Gtec ZS110 User manual

USER MANUAL
On-Line UPS
Model ZS110
6000VA-10000VA
Uninterruptible PowerSupply System
1

2
Contents
1Brief introduction.................................................................1-5
1.1System andmodeldescription....................................................1
1.2Descriptionof commonlyused symbols....................................2
1.3Appearance...............................................................................2-4
1.4Productspecificationandperformance......................................5
2. Safety Instruction...................................................................6
3. Installation........................................................................7-14
3.1Unpackingandinspection...........................................................7
3.2Input andoutputpower wiringandprotectiveearthground
installation..............................................................................7-9
3.3Operatingprocedureforconnectingthe longbackuptime
modelUPSwiththeexternal battery..................................9-10
3.4Paralleloperation.................................................................10-13
4. OperationandOperatingmode.......................................14-20
4.1Operation..............................................................................14-15
4.2Operatingmode....................................................................15-20
5. Batterymaintenance.............................................................21
6. Notesfor batterydisposal and battery replacement..............22
7. Troubleshooting..............................................................23-24
Appendix 1 Description of Display panel.............................25-26
Appendix2 Indicator and alarm..........................................27-28
8. Chapter Operation(LCDmodel) ....................................29-39
8.1OperationDisplay Panel...............................................................29
8.2OperationMode.......................................................................30-34
8.3OperatingInstructions.............................................................34-35
8.4CheckingUPSfunction.................................................................36
8.5Troubleshooting.......................................................................37-39
3
1. Brief introduction
1.1Systemandmodel description
TheOn-Line-Series isanuninterruptiblepower supply incorporating
double-converter technology.Itprovides perfect protectionspecifically for
strictload. Thedouble-converterprinciple eliminatesallmains power
disturbances. Arectifier converts the alternatingcurrentfrom the socket
outlet to direct current. Thisdirect current charges the batteriesand powers
the inverter.In the eventof powerfailure, the maintenance-freebatteries
power the inverter.Thustheinverter generates asinewave AC power,
which permanentlysupplies the loads.
Designed with the provenon-line, double conversionarchitecture, this
series ofUPS offers thegreatest degree ofavailabilityinpowerprotection
andprovidescontinuous high-quality AC power to connectstrict load,
especially for the basicequipments insomeareasas: finance,
communication, government, traffic, manufacture, education andso on.
This manual is applicableto the followingmodels:
TypeModel InputBattery
6KVA6KSingle phase +N inbuilt
Standard 10KVA10KSingle phase +N inbuilt
6KVAS 6KS Single phase +N External batterybank
10KVAS10KSSingle phase +N External batterybank
10KVAS3C10KS Three-phase + N + PEExternal batterybank
12KVAS3C12KS Three-phase + N + PEExternal batterybank
15KVAS3C15KS Three-phase + N + PEExternal batterybank
Long
back up
time
20KVAS3C20KS Three-phase + N + PEExternal batterybank

4
1.2 Description of commonly usedsymbols
Thefollowingsymbols willbe used in thismanualand mayappearduring
the courseof your practical applications. Therefore,allusers shouldbe
familiar with them and understand their meanings.
1.3Appearance
BACK VIEW of 6K
Notationand Explanation
Notation
ExplanationNotation
Explanation
Alert you topayspecial
attention Protective ground
Cautionofhighvoltage Alarm silence
Turn on the UPS Overload indication
Turn offthe UPS Batterycheck
Idle or shut down the UPS Recyclable
Alternatingcurrent source (AC)
Donot dispose with
ordinarytrash
Direct current source (DC)
Battery
5
BACK VIEW of 6K-KS
BACK VIEW of 10K

6
BACK VIEWof 10K-KS
BACK VIEW of 3C10K-KS 3C12K-KS 3C15K-KS 3C20K-KS
7
1.4Product specification andperformance
General specification Input(full load)Output
Power Rating
Model Frequency
(Hz) VoltageCurrent
Voltage Current
Dimensions
(W*L*H)mm
Weight
(kg)
6KVA/4.8KW
6K 50/60 (176-276)VAC
31max
220V/230V
27A 260X560X717
68
6KVA/4.8KW
6KS 50/60 (176-276)VAC
31max
220V/230V
27A 260x533x501
17.5
10KVA/8KW
10K 50/60 (176-276)VAC
50max
220V/230V
45A 260X560X717
70
10KVA/8KW
10KS 50/60 (176-276)VAC
50max
220V/230V
45A 260x533x501
19.5
10KVA/8KW
3C10KS 50/60 (304-478)VAC
50max
220V/230V
45A 260X560X717
12KVA/9.6KW
3C12KS 50/60 (304-478)VAC
60 max
220V/230V
54A 260X560X717
15KVA/12KW
3C15KS 50/60 (304-478)VAC
75 max
220V/230V
68A 260X560X717
20KVA/15KW
3C20KS 50/60 (304-478)VAC
100 max
220V/230V
91A 260X560X717
●Electrical performance INPUT
Model Voltage FrequencyPower Factor
6K(S)/S10K(S) Single-phase(220VAC
230VAC)50/60Hz±5%
(adjustable)
>0.99(Full load)
3C10KS/3C12KS/3C15KS
/3C20KS Three-phase(380VAC/220
VAC 380VAC/230VAC)50/60Hz±5%
(adjustable)
>0.95(Full load)
Output
Voltage
regulation
Power
factor
Frequencytolerance Distortion Overload capacity
Current
crest ratio
±1%0.8lag
Synchronized
46-
54Hzin Line mode
(AC mode)±1% of
normal frequencyin
Batterymode
THD<2%
Full load
(Linear load)
105%-
125%load transfers
tobypass mode after 1
minutes >130% load
transfers to bypass mode
after 30second
3:1
maximum
Operating environment
TemperatureHumidityAltitude Storage temperature
0°-40°<95%<1000m0°-40°
Note: Ifthe UPS is installed orused in aplace where the altitudeis above
than 1000m, theoutputpower must bedecreaseinuse, please refer
to the following:
Altitude(M) 1000150020002500 3000 3500 4000 4500 5000
Load 100%
95%91%86%82% 78% 74% 70% 67%

