Hanbay M Series User manual

Page 1 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
MCx-xxxAx-8.09
(12-24 VDC; 4-20 mA Control)
USER MANUAL
Contents
INSTALLATION 2
Mounting 2
Wiring 2
Power Supply and Current Draw 3
Control Signal and Feedback 3
OPERATION 4
DIP switches 4
Controlling the Actuator 4
Changing the number of turns 5
Torque Settings 6
Speed and Torque Details 6
Signal Loss and Calibration 8
Troubleshooting 9
ACTUATOR DIMENSIONS 10
PART NUMBER BREAKDOWN 12
LABEL BREAKDOWN 13

User Manual MCx-xxxAx-8.09
Page 2 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
INSTALLATION
Mounting
In most cases, the actuator must be mounted
and supported as shown in the image to the
right. The mounting bracket is not supplied by
Hanbay.
Exceptionally, the actuator may be suspended
on the tubing itself but ONLY if the application is
vibration free and the tubing is minimum ¼” dia.
stainless.
Wiring
The actuator comes standard with a Turck 5 position connector and a 20’ cable with plug. Cut the cable to
the length required and then connect according to the following wire color schematic:
Wire color schematic for “Turck5” cable:
If the Turck cable is not included in your actuator, connect the wires to the corresponding pins on the
terminal block as indicated in the schematic:
Pin
Colour
Function
6
White
+24 VDC
5
Black
Power Gnd.
4
Grey
Output Signal (4-20 mA)*
3
Not connected
2
Brown
Isolated** Input Signal Gnd.
1
Blue
Isolated** Input + Signal (4-20 mA)
* “feedback” available in MCx-Lx-xxxAFversion of actuator only.
** “isolated” available in MCx-Lx-xxxAIand xxxAFversions of actuator only.
Terminal
1 2 3 4 5 6
Remove R66 to
convert from 4-20 mA
to 1-5 V input signal
Mounting
Bracket
Cable Entry

User Manual MCx-xxxAx-8.09
Page 3 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Power Supply and Current Draw
The MCx-Lx-xxxAx may be connected to voltages ranging within 12-24 VDC.
The current draw will range from minimum 100 mA to maximum 3 A while the actuator is active. When not
moving, the actuator draws approx. 50 mA.
Control Signal and Feedback
Locate the correct connection terminals/wires as shown on the previous page, then connect your input signal
on positions 1 and 2 (blue and brown wires) as shown below. Feedback, if applicable is connected to
position 4 (grey wire).
Note: Digital potentiometer functionality is disabled for supply voltages below 18 VDC, so the
actuator position will not be retained on power-loss, on power-up the actuator will need to be
re-zeroed every time.
1 2 3 4 5 6
P1
4-20 mA Signal source,
user powered
-
+
Actuator
MCx-xxxAx
Internal
RES
R66
NOTE 1: Usually, the actuators are
shipped for 4-20 mA signal input.
For 1-5 V signal input, remove 250
ohm resistor R66.
The actuator 4-20 mA output is internally supplying the signal current and can drive sufficient voltage for
any sensing resistor of up to 250 ohms.
The potential of the external GND after the sensing resistor may not be more than +6 VDC / -2 VDC away
from the power GND of the actuator.
This feedback signal output is only available in HANBAY MCx-xxxAF model actuators.
External
4-20 mA
Sensing
resistor
NC
NOTE 3: DO NOT CONNECT pin 4
directly or through a multimeter only to
ground.
A sensing resistor of 50 ohms or more
needs to be present.
Not observing this warning will damage
the equipment.
NOTE 2: Signal gnd. is NOT ISOLATED
from power gnd. in all MCx-xxxAB basic
models.
If your signal gnd. is different from power
gnd. use HANBAY MCx-xxxAI or MCx-
xxxAF model actuators.

User Manual MCx-xxxAx-8.09
Page 4 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
OPERATION
DIP switches
The DIP switches allow you to change the
settings on your actuator. To flip a switch,
gently use a small flat-head screwdriver.
See the table below for DIP switch functionality.
DIP
Function
1
2
Speed: Choose how quickly the actuator will turn the drive wheel. See p.6.
3
Only in the ON position for actuator model MCH (with external gear stage).
4
5
6
7
8
Turns: The actuator usually ships from the factory with the recommended number of turns for the
valve. However, this number can be changed. Turning on a switch will add a specific number of
turns to the actuator’s movement.
See p.6 for relation between positions of the DIP switches and number of turns.
Example: Turning on DIP 6 adds four turns, turning on DIP 8 adds one turn. If both DIP 6 and 8 are
on, then the total turns of the actuator would be five.
9
Signal loss: See p.7
10
11
Seating torque: Set how much torque the actuator exerts on the valve lever during the calibration
(finding valve seat) procedure. See p.6
12
Direction/Calibration: Toggle switch on and off while powered to re-calibrate actuator (find valve
seat). Also sets direction in which the actuator will open and close. See p.7
Example: The MCM model actuator turns clockwise when the signal is decreased with DIP 12 in the
OFF position. Putting DIP 12 in the ON position will cause counterclockwise turning for a decrease
in signal. For changes in DIP 12 position to take effect, the power to the actuator must be cycled.
Controlling the Actuator
The 4-20 mA (or 1-5 V / 1-10 V) input signal represents a total span of a number of turns.
I.e.: If you set the number of turns to 2, then a signal of 12 mA will set the actuator to exactly 1 turn from the
fully closed position. 15 mA will give: (15-4)/16=0.6875 ⇒68.75% of 2 turns ⇒1.375 turns from closed.
In this example DIPs 1, 2, 5 and 12 are on.

