accordance with the standard: Igas = 1 VRLA type battery
When the equation is applied for 240 element (40 battery) hermetically-sealed lead batteries:
A = 336 x C10 / 10³ [cm²]
When using 120Ah batteries, the minimum aperture should be approximately:
A = 41 [cm²]
1.3.3 Storage
If the equipment is not installed immediately, it must be stored in a room protected against excessive humidity
and heat sources (see Table.9-2).
The battery needs to be stored in dry and cool place with good ventilation.
The most suitable storage temperature is from 20 ºC to 25ºC.
Preventing battery slow discharge
警告
危险

Quick start_MUST400T_ENG_REV00 6
Should the UPS remains unpowered for a prolonged period of time while the battery are connected, the
batteries may slowly discharge and being so permanently damaged .In such cases it is therefore
recommended to leave the battery circuit breaker(s) open. During storage in any case, periodically charge the
battery according to the battery user manuals.
1.4 Positioning
When the equipment has been positioned, ensure the UPS will remain stationary and stable.
To guarantee optimize working lifetime, the place chosen must guarantee:
Space for easy operation on the UPS
Enough air to dispel heat produced by UPS
Protection against atmospheric agents
Protection against excessive humidity and heat sources
Protection against dust
With the current fire prevention requirements
The operating environment temperature is within +20°C to +25°C. The batteries are at maximum
efficiency in this temperature range (for information about the battery storage and transportation as well
as the environment, refer to Table.9-2 )
This equipment is of steel frame structure wrapped by removable panels. The cover and the lateral
panels are fixed by screws.
After opening the UPS rack door, the auxiliary connections for communitation ports and dry-contact and
the maintenance bypass can be accessed.
The UPS provides air inlet port in the front and the air exhaust port in the rear part. It is forbidden to
install the UPS directly to the rear wall. Leave at least 50cm of free space in the rear. See picture
below.
1.4.1 System Cabinet
A UPS system can comprise an UPS rack system, external battery cabinet, depending on the specific system
requirement.
All the UPS system cabinets used in the same installation site are of the same height and should be
positioned side-by-side to achieve an aesthetically appealing effect. Refer to Chapter 7 Installation Drawing
for the positioning of UPS cabinet.

Quick start_MUST400T_ENG_REV00 7
1.4.2 Moving the Cabinets
Warning
Ensure that any lifting equipment used in moving the UPS cabinet have sufficient lifting capacity. The UPS is
fitted with castors –take care to prevent movement when unbolting the equipment from its shipping pallet.
Ensure adequate personnel and lifting aids are available when removing the shipping pallet.
Ensure that the UPS weight is within the weight loading capacity range of any hoisting equipment. See
Table.9-3 for UPS weight.
UPS and optional cabinets can be handled by means of a fork lift or similar equipment. The UPS cabinet can
also be moved by its wheels (where are present) only for short distance.
Note: Care must be taken when handling units fitted with batteries. Keep such moves to a minimum.
1.4.3 Distances Required for Operating
It’s no necessary to leave free space in lateral part of the UPS.
To permit first commissioning, the tightening of power terminals inside the UPS and all service activity, it is
recommended to leave enough free space to enable the passage of personnel with the doors fully opened. It
is important to leave a distance of 500mm in the rear side of the rack to permit adequate circulation of air
coming out the unit.
1.4.4 Front Access & Rear access
The UPS system is designed for front and rear access. For common service activity and replacement of
power modules is required only front access, for installation is required rear access.
1.4.5 Final Positioning
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS will
remain stationary and stable.
1.4.6 Installation of Adjustable Feet
Installation diagrams in Chapter 4 of this manual identify the location of the holes in the base plate through which the
equipment can be bolted to the floor. If the UPS is to be located on a raised floor, it should be mounted on a pedestal
suitably designed to accept the UPS point loading (more than 800 kg).
1.4.7 UPS Composition
The UPS structure is shown in Fig. 1-1. The UPS configuration is available in Table. 1-1
警告
危险