8
2. Safety Instruction
Even iftheinterruptiblePower System(UPS) isnotconnectedto utility
power,the outputsocketof theUPS maystillpresent220V/230Voutput
voltage.
If itis necessaryto replace the external batterycord or powercord, please
purchase the originalmaterial fromthe service center or distributorof
our company so as toavoid overheat or spark resulting infiredue to
insufficient capacity.
Donotletbattery or batteries get closetoanyheatingsourceanddo not
incinerate batteryor batteries, theymayexplode.
Donot open or mutilate the batteryorbatteries, released electrolyteis
highlypoisonous and harmful tothe skin and eyes.
Donotshortthepositiveand negativeofbattery electrode. Otherwise, it
maycauseelectric shockorfire.
To avoid therisk of beingshocked, please donotattempt to open thecase
of the UPS.
Abattery can presentariskof electricshockandhighshort circuit
current.
Donot plughousehold appliance such as hair dryers to UPS.
9
3. Installation
3.1Unpacking and inspection
1) Unpack the packagingandcheck the packagecontents. The shipping
packagecontains:
A UPS
A usermanual
A communication cable
2) Inspect the appearanceof theUPS to seeifthere is anydamage during
transportation.Donotturnonthe unit andnotify the carrier anddealer
immediately if there is anydamage or lackingof someparts.
3.2Input and output power wiringand protective earth ground
installation
3.2.1. Notes forinstallation
1) The UPS mustbe installedinalocation withgood ventilation, far away
fromwater, inflammablegas and corrosive agents.
2) The UPS shouldnotbe tilted.The air inletportat the lowerpart of the
frontpaneland thefanoutlet porton the rearpanelshould notbe
blocked soas to ensure goodventilation (Allow at least0.5m of spaceon
each side).
3) In caseifthe UPS isunpacked,installed andusedat verylow
temperatures, condensationofwater drops mayappear. Itis necessaryto
waituntil theUPS isfullydried inside out before proceedingto
installationand use. Otherwise, there maybearisk of electricshock.
3.2.2. Installation
Installationand wiring must be performed in accordancewiththe local
electriccodeandthefollowinginstructionsbyprofessional personnel. For
safety, please cut off themains powerbreaker beforeinstallation. The
batterybreakeralso needs to becut off ifit is alongbackup time model.
1) Open the terminalblock cover locatedon therearpanel of the UPS
(please refer to theappearancediagram).
2) For6K (S) UPS, it is recommended to select the UL101510AWG
(6mm2) wireor otherinsulated wirewhichcomplies with AWG Standard
forthe UPS inputand outputwirings.

10
3) For 10K (S)/3C10KS UPS, itisrecommended toselect theUL1015
8AWG (10mm2) wireor other insulated wirewhich complies with AWG
Standardforthe UPS inputand output wirings.
4) For 3C12KS/3C15KS/3C20KS UPS, itis recommendedtoselectthe
UL10156AWG(25mm2)wireor other insulated wire whichcomplies
with AWG Standard for theUPS input andoutput wirings.
Note:Donot usethe wallreceptacleas the inputpowersource for the
UPS, as its rated currentisless thanthe UPS’s maximum input
current.Otherwisethereceptaclemay beburned and destroyed.
(Please referto section 1.4)
5) Connect theinputand outputwires to the correspondinginput and output
terminals according to the followingdiagram.
Note:you must makesurethat the input andoutput wires and the input and
outputterminals are connected tightly.
6) The protectiveearthgroundwirerefers tothewire connectionbetween
theequipment which consumeselectro-equipment and the ground wire.
The wire diameter of protectiveearthground wireshouldbe atleast as
abovementioned foreachmodel andgreen wireor green wire with
yellow ribbon wireis used.
7) After havingcompletedtheinstallation, make surethewiring is correct.
8) Please installthe leak currentprotectivebreaker at the output power
distributionpaneloftheUPS if necessary.
9) To connect the load with theUPS, please turn off all theloads first,then
performtheconnection andfinallyturnonthe loads oneby one.
10) Nomatter the UPS is connected tothe utilitypoweror not, theoutput
oftheUPS may haveelectricity. The partsinside the unitmaystillhave
hazardous voltage after turningoff theUPS. To makethe UPS have no
output, poweroff the UPS, andthen disconnectthe utilitypower supply.
11) Suggest charging the batteriesfor 8hours before use. After connection,
turn theinput breaker inthe “ON” position,the UPS willcharge the
batteries automatically. Youcanalsousethe UPSimmediately without
chargingthe batteries first, but the backuptimemaybe lessthanthe
standardvalue.
11
12) If it is necessary toconnect the inductanceloadsuch as amonitorora
laser printer tothe UPS, the start-uppower shouldbe used for
calculatingthe capacityoftheUPS, as its start-uppowerconsumption
is too bigwhen it is started.
Input and Output TerminalBlock wiringdiagram of 6K(S) 10K(S)
InputandOutputTerminal Block wiringdiagram of
3C10KS/3C12KS/3C15KS/3C20KS
3.3Operatingprocedureforconnecting the longbackup time
model UPSwith the external battery
3.3.1.The nominal DC voltageof external batterypack is192VDC. Each
batterypack consists of 16 pieces of12V”maintenance-free” batteriesin
series. To achievelonger backuptime, itispossibletoconnect
multi-batterypacks, butthe principle of “same voltage, same type” should
be strictlyfollowed.
3.3.2.For6KS/10KS/3C10KS/3C12KS/3C15KS/3C20KS,Theprocedure of
installingbatterybank shouldbecomplied withstrictly.Otherwiseyou
mayencounter the hazardousof electric shock.