User Manual MCx-xxxAx-8.09
Page 5 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Changing the number of turns
With the DIP switch settings, you can adjust anything between 1 and 31 turns to represent the full signal
range of 4-20 mA. Check in the table below. (1 = “On”, 0 = “Off”)
Total Turns
Dip4=0
DIP 5
DIP 6
DIP 7
DIP 8
reserved
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
WARNING: Be sure that the number of turns the actuator is set for is LESS than the number of
turns for the valve. The actuator should not stop itself on a fully opened valve. It can damage the
valve, and the actuator will lose its position.
For more turns, set DIP 4 to the ON position.
This will add 16 turns to the number set by
DIPs 5 through 8, as shown in the table.
DIP 4=0
+0 turns
DIP 4=1
+16 turns

User Manual MCx-xxxAx-8.09
Page 6 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Torque Settings
To accommodate different valves and other applications with
different torque requirements, the actuator can be set to apply
different torque on the valve stem when in the seating mode.
During normal operation, the actuator will try to reach the speed
set by DIP 1 and DIP 2. It will use 100% torque to try and reach
the selected speed, regardless of the positions of DIP 10 and DIP
11. Current draw is limited to 3 A regardless of settings.
Please see the box to the right and the tables below to select the
power setting that is right for your application.
To deal with sticking valves, at the beginning of the first reversing movement after the seating (“zeroing”) of
the valve, the actuator will apply double the power set by DIP 10 and DIP 11 (up to 100% power.)
This “pull out” function is always enabled.
Speed and Torque Details
The maximum speed of the actuator can be set by using the first two positions of the DIP switch selector.
As a result of this setting, the actuator will limit the maximum speed. The tables below show the time required
to complete one turn.
The seating torque depends on the voltage provided in the power connection and on the
seating power settings on DIP 10, 11 as shown below.
MCL-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque (in-lbs)
Operating
torque is
100%
12VDC
24VDC
OFF
OFF
7
OFF
OFF
6
12
OFF
ON
3
OFF
ON
10
20
ON
OFF
2
ON
OFF
19
38
ON
ON
1
ON
ON
24
48
NOTE: If actuator is MCJ-xxxAx, divide torque values by 3.
To convert in-lbs to Nm, divide by 9.
Seating power settings:
(when operating at 24 VDC)
DIP 10
DIP 11
Power
OFF
OFF
16%
OFF
ON
33%
ON
OFF
66%
ON
ON
100%
WARNING: High power settings can supply enough torque to damage your valve.
Please be cautious, especially when using the 100% power setting.
Note: 66% setting and 100% setting require voltage supply minimum values as follows:
-Supply voltage needs to be min 14 VDC for 66% setting
-Supply voltage needs to be 16 VDC for 100% setting
-When operating above 20 VDC and 66% power, Duty cycle is reduced to 50% - 25%
maximum. At these levels, the electronics produce more heat which must be dissipated
(depending on environmental temperature)

User Manual MCx-xxxAx-8.09
Page 7 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
MCM-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque (in-lbs)
Operating
torque is
100%
12VDC
24VDC
OFF
OFF
23
OFF
OFF
17
35
OFF
ON
11
OFF
ON
30
60
ON
OFF
7
ON
OFF
55
115
ON
ON
4
ON
ON
70
145
NOTE: If actuator is MCK-xxxAx, divide torque values by 3.
To convert in-lbs to Nm, divide by 9.
MCH-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque (in-lbs)
Operating
torque is
100%
12VDC
24VDC
OFF
OFF
90
OFF
OFF
60
120
OFF
ON
45
OFF
ON
102
205
ON
OFF
30
ON
OFF
200
400
ON
ON
18
ON
ON
248
497
To convert in-lbs to Nm, divide by 9.
MCF-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque (in-lbs)
Operating
torque is
100%
12VDC
24VDC
OFF
OFF
161
OFF
OFF
115
230
OFF
ON
77
OFF
ON
190
380
ON
OFF
49
ON
OFF
360
720
ON
ON
28
ON
ON
457
915
To convert in-lbs to Nm, divide by 9.