Quick start_MUST400T_ENG_REV00 8
(a) 10 module cabinet
(b) 6 module cabinet
Fig.1- 1: UPS Structure

Quick start_MUST400T_ENG_REV00 9
Table.1- 1: UPS Configuration List
Item
Component
Quantity
Remarks
1
System Display
1
Requisite, factory installed
2
Bypass module
1
Requisite, factory installed
3
Input/output/maintenance
bypass siwtches
1
Requisite, factory installed
4
Power module
1 ≤n ≤10
Requisite
1.4.8 Installing Power Modules
It’s not possible to install a power module with different rated power.
The default power modules number is from the top to the bottom.
Insert the module in the right free shelf, and push it into the cabinet.
Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module.
See fig.1-2
Fig.1- 2: Power Module Installation Diagram
1.4.9 Cable Entry
Cables can enter into the UPS system both from bottom and top. Cable entry is made possible through a
blanking plates fitted at the bottom or top of the equipment. The recommended installation practice is to install
glands to prevent foreign material entering into the cabinet.
1.5 External Protective Devices
For safety concerns, it is necessary to install external circuit breakers or other protective devices for the input
AC supply of the UPS system. This section provides generic practical information for qualified installation
engineers. The installation engineers should have the knowledge of the wiring standards, and the equipment
to be installed.

Quick start_MUST400T_ENG_REV00 10
1.5.1 Rectifier and Bypass Input Supply of the UPS
Over currents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power
cable current-carrying capacity and overload capacity of the system (see Tab. 9-7). Generally, the magnetic
circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the current listed in Tab. 9-7 is
recommended.
Dual input: In case of double mains used, separate protective devices should be installed for the rectifier input
and bypass input in the incoming mains distribution panel.
Note: The rectifier input and bypass input must use the same neutral line.
So don’t remove the neutral common copper bridge present between input and bypass terminals
Protection against earth faults (RCD devices):
The RCD device installed upstream of the input supply should be comply with:
Sensitive to DC unidirectional pulses (classA) in the network
Insensitive to transient current pulses
Have an average sensitivity that is adjustable between 0.3A and 1A.
Fig.1- 3: The Symbols of RCCB
When using the RCD in the split bypass system or parallel system, the RCD should be installed upstream of
the input distribution to avoid wrong alarm.
The residual current introduced by RFI filter in the UPS is between 3.5mAand 1000mA. It is recommended to
confirm the sensitivity of each RCD of upstream input distribution and downstream distribution (to load).
1.5.2 External Battery
The DC compatible circuit breaker provides over current protection for UPS system and battery, which is
provided by the external battery cabinet.
1.5.3 UPS Output
In case of an external distribution cabinet is used for load distribution, the selection of protective
devices must provide discrimination with those that are used at the input to the UPS
(see Tab. 9-7).

Quick start_MUST400T_ENG_REV00 11
1.6 Power Cables
Design the cables according to the descriptions in this section and local regulatory wiring standards, and the
environmental conditions (temperature and physical support media) should be taken into consideration.
Refer to IEC60950-1 Table 3B Cabling.
WARNING
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC SHOCK HAZARD,
OR RISK OF FIRE, IFAN EARTH FAULT OCCURS.
Table.1- 2: Maximum Steady AC and DC Current
UPS
power(KVA)
Rated current (A)
Main input current at full load
battery charging (1,2)
Output current at full load
(2)
Battery discharging current at
E.O.D=1.67V/cell, no overload
380V
400V
415V
380V
400V
415V
36
Batt./string
38
Batt./string
40
Batt./string
200
306
291
280
303
288
277
468
443
421
120
184
175
168
182
173
166
281
266
253
100
153
146
140
152
144
139
234
222
211
60
92
88
84
91
87
83
142
133
127
40
62
59
56
61
68
56
94
89
85
30
46
44
42
46
44
42
71
67
64
20
31
29
28
31
34
28
47
45
43
Note:
1. Input current related to single mains supply.
2. Take special care when determining the size of the output and bypass neutral cable, as the current
circulating on the neutral cable may be greater than nominal current in the case of non-linear loads, which is
usually 1.732 times of rated currents.
3. The earth cable connecting the UPS to the main ground system must follow the most direct route possible.
The earth conductor should be sized according to the fault rating, cable lengths, type of protection, etc.
According to AS/IEC60950-1, the cross section area of the conductor is 90mm2 (200kVA), the cross section
area of the conductor is 50mm2 (120KVA).
4. When sizing battery cables, a maximum volt drop of 4Vdc. is permissible at the current ratings given in
Table.1-2. The load equipment is connected to a distribution network of individually protected busbars fed by
the UPS output rather than connected directly to the UPS. In case off cabinet parallel, the output cable of
each ups rack unit should be kept at equal length between the output of the ups rack output terminals and the
parallel distribution busbars to avoid affecting the shared current. When laying the power cables, do not form
coils, so as to avoid the formation of electromagnetic interference.
5. See Chapter 4 Installation Drawing for the positions of wiring terminals.
警告
危险