12
1) ADC breakermustbe connectedbetween the batterypack and the
UPS. The capacityof breaker must benotlessthanthedata specified
in the general specification as follow.
Model
6K6KS10K10KS 3C10KS3C12KS 3C15KS3C20KS
Battery
voltage
192VDC
192VDC
192VDC
192VDC
240VDC 240VDC 240VDC 240VDC
Battery
current
34Amax
34Amax
56Amax
56Amax
46Amax. 56Amax.
70Amax. 102Amax.
Note:240VDC battery voltagecan be choose for 6K(S)/10K(S).
2) Setthe batterypackbreaker in“OFF” positionandconnect the16
pieces of batteries inseries.
3.3.3. To completetheconnectionbypluggingthe connector of the external
batterycableintothe external battery socket oftheUPS. Do notattempt to
connectany loads to theUPS now. Youshouldconnectthe inputpower
wire tothe rightposition first.And then set thebreaker ofthebattery pack
in the“ON” position. After thatset the inputbreaker inthe “ON”position.
TheUPS begins to chargethebattery packs at thetime.
3.4Parallel operation
3.4.1. Briefintroduction of the redundancy
N+X iscurrentlythe most reliable powersupply structure.Nrepresentsthe
minimumUPS numberthat the total loadneeds; X represents the redundant
UPS number,i.e. thefault UPS numberthatthe systemcanhandle
simultaneously.Thebigger theXis, thehigher reliabilityofthe power
systemis. For occasions wherereliability ishighlyrequired, N+X is the
optimalmode.As long as theUPS isequippedwith parallel cables, upto3
of themcanbeconnectedin paralleltorealizeoutputpower sharingand
power redundancy.
3.4.2. Parallelinstallation
1) Users need toopt astandard 25-pin communicationcable,which should
have25 cores, corresponding stitches and shield, asthe UPS parallel cable.
Thelength of the parallel cableis appropriate to beless than 3 m.
2) Strictlyfollowthestand-alone wiring requirementtoperformthe input
wiringof each UPS.
13
3) Connecttheoutputwires of each UPS toanoutputbreakerpanelfirst,
and then connect the wiringto theloadviathebreakerpanel.
4) Theparallel UPS mustbeequippedwithbatteryindividually.
5) Pleaserefer thefigurefollowedto see the wiring of paralleloperation.
The capacityof thebreakermustbenotlessthanthe specification as
follow. Model No. Capacityofbreaker
6K(S) 40A/250VAC
10K(S)/3C10KS 60A/250VAC
3C15KS/3C20KS 100A/250VAC
*The requirement of theoutputwiringis as follows:
●When the distancebetween theUPSsin paralleland the breakerpanel is
less than20 meters, the difference betweenthe wires ofinput &output
oftheUPSs is required to be lessthan20%;
●When the distancebetween theUPSsin paralleland the breaker panel is
greater than 20 meters, thedifference betweenthewires of input&
output of the UPSs is required to be less than 10%.
3.4.3. Operation and maintenance
1) To performthe generaloperation, follow thestand-aloneoperating
requirement;
2) Startup: Theunits transfer to INV mode simultaneouslyas they startup
sequentially in utilitypower mode;
Shutdown:theunitsshutdown sequentiallyinINV mode.When the last
onecompletes theshutdown action,each unit willshut down the inverter
simultaneouslyandtransferto bypass mode.
3) Toperform themaintenance, follow the stand-alonerequirement.

14
15

16
4. OperationandOperatingmode
It is easyto operate the equipment, withnoprevioustraining. Youjust need
to read throughthismanualand operateaccording tothe instructions init.
Themeaningof the LED indicators,please refer to theappendix 1 “Display
panel”.
4.1Operation
4.1.1. Turn on the UPS with utility power supplied
1) After you make sure thatthepower supplyconnection iscorrect,setthe
inputbreaker in the“ON” positionfirst. At this time thefan rotates and
theUPS suppliespowertotheload via thebypass. TheUPS operatesin
Bypass mode.
2) To power onthe UPS bysimplypressingthe “ON”button continuously
for morethan 1 second.
3) When beingpoweredon, theUPS willperformself-diagnosis, withthe
load/batterylevelLEDsturned on and then off one afteranotherin
ascendingorder. Afewsecondslater, the INV LED is turnedon, the
UPS is alreadyrunningin UtilityPower mode.If the utilitypoweris
abnormal, theUPS will operate in batterymodewithoutoutput
interruption of theUPS.
4.1.2. Turn on the UPS with no utilitypower supplied
1) Press the “ON”buttoncontinuously formore than 1 secondtopoweron
theUPS. For longback up time model(“L” model), please makesure
thatthe batterybreaker is in“ON”position.
2) Duringthecourseof starting up, the UPS has thesameaction as ifitis
connected to utility powerexceptthat the utility power LED is notturned
onand thebattery LED is turned on instead.
4.1.3. Turn offtheUPS with utility powersupplied
1) Press the“OFF” buttoncontinuously formore than1second toturn off
the inverter of the UPS immediately.
2) When beingpowered off, the UPS will perform self-diagnosis, the
Load/Batterylevel LEDswill be turned on andthen off one afteranother
in ascending order, then theINV LED will be turned off and Bypass
17
LED willbeturnedon. TheUPS is workinginBypass mode.
3) Uponcompletionoftheabove toturn it off,output ofelectric current of
theUPS is stillpresent. In order to cutoff the output from theUPS,
simplycut off the utility power supplyand theUPS willperform
self-diagnosis, finallynot anydisplayis shown onthedisplaypanel and
novoltageoutputis availablefromtheUPS output.
4.1.4. Turn offtheUPS with no utility powersupplied
1) Press the “OFF” buttoncontinuouslyformore than1secondto power
offthe UPS.
2) When beingpowered off, the UPS will perform self-diagnosis, the
Load/BatterylevelLEDswill be turned onandthenoff oneafter
another in ascendingorder. Finally notanydisplay is shownonthe
display panel and no voltage is availablefrom theUPS output.
Suggestions:
Please turn offtheconnectedloads beforeturning on the UPS and turnon
the loadsone byone after theUPSis workinginINVmode. Turn offallof
the connected loads before turning offthe UPS.
4.2Operatingmode
4.2.1. Normal powermode
In thenormalmode,thedisplayonthe frontpanelis shownin the
followingdiagram. The utility powerindicatorandthe Inverter indicator
are turnon.
Theload/batterycapacity indicator willbe turnedonin accordance withthe
load capacity connected.
1. If theutilitypower indicator blinks, itindicates that thereareproblems
with reversedpolarity(L,N)of sitewiring ordisconnect with ground
thatmayresultinshockhazard. UPS is stillworkinginnormalmode.If
thebattery indicatoristurnon at thesametime,itshows that thevoltage
orfrequencyoftheutilitypower is out of the normal inputrangeof the
UPS. The UPS works in batterymode.