User Manual MCx-xxxAx-8.09
Page 8 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Signal Loss and Calibration
1. For actuators that are not connected to a UPS (Uninterruptible Power Supply), the loss of signal
will be simultaneous with power loss. Consequently, the actuator will not be able to move anywhere.
In the shutdown process, the actual position is automatically saved to the internal EEPROM. [This
saving of the position only happens for min. 18 VDC supplies] When power is restored, the actuator
will “know” its location and will simply start to follow the signal as received.
IF YOU HAVE TO turn the actuator manually when its power is turned off, it will lose its
position, and it will need to be re-zeroed (as described in sub-section 3)
2. For actuators that are connected to a UPS the behavior on signal loss can be set as follows:
Normal position of DIP 9: OFF
With DIP 9 in the off position, the actuator will ignore the signal if it is lost (i.e.: if the signal falls below
0.700 V or 2.80 mA) and simply remain in its current position.
Note: if the sensing resistor R66 is removed (for 1-5 V input signals), we recommend placing a 10K
resistor between signal and signal GND.
Predetermined signal loss position DIP 9: ON
With DIP 9 in the on position, the actuator will move to a predetermined position when the signal is
lost (i.e.: if the signal falls below 2.80 mA or 0.700 V).
Setting of the predetermined signal loss position:
a.- turn DIP 9 to the “off” position
b.- re-zero the actuator by sending and holding an input signal between
2.80 and 4.16 mA (0.700 and 1.04 V) wait until the device is re-zeroed, (i.e.: valve is closed)
c.- by varying the input signal, move the actuator to the position that is going to be the
predetermined signal loss position.
d.- switch DIP 9 to the “on” position. The current actuator position will be saved as the default
signal loss position. (The default signal position is an absolute actuator position, not a signal
value.)
3. Re-zeroing the actuator and initiating calibration routine:
The actuator will re-zero when the input signal is between 2.80 and 4.16 mA (0.700 and 1.04 V). It
will turn clockwise until the actuator has reached the fully closed position of the valve.
If the valve is removed for any reason, the calibration routine must be initiated on the
actuator manually. This is done by toggling DIP 12 (switch position, then back to the original
position) while the actuator is powered. This will prevent damage to the valve.
If you need to re-zero in the opposite direction (i.e.: for pressure regulators, which typically go to
the “top” fully open position at 4 mA) change the setting of DIP 12 and cycle power.
4. Feedback calibration: [MCx-xxxAF model actuators only]
The current feedback will be calibrated from the factory.
To re-calibrate the feedback:
a.- Turn off the actuator and disconnect the feedback and input signals. If possible, remove the
actuator from the valve.
b.- Connect the feedback signal to the signal input. Also connect the power and signal grounds.
c.- Power up the actuator with this “signal loop-back” setup.
d.- Short SP1. It will automatically run a special routine to calibrate the feedback signal to the
signal input. The whole process takes about 1.5 seconds.
e.- turn off the power and reconnect the actuator as normal.

User Manual MCx-xxxAx-8.09
Page 9 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Troubleshooting
Upon noticing a problem, your first step should almost always be to recalibrate the actuator by toggling DIP
12 while the actuator is powered. This alone can solve the most basic problems. See sub-section 3 above for
more details.
If the actuator does not move, try following these steps:
1) Re-calibrate the actuator. This will move the actuator regardless of what signal it is receiving.
2) A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator.
3) Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate.
If the problem persists, please call Hanbay for technical support.

User Manual MCx-xxxAx-8.09
Page 13 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
LABEL BREAKDOWN
Actuator Series
M-Series or R-Series
Actuator Supply Voltage
12-24 VDC @ 3.0 A or
110-240 VAC @ 1.5A
Circuit Board Version
Ax-8.09
Dx-10.31
Dx-4.10 (Obsolete since 2019)
Px-10.3
Actuator Part Number
Refer to part number breakdown
for available options.
QR Code
Scan this QR code for a
direct link to the user
manual for your unit!
Actuator Serial Number
This serial number is unique for
each individual unit and is directly
tied to your order/invoice number.
Firmware Version
AF-1.05 MM = Multiturn
AB-1.05 MML = Multiturn Low Torque
AS-1.05 MMUL = Multiturn Extra Low Torque
QM = Quarter turn
QM97 = Quarter turn 97°
DT-2.01
DC-2.01
DT-4.06 (Obsolete since 2019)
M-Dx V2.31
This manual suits for next models
7
Table of contents
Other Hanbay Controllers manuals

Hanbay
Hanbay MC A 8.09 Series User manual

Hanbay
Hanbay MC-AS-1.05 Series User manual

Hanbay
Hanbay RD-AC Series User manual

Hanbay
Hanbay MC-B-A-8.09 Series User manual

Hanbay
Hanbay MD DT-10.31 Series User manual

Hanbay
Hanbay RC Series User manual

Hanbay
Hanbay MC DC-2.00 Series User manual

Hanbay
Hanbay RC AS-1.05 Series User manual

Hanbay
Hanbay RD-DT-10.31 Series User manual