Quick start_MUST400T_ENG_REV00 12
1.6.1 Cable Connections
Note
The operations described in this section must be performed by authorized electricians or qualified
technical personnel. If you have any difficulties, do not hesitate to contact our Customer Service & Support
department.
After the equipment has been finally positioned and secured, refer to Chapter 4 Installation Drawing to
connect the power cables as described in the following procedures:
1. Verify that all the external input distribution switches of the UPS are completely opened and the UPS
internal maintenance bypass switch is opened. Attach necessary warning signs to these switches to prevent
unauthorized operation.
2. Open rear panel of the UPS, and then the power connection terminals are accessible.
3. Connect the protective earth and any necessary grounding cables to the PE terminal. The cabinet for the
UPS must be connected to the user’s ground connection.
Note: The grounding cable and neutral cable must be connected in accordance with local and national codes
practice.
Identify and make power connections for incoming cables according to one of the two procedures below,
depending on the type of installation:
Common Input Connections
4. For common bypass and rectifier inputs, connect the AC input supply cables to the UPS bypass terminals
(X2/L21-L22-L23 X1/N1) Refer to Fig. 4-11 and tighten the connections to 5 Nm (M6 Bolt), 13Nm (M8 Bolt) or
25Nm (M10 Bolt). Do not remove copper bridge between X1 and X2 terminals.
ENSURE CORRECT PHASE ROTATION AND TIGHTEN CONNECTION TERMINALS
Split Bypass Connections
5. If a 'split-bypass' configuration is used, ensure that the common copper bridges between Bypass and
Rectifier inputs are removed.
Note: DO NOT REMOVE THE NEUTRAL COPPER BRIDGE
Connect the AC input supply cables to the rectifier input terminals (X1/L1-L2-L3-N1) Refer to Fig.4-11 and the
AC bypass supply cables to the bypass input terminals (X2/L21-L22-L23) and tighten the connections to 5
Nm (M6 Bolt) or 13Nm (M8 Bolt) or 25Nm (M10 Bolt).
Note: ENSURE CORRECT PHASE ROTATION AND TIGHTEN CONNECTION TERMINALS
Frequency Converter Mode
If the frequency converter configuration is used, connect the AC input cables to the rectifier input terminals
(X1/L1-L2-L3-N1) Refer to Fig.4-11 and tighten the connections to 5Nm (M6 bolt), or to 13Nm (M8 bolt), or to
25Nm (M10 bolt).
Note: ENSURE CORRECT PHASE ROTATION AND TIGHTEN CONNECTION TERMINALS.
No need to connect the bypass input cables to bypass input terminals in case of dual input version and
ensure to remove copper bridge in phases terminals. Leave the neutral copper bridge installed.
警告
危险