18
Figure 4-1 NormalMode
2. If outputoverloaded, theloadlevel indicators will beturned onand
alarm willbeepeverysecond. Youshouldget rid ofsomeunnecessary
loadsone byonetodecrease theloads connectedtotheUPS less than
95% capacityof theUPS.
3. If the batteryindicatorblinks, itindicates thatnobattery isconnectedto
theUPS or battery voltageistoo low. Youshould checkifbatteryis
properly connected tothe UPS, and press function buttonmore than 5
seconds tostartthebatteryself-diagnosis. Iftheconnection between
batteryand UPS isconfirmed withoutanyproblem, it maybeduetothe
defector aging ofthe battery,please refer to the “troubleshooting”in
chapter 7 to solvetheproblem accordingly.
Note:Connection tothepowergenerator should bemade according to the
followingsteps:
lActivatethe powergenerator and waituntilthe operationis stable
beforeconnectingthe outputof the power generator tothe UPS(be
sure thatthe UPS is inidle mode). Then,turnontheUPS according to
thestartup procedure. Afterthe UPSis turned on,the loads are
connected one byone.
lItrecommended thatthe capacityofthe AC generator chosen should
doublethat ofthe UPS.
4.2.2Batterymode
In batterymodethe display on thefront panel isshown inthe following
diagram. Thebatteryindicator and theinverter indicator are turnon. If the
19
utility powerindicator blinksat the sametime, itshows that the utility
power isabnormal.The load/batterycapacity indicators willbe turn onin
accordance with the batterycapacity.Please notethat the load/battery
capacityindicator innormal modewillindicate thebatterycapacityin
batterymode.
1. Whenthe ups is runninginbatterymode,thealarmwillbeepevery4
seconds. If the “Function”keyispressed formorethan 5seconds, the
alarm willnot beep (silence function). Press the “Function”keymore
than5seconds againto resume the alarm function.
Figure4-2 BatteryMode
2. When the batterycapacitydecreases, thenumber of load/batterycapacity
indicatorsturned on willdecrease. If thebattery voltagedrops tothe
pre-alarm level(capableofmaintainingthe backup timeformore than 2
minutes), the alarm willbeepeverysecondto remind the userof
insufficient battery capacity.
4.2.3Bypass mode
Whenoperatinginbypass modesetup throughUPSilonsoftware,the
displayon the frontpanelisshow inthefollowingdiagram. The utility
power indicatorandthebypass indicator are turnon. Theload/battery
capacityindicatorwillbe turnedoninaccordancewiththeload capacity
connected.
1. If the utilitypowerindicator blinks, itshows thatthe voltageor
frequencyofthe utilitypowerisout of the inputrangeof theUPS or
thereareproblems with reversed polarity (L/N) of site wiringor

20
disconnectto the ground for protection.
2. When operatinginbypass mode,the UPSbeepsevery2minutes, If the
“Function” keyis pressed formorethan5seconds, the alarmwillnot
beep(silencefunction).Press the “Function” keymore than5seconds
again toresumethealarmfunction.
Notes: Whenoperatinginbypass mode, the backup function ofthe UPS is
notavailable and the power used by the loadis directly from the utility
powervia internal EMI filter.
Figure 4-3 Bypass Mode
4.2.4. Abnormalitymode
In casethe faultLED is turned on when the UPS is in use, it showsthat the
UPS is operating in abnormalmode. Please referto the troubleshooting in
section 7 for details.
4.2.5. Backup timefor the standard model
Thebackup timeof the longbackuptimemodel isdependent on the
external batterypackcapacityandtheloadlevelas wellas other factors.
Thebackup timeof standardmodelmay varyfrom differentmodelsand
load level.
Please refer to thefollowing:
21
4.2.6. Internet Communication
This seriesis equippedwithan intelligent slotforWeb power (optional
accessory)or otheroptional card to achieveremotemanagementof the
UPS. Please contactyour local distributorfor furtherinformation.
4.2.7. Description ofcommunication interface
1) Thestandard RS232 port is applicable to communicate with computer.
Description andpin assignment of RS232
Baud rate: 2400bps
Databit:8 bit
Endingbit: 1bit
Parity bit:None
DB-9pin assignment:
RS232 Interface

