HBX CPU-0600 User manual

HBX Control Systems Inc.
Installation Manual
CPU-0600
Version 1.0.0
CPU-0600

Page 2
Control Systems Inc.
Comfort
Control
Innovation
HBX CPU-0600 Control
Version 1.0.0.0
Table of Contents
TABLE OF CONTENTS
Introduction ............................................................................................ 1-3
Description .............................................................................................. 1
Safety Symbols & Warnings ................................................................... 2
Receipt & Inspection .............................................................................. 2
Technical Data and Dimensions ........................................................... 3
Wiring & Installation ............................................................................... 4-25
Wiring ....................................................................................................... 4
Installation ............................................................................................... 5
Main Screen Navigation.......................................................................... 6
Staging Mode Setup ..............................................................................6-14
Mixing Mode Setup .............................................................................. 15-24
Differential Setpoint Setup .................................................................... 25-28
Dual Setpoint Setup ............................................................................... 29-31
Pump Sequencer Setup ........................................................................ 32-34
Troubleshooting Guides...........................................................................48-50
Warranty Information .............................................................................. 51

HBX CPU-0600 Control
Version 1.0.0
Page 1
RELAYS
240VAC 5A Max
INPUT
120VAC 15A Max
ECO-0600
ZONE CONTROLLER
ECO-0600
GEOTHERMAL CONTROL
CPU-0600 INTRODUCTION
The CPU-0600 is designed to be a stand-alone Outdoor
Reset Control device. The purpose and function of the
CPU-0600 is to provide control for multiple applications. The
applications are selectable through a full touch screen display
on the programming interface and consist of Boiler, Mixing,
Differential Setpoint, Dual Setpoint and Pump Sequencer. The
CPU-0600 is a Wi-Fi enabled control that allows access through
the HBX Sensorlinx mobile app.
Boiler Control
The use of the CPU-0600 as a Boiler Control allows the
capability to run up to four (4) On/Off boilers, and three (3)
modulating boilers with DHW requirements. Expandability for
more stages is possible with additional CPU-0600 controllers.
Mixing Control
As a Mixing Control, the CPU-0600 has the capability to run
four (4) On/Off Boilers and three (3) modulating boiler. Mixing
types include Modulating Mixing, Floating Action Valve and
Injection Pump
Pump Sequencer
This control allows the system to sequence and cycle pumps,
override pumps and turn the pump off when the outdoor
temperature goes above a certain value (WWSD).
Differential Setpoint Control
The CPU-0600, when selected the control will allow to run a
temperature differential for a setpoint.
Dual Setpoint
This mode is for use when one or two independent setpoints
are needed in a system.
This control can also function as a stand alone system without WiFi
capabilities.
FEATURES
• Remote access for Apple® and
AndroidTM devices via Sensorlinx mobile
app
• Full-Colour touch screen display
• Control up to 4 on/off boiler stages per
controller
• Control up to 3 modulating boilers (0-10
VDC) per controller
• Expandable up to 16 on/off boiler
stages and/or 12 Modulating boilers.
• DHW control
• Boiler lead lag and rotation on time or
cycles
• Boiler and DHW differential
• Multiple pump control options (system,
boiler, DHW)
• Multiple mixing control options
(Injection, Mod, Floating)
• Outdoor temperature reset with WWSD

HBX CPU-0600 Control
Version 1.0.0
Page 2
Extreme Hazard
This action poses a serious threat that could result in
personal injury or death, as well as permanent damage to
the equipment. Proceed with caution.
EXTREME HAZARD: This HBX control is a microprocessor based controller and as such is not to be regarded as a safety (limit) control.
Please consult and install the heating or cooling appliance in accordance with the manufacturer’s recommendations.
Moderate Hazard
This action may cause personal injury or have adverse
effects on the installation process if handled incorrectly.
WARNING: Only suitably qualied individuals with formal training in electrical and hydronic controls should attempt the installation
of this equipment. Incorrect wiring and installation will affect the