Quick start_MUST400T_ENG_REV00 13
Output System Connections
6. Connect the system output cables between the UPS output terminals (X3/L31-L32-L33-N2) Refer to
Fig.4-11 and the critical load and tighten the terminals screws to 5Nm (M6 Bolt) or to 13Nm (M8 Bolt) or to
25Nm (M10 Bolt).
Note: ENSURE CORRECT PHASE ROTATION.
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then
ensure that the system output cables are safely isolated at their ends.
7. Re-install all the protective covers.
警告
危险

Quick start_MUST400T_ENG_REV00 14
General safety information for UPS 62040-2 CLASS 2-3:
Italiano
English
Francais
Deutsch
Espanol
Attenzione leggi per
prima il manuale.
Warning: please read
the manual first.
Attention, lire le
manuel d’instruction.
Achtung: Zuerst die
Bedienungsanleitungen
durchlesen.
Cuidado! Leer el
manual de el
usuario antes de
obrar
Apparato per
ambiente di
lavoro interno con
polveri e inquinanti
normali.
Indoor equipment for
environment with
normal pollution and
dust.
Equipements pour
l’intérieur avec une
pollution normale.
Gerät für interne
Arbeitsräume mit
normaler Schadstoff-
und Staubentwicklung.
Equipo por el
interior con polvo y
poluciòn normal
EMC
L’Apparato In
ambienti residenziali
può causare
interferenze
In residential
environments the
equipment can cause
interference
L’appareil peut
provoquer des
interférences dans
une zone
résidentielle.
Das Gerät kann in
Wohngebäuden
Interferenzen
verursachen.
En el ambiente
residencial el
equipo puede
causar
interferencias
Collegare il
conduttore di terra al
UPSE’ consigliata la
protezione
differenziale
At first connect the Pe
conductor.Differential
protection is suggested.
En premier connecter
le conducteur de
terre (PE). Protection
différentielle
suggérée.
Das Erdungskabel an die
USV abschließen. Ein
Differentialschutz ist
ratsam.
Conectar el cable
de tierra a el SAE.
Se aconseja la
protecction con el
interruptor
diferencial
Attenzione batterie
interne non aprire
pericolo
Warning: batteries
inside, do not open for
chemical and electrical
risk
Attention, batteries
internes, risques
chimiques et
électriques.
Achtung! Batterien im
Inneren. Nicht öffnen!
Gefahr!
Cuidado! Batteries
en el interior, no
abrir, peligro
Attenzione la
manutenzione è
consentita solo al
personale
dell’assistenza tecnica
scollegare rete e le
batterie prima di
operare
Warning, maintenance
is allowed only to duly
trained persons. Only
technical assistance
personnel can open
and repair the UPS.
Before working on the
UPS disconnect mains
and batteries.
Attention, seules les
personnes autorisées
peuvent ouvrir et
intervenir dans
l’onduleur. En
premier, couper
l’alimentation et le
circuit des batteries.
Achtung: Die Wartung
ist ausschließlich dem
technischen
Kundendienst
vorbehalten!
Das USV-Netz vor dem
Eingriff abtrennen!
Cuidado! La
asistencia tècnica
debe ser hecha
solamente para el
personal tècnico
especializado.
Desconectar el SAE
antes de operar
Attenzione durante la
manutenzione usare i
DPI
Warning: during
maintenance use
protection devices
Attention, utilizer les
EPI (équipements de
protection
individuels)
Achtung! Während der
Wartungsarbeiten
müssen die PSA
verwendet werden.
Attencion utilizer
los dispositivo de
protection
individual antes de
obrar
Table of contents
Other Gtec UPS manuals
Popular UPS manuals by other brands

Eaton
Eaton 93PM IBC-L Installation and operation manual

Eaton
Eaton Callisto 5PX RT G2 Service manual

Lowell power
Lowell power Pure Sine Wave Value Series User & installation manual

CyberPower
CyberPower CP1200EIPFCLCD Function setup guide

Mustek
Mustek POWERMUST 636 quick start guide

CyberPower
CyberPower Value800EI user manual