22
PinnumberFunction descriptionI/O
3Rxd Input
2Txd Output
5GND Ground
2) User enables tomonitorand managethe UPSthroughinstalled the
AS400 card(optional).
PIN1:UPS failure(normally open, activeclose)
PIN2:summary alarm
PIN3:ground
PIN4:Remoteshutdown
PIN5:Common
PIN6:Bypass active (relay close)
PIN7:Batterylow
PIN8:UPS On (relayclose)
PIN9:UtilityPower failure (normally open, active close)
AS400 Interface
23
5. Batterymaintenance
●Thisseries UPS onlyrequires minimal maintenance. The batteryusedfor
standard modelsis valveregulatedsealed lead-acidmaintenancefree
battery. These modelsrequire minimal repairs. The only requirementis to
chargetheUPS regularlyinorder tomaximizetheexpected lifeof the
battery. When beingconnectedtotheutilitypower, whether theUPS is
turned onor not,the UPS keepschargingthe batteries andalso offers the
protective function of overchargingandover discharging.
●The UPS shouldbecharged onceevery 4to 6months if it has not been
used foralongtime. In theregions of hot climates, the battery should be
chargedanddischarged every 2months. The standard chargingtime
should be at least 12 hours.
●Undernormal conditions, the batterylife lasts 3to5years. In caseifthe
batteryis foundnot in good condition,earlierreplacement shouldbemade.
Battery replaceevent should beperformed byqualifiedpersonnel.
●Replace batteries withthesame numberand same type of batteries.
●Keep the ambienttemperature between 15 and 25
●Donotreplacethebatteryindividually.Allthe batteries shouldbe
replacedat the sametimefollowingtheinstructions of the battery
supplier.
●Normally,the batteriesshouldbechargedanddischargedonce every 4to
6months. Chargingshould beginafter the UPS shuts down automatically
inthe course of discharging, the standard chargingtimeforthe standard
UPS should be at least12hours. Discharge the batterywith theload more
than 50%.

24
6. Notesfor batterydisposal and battery replacement
1) Beforedisposing batteries, remove conductivearticles such as necklace,
wrist watches and rings.
2) If it isnecessaryto replaceanyconnection cables, please purchasethe
original materials from the authorized distributors or service centers, so
as to avoid overheat or spark resultingin fire duetoinsufficient capacity.
3) Do notdispose of batteries or batterypacks ina fire, they may explode.
4) Donotopenor mutilate batteries, releasedelectrolyte is highly
poisonous andharmfulto the skinand eyes.
5) Do notshort thepositiveand negativeelectrodes ofthe battery,
otherwise, it mayresultin electricshock or fire.
6) Makesure that there is no voltagebeforetouching the batteries. The
batterycircuitisnot isolated from theinputpotential circuit.There may
be hazardousvoltage between the batteryterminals and the ground.
7) Eventhoughtheinputbreakerisdisconnected,thecomponentsinside
theUPS are stillconnectedwiththebatteries, andtherearepotential
hazardous voltages. Therefore,beforeanymaintenance andrepairswork
is carried out, switch off thebreakerof the batterypackordisconnectthe
jumperwireof connectingbetween thebatteries.
8) Batteriescontain hazardous voltageandcurrent.Battery maintenance
such as the batteryreplacementmust be carried out byqualified
personnelwho are knowledgeableabout batteries. Noother persons
shouldhandlethebatteries.
25
7.Troubleshooting
Problem Possiblecause Solution
The 1#Fault LED
and the 6 #LED are
turned on, the buzzer
beeps continuously
The UPS
shutdowndue to
internal overheat
Make sure the UPS is not
overloaded; the air vents are not
blocked andthe ambient
temperature is not toohigh. Wait
for10 minutes for the UPS tocool
down before turningon again.If
failed, please contact the distributor
orservice center.
The 1#Fault LED
and the 2#and5#
LED are turned on,
and the buzzer beeps
continuously
The UPS output
is Short circuited.
Turnoff the UPS. Remove all the
loads. Ensure that the loadis not
failed or the UPS has nointernal
faults before turningit on again. If
failed, please contact the
distributororservice center.
The 1# Fault LED
and the 4#LED are
turned on, the UPS
beeps continuously
The UPS shuts
downdue to its
internal fault.
Please contact the distributoror
service center.
The 1#Fault LED
and the 5# LED are
turned on, the UPS
beeps continuously
The UPS shuts
down due toits
internal fault.
Please contact thedistributoror
service center.
The utilitypower
LED flashes
The voltage or
frequencyofthe
utilitypower is
out of the input
range of the
UPS.
The UPS is running in battery
mode. Tosaveyour data andclose
the application program. Make
sure the utilitypower is within the
inputvoltageor frequencyrange
permitted bythe UPS.
The 1#Fault LED
and the 2#LED are
turned on, the UPS
beeps continuously
The UPS is
overloaded or the
load equipment is
faulty
Check the loads andremove all no
critical equipment. Recalculate the
loadpower and reduce thenumber
of loads connectedtothe UPS.
Checkthat the loads are not failed.
The 1#Fault LED
andthe batteryLED
are turned on, the
buzzer beeps every
second
The charger of
the UPS is
defective.
Please contact thedistributoror
service center.

26
7.Troubleshooting
Problem Possible cause Solution
BatteryLED flashes Batterylow
Checkthe battery.If the
batteryis damaged, replace
the batteryimmediatelyand
ensure that the batterybreaker
is in “ON” position.
The utilitypower is
normal, but the UPS
cannot turninline
mode
AC input breaker in
“OFF” position Set the input breaker in“ON”
position
Batterynotyet been
fullycharged
Keep UPS connectedto utility
power persistentlyformore
than 10hours torecharge the
batteries again.
UPS overloaded Check the loads and remove
the non-critical equipment.
Batterydischarging
time diminishes
Batteryaged
Replace thebatteries. Please
contact the distributorto
obtainthe parts and
replacement service.
The “ON” buttonis
pressed toobriefly Press the “ON” buttonfor
more than1second.
The UPS is not
connectedtothe
batteryorthe battery
packvoltage is toolow.
Check the batteryor recharge
the battery.
The UPS cannot
power on after
pressingthe “ON”
button
UPS internal fault Please connect the distributor
orservice center.
Whenyoucontactthe service center, please providethe following
information:
●Model No. and theserialNo. of theUPS;
●The datewhen the problem arose;
●Complete descriptionof the problem,includingtheLEDdisplay, alarm
warning,powercondition andloadcapacity.IfyourUPS is along
backup timemodel, you mayalso provide the batteryinformation.
27
Appendix 1 Description of Display panel
1. ON button:
Pressingthe ON/OFF buttonmorethan1second, the UPS system is turned
on.
2. OFF button:
Bypressingthisbutton more than 1second turns off theUPS system
whenever theUPS run under the normal mode/battery mode.
3. Functionbutton
TheFunction buttonprovides thefollowing functions:
1) Batteryself- diagnosis: When the UPS ran innormal mode, pressingthis
button more than 5seconds (buzzerbeepstwice)canstartthe battery
self-diagnosis.
2) Silence function in battery/bypass mode
In battery/bypassmode, when the buzzer beeps, pressingand holding the
functionbuttonfor more than 5seconds (buzzer beeps onetimes) can
silence the buzzer. Press the buttonformore than5seconds(buzzer
beeps twice) again toresumethealarm function.
Note: Thealarm silencingfunction of theFunction buttonisvalidonlyin
battery mode, and invalidfor any other UPS alarm.
4. LED indicators
The LEDscontains Faultindicator, Load/batterycapacity indicator,
Bypassindicator,utilitypower indicator, Inverter indicator, Battery
indicator.

28
Appendix 1 Description of Display panel
Table Appendix 1 Descriptionofindicators
No. Color Indicator Description
1# Red Fault indicator When theindicator on, it shows that
the UPS in abnormal condition.
2# Orange Load/batterycapacityindicator
3# Green Load/batterycapacityindicator
4# Green Load/batterycapacityindicator
5# Green Load/batterycapacityindicator
6# Green Load/batterycapacityindicator
Show the capacityof load/battery:
1.Indicate the percentageof the load
capacityinnormalmode and bypass
mode
2.Indicate the batterycapacitylevel in
batterymode.
7# Orange Bypass indicator When theindicator on, it shows that
the loading current is supplied from the
utilitypower directly
8# Green Utilitypowerindicator When theindicator on, it shows that
the utilitypoweris normal.
9#Green Inverter indicator When theindicator on, it shows that
the load current is supplied fromutility
poweror batteryviathe inverter.
10# Orange Batteryindicator When theindicator on, it shows that
the load current is supplied from
batteryviathe inverter.
29
Appendix2 Indicator andalarm
LED indicators
No. Operating status 1
# 2
# 3
# 4
# 5
# 6
# 7
# 8
# 9
# 10
# Audible alarm
10%--25%Load ●
●
●
none
226%--50%Load ●
●
●
●
none
351%--75%Load ●
●
●
●
●
none
4 76%--100%
Load ●
●
●
●
●
●
none
5
Normal
mode
101%--105%
Load ●
●
●
●
●
●
●
none
6 0~20%
batterycapacity ●
●
●Beeponce
everysec
7 21%~40%
batterycapacity ●
●
●
●Beeponce
every4sec.
8 41%~60%
batterycapacity ●
●
●
●
●Beeponce
every4sec.
9 61%~80%
batterycapacity ●
●
●
●
●
●Beeponce
every4sec.
10
Battery
mode
81%~100%
batterycapacity ●
●
●
●
●
●
●Beeponce
every4sec.
11Bypass mode ↑
↑
↑
↑
●
●
●
Beeponce
every2min.
12 Overloaded in Normal
mode ●
●
●
●
●
●
●
Beep twice
everysec
13 Overloadedin bypass
mode ●
●
●
●
●
●
●
Beep twice
everysec
14Utilitypowerabnormal ↑
↑
↑
↑
↑
↑
★
↑↑none
15Bypass mode abnormal ↑
↑
↑
↑
↑
★
↑
↑↑none
16 Overload inBatterymode,
pre-alarm ●
↑
↑
↑
↑
↑
●
●Beep twice
everysec
17Overload fault ●
●
↑
Sustained
beep
18 Overheatingfault ●
●
↑
↑
Sustained
beep
19Inverter fault ●
●
↑
↑
Sustained
beep
20Output short circuit ●
●
●
↑
Sustained
beep

30
LED indicators
No. Operating status 1
# 2
# 3
# 4
# 5
# 6
# 7
# 8
# 9
# 10
# Audible alarm
21 BUSvoltage fault ●
●
↑
↑
Sustained
beep
22Chargerorbatteryfault ●
↑
↑
Beeponce
everysec
23Fan failure ●
●
●
↑
↑
↑↑Beeponce
everysec
24Parallel fault ●
●
●
●
↑
↑
Sustained
beep
25ID repetition ●
●
●
↑
Sustained
beep
27 BAT voltage low ↑
↑
↑
↑
↑
↑
↑
↑
↑★Beeponce
everysec
28 Over Charger ●
●
↑
↑
↑↑Sustained
beep
29 Reversed polarity(L, N) of
input wiring or
disconnected with ground. ↑
↑
↑
↑
●
↑
★
↑↑Beeponce
everysec
30 BAT fault ●
●
●
↑
↑
Sustained
beep
31 EPO mode ↑
↑
↑
↑
↑
↑
Beeponce
everysec
32 Bus short ●
●
●
↑
↑
Sustained
beep
33Negtive power fault ●
●
●
●
↑
↑
Sustained
beep
34 React PowerFault ●
●
●
●
↑
↑
Sustained
beep
35 Power Fault ●
●
●
●
●
↑
Sustained
beep
36 Inv RlyStick Fault ●
●
●
↑
↑
Sustained
beep
37 InvRlyOpen Fault ●
●
●
↑
↑
Sustained
beep
38 Line SCR Fault ●
●
●
●
↑
↑
Sustained
beep
39Line In Fuse Open Fault ●
●
●
↑
↑
Sustained
beep
LED indictor description: ●:O n:Flash↑:Depending on otherconditions
31
8Chapter Operation(LCD model)
8.1OperationDisplay Panel
1. ON button:
Pressingthe ON buttonmore than1second(buzzer beepsonce), theUPS
systemisturned on.
2. OFF button:
Bypressingthis buttonmore than1second(buzzerbeepsonce) turns off
the UPS system whenevertheUPS rununderthenormal mode/battery
mode.
3. Functionbutton
TheFunction buttonprovides thefollowing functions:
a)Batteryself- diagnosis:When the UPS ran innormal mode,pressingthis
button more than 5seconds (buzzerbeepstwice)canstartthe battery
self-diagnosis.
b) Silence function in battery/bypass mode
In battery/bypassmode, when the buzzer beeps, pressingand holding the
functionbuttonfor more than 5seconds (buzzer beepstwo times) can
silence the buzzer. Press the buttonformore than5seconds(buzzer
beeps twice) again toresumethealarm function
c)LCD displayscreenswitch
Pressing the functionbuttonformore than 1 seconds (buzzer beeps once)
to switch LCD display screen
4. LED indicators
The LED indicators contains Fault indicator, Bypass indicator, utility
powerindicator, Inverter indicator, Batteryindicator.The definition of
each indicator is the sameasLED panel (refer totable Appendix 1).

32
8.2OperationMode
UPS OperationModecontains normal mode,battery modeand bypass
mode. Under thethree modes, the page showingoutputvoltageand output
frequencyis themaindisplaypage.If usersneed more informationabout
UPS, Pressingthefunctionbuttoncan initiatedisplayscreen switch.If the
currentpageis notthe mainpage,UPS will autoswitch back the main page
after30 seconds. Inorder to extendtheLCD usage life, the backlightwill
turnoff after1minutewithout any switch operation. Atthispoint, Users
justneed to touchanybutton briefly, the backlightwill beturn on.
8.2.1Normal mode
Whenoperatingin the normalmode, the display of mainpage on the front
panelis shown as the figure 8-2. The utilitypowerindicatorand the
Inverterindicator are turn on.Loadinformationareashows load value,and
the batterylevel areaindicates dynamicallywhen the batteryis notfull
charged(the batterylevel icons litoneafteranother circularly). When the
batteryisfullcharged, allthe levelicons are turn on.
1) Iftheutilitypowerindicator blinks, itindicatesthat thereare problems
with reversed polarity (L,N) ofsite wiringordisconnect with ground.
UPS is still workingin normal mode. If thebatteryindicator is turnonat
thesametime,itshows that the voltage or frequencyof theutility power
isoutof the normal inputrange of the UPS. TheUPSworks inbattery
mode.
Figure 8-2 NormalMode
33
2) Ifload ismorethan 105 percent,the buzzerbeepstwiceeverysecond,
meanwhile, the warningicon blinks every second too,remindingthat
you havebeen overloaded.You should get ridof some unnecessary loads
onebyoneto decreasethe loads untilthealarm clear
3) If the battery indicator blinks,itindicatesthat no battery is connectedto
theUPS or battery voltageistoo low. Youshould checkifbatteryis
properly connected tothe UPS, and press function buttonmore than 5
seconds tostartthebatteryself-diagnosis. Iftheconnection between
batteryand UPS isconfirmed withoutanyproblem, it maybeduetothe
defector aging ofthe battery,please refer to the “troubleshooting”in
chapter 7 to solvetheproblem accordingly.
4) Theother four displaypages are load percentpage, actual loadpage,
inputinformationpage andthemaximum temperaturepage.
Note:Connection tothepowergenerator should bemade according to the
followingsteps:
lActivatethe powergenerator and waituntilthe operationis stable
beforeconnectingthe outputof the power generator tothe UPS(be
sure thatthe UPS is inidle mode). Then,turnontheUPS according to
thestartup procedure. Afterthe UPSis turned on, the loads are
connected one byone.
lItrecommended thatthe capacityofthe AC generator chosen should
doublethat ofthe UPS.
8.2.2BatteryMode
Whenoperatingin the normalmode, the display of main pageon the front
panelisshown as the figure8-3.Thebattery indicatorand theInverter
indicator are turn on. If the utilitypower indicator blinks atthesametime,
itshows thatthe utility power is abnormal. Loadinformation areashows
load value, and bat level area showscurrent batterycapacity.
1) When the UPS is runninginbatterymode, the alarm will beep every4
seconds.If the “Function”keyis pressed formore than 5seconds,the
alarm will notbeep (silence function). Pressthe“Function”keymore
than 5 seconds again to resume the alarm function.

34
Figure8-3 BatteryMode
2) Whenthebattery capacitydecreases, thenumber of load/batterycapacity
indicators turnedonwill decrease.If the battery voltagedrops to the
pre-alarm level (capable of maintainingthebackup time for morethan2
minutes), thealarm willbeep everysecondto remindthe user of
insufficient battery capacity.
3) Theother four displaypages are load percentpage, actual loadpage,
batteryinformation pageand the maximum temperaturepage.
8.2.3Bypass Mode
Whenoperatinginbypassmodesetup throughUPSilonsoftware,the
displayonthe frontpanel is shown asthefigure 8-4, theutility power
indicator andthe bypass indicatorare turnon. The load/batterycapacity
indicator willbeturnedoninaccordancewiththe loadcapacity connected.
Loadinformationareashows load value, and the batterylevel area
indicatesdynamically when the batteryis not fullcharged(thebattery level
icons litone after another circularly). When thebatteryisfullcharged, all
the levelicons are turnon.
1) When operatinginbypass mode,theUPS beepsevery2minutes. If the
“Function” keyis pressed formorethan5seconds, the alarmwillnot
beep (silencefunction). Press the “Function” keymorethan 5seconds
again toresumethealarmfunction.
2) If theutilitypower indicator blinks, it shows that the voltageor
frequencyofthe utilitypowerisout of the inputrangeof theUPS or
thereareproblems with reversed polarity (L/N) of site wiringor
disconnectto the ground for protection.
35
3) Theother four displaypages are load percentpage, actual loadpage,
input information pageand the maximum temperaturepage.
Notes: Whenoperatinginbypass mode, the backup function ofthe UPS is
notavailable and thepower usedbytheload isdirectly from the
utilitypowervia internal EMI filter.
Figure 8-4 Bypass Mode
8.2.4LCD indication of UPS alarmstatus and faults
In the eventofanUPS fault,UPS enters faultoperationmode, at this point,
the faulticon turnon consistently,the buzzer beepscontinuouslyand the
data information areashows currentfaultcode(refer to table8.5-1), the
displayon the frontpanel isshown as the figure8-5.
Figure8-5Faultdisplay

36
When awarningoccurred,the fault icon blinkseverysecond, and users can
switchto thealarm display pageshown as the figure 8-6 tocheck the
warning code.
Figure 8-6 Alarmdisplay
8.3OperatingInstructions
8.3.1UPS ON/OFF Operation
Note
Thebatteryis fullychargedbefore delivery. However, storageand
transportation will inevitably cause somecharge loss.Therefore, it
isadvisable tochargethebatteryfor 10 hours before using it, so as
to ensure adequatebatteryautonomy.
1. Turning onthe UPS
Theoperation of turning on the UPS contains:turningon with utility power
and turning onwithout utilitypower.
1) Turningon with utilitypower:
Connect the mains input tothe UPS, press the ON button morethan one
second,UPS startto turnon. At this point,the LCDbegins toconduct
self-diagnosis (alltheLCDindicators are turn onabout4seconds).
Secondslater, the UPS willbeginto operatein Normal mode; meanwhile,
the utilitypowerindicator,inverterindicators will turnon. If the utility
power is abnormal, theUPS will work inbatterymode.
2) Turningon withoututility power:
With no mainsinputfeed to theUPS, press the ON buttonmore than one
second,ups starttoturn on, At this point,theLCD beginstoconduct
self-diagnosis (alltheLCDindicators are turn onabout4seconds).
Secondslater, thebatteryindicator, inverter indicators willbeturnon to
37
indicatethatthe UPS is workinginbatterymode.
2. PoweringdowntheUPS
Theoperationofpoweringdown the UPS contains: turningoff upsin
normal mode, turningoff ups in batterymode
1) Completelypower down theUPS from Normal mode
Holdandpress theOFF buttonpersistentlyformore than1secondto
power off theUPS. If itbasbeenset up toworkinbypass modeby
software, the bypass indicator will be turn on toindicatethat the UPS is
workinginbypass mode. In order tocut offthe outputfrom the UPS,
simplycut off the utilitypowersupply.LCD begins toconduct
self-diagnosis (alltheLCDindicators are turn onabout4seconds),
secondslater, notanydisplayis shown onthefrontpanel andno output
is available from the UPS outlets, systemcompletelypower down.
2) Completelypower down theUPS from Batterymode
Press the “OFF”button persistentlyfor morethan 1secondtopoweroff
the UPS. When beingpoweredoff,the LCD willstart self-diagnosis(all
the LCD indicators are turn onabout4seconds), seconds later,not any
displayis shownonthe frontpanelandno voltageoutputisavailable
from the UPS outlets, systemcompletely power down.
8.3.2Conducting Battery self-diagnosis
In UPS operation, users canmanuallyinitiatebatteryself-diagnosisto
check thebatteryconditions. There are two methods to initiatethe battery
self-diagnosis:
1. Through thefunction button
In normal mode, press andhold thefunctionformore than 5seconds
until the buzzer beeps twice.Atthis pointthe indicators (LED7~10)will
blinkcyclically,indicatingthe UPS has workedin battery mode andthe
batteryself-diagnosis has started. The batteryself-diagnosis willlastfor
5secondsdefault.In theevent of abatteryfaultduringbattery
self-diagnosis, theUPS will transfer to normal mode automatically.
2. Through themonitor software
Users canalso initiate batteryself-diagnosisthroughthebackground
monitoringsoftware.

38
8. 4Checking UPS function
Every time whenconductingfield maintenance, pleasecheck theregular
functionof theUPS, including:
1. Check theoperation status of the UPS
If themain voltage iswithinthespecifications, the UPS shouldoperate
innormal mode;ifthe mainvoltageisabnormal, the UPS shouldoperate
in battery mode. Inboth cases, there shouldbeno faultindication.
2. Check thetransfer between theUPS operation modes
Disconnectthe maininput tosimulateamains failure,theUPS should
transfer tobattery modeand operate normally; thenrecover the mains
input, the UPS should transfer to normal mode andoperate normally
3. Check theLED indicators of the UPS
Duringthecheck processes stated above,check that the LED indication
of the UPS agrees withthe UPS operation mode.
39
8Chapter Operation(LCD model)
8.5Troubleshooting
In the eventof anUPS fault,shootthe trouble accordingtoTable8.5-1. If
the fault stillpersists, please contact ourcustomer servicecenter.
Faults
Fault/
Warning
code Fault icon Alarm Possible
cause Solution
F01 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F02 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F03 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F05 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F06 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F07 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F08 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F10 on
constantly Beep
continuously
The UPS
output is
short
circuited
Turn offthe UPS. Remove
all loads.Ensure that the
loads arenot failed or the
UPShas no internal short
before turnon it again. If
failed, please contact the
distributor or service center
F17 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F21 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F25 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F26 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F29 on
constantly Beep
continuously Internal
fault. Please contact thedistributor
or Service center
F32 on
constantly Beep
continuously parallel line
loss Please check parallel line
connect or not.
Other manuals for ZS110
1
Table of contents
Other Gtec UPS manuals
Popular UPS manuals by other brands

Salicru
Salicru SLC-700-TWIN PRO quick start guide

Vertiv
Vertiv Liebert ITA2 user manual

Huawei
Huawei UPS5000-E Series user manual

Xtreme Power Conversion
Xtreme Power Conversion A60 Standby User & installation manual

Online
Online USV XANTO quick start guide

INFOSEC UPS SYSTEM
INFOSEC UPS SYSTEM S5 USB NEO user guide

Eaton
Eaton EX 2200 RT 2U Installation and user manual

Niveo Professional
Niveo Professional NUPS23-1500 user guide

Gewiss
Gewiss GW81761 Installation and user manual

Altronix
Altronix RESERV ReServ5WP installation guide

Pioneer
Pioneer DreamBook Solar UPS Battery Bag user manual

Power Solid
Power Solid PS-PGU1500VA#2B9A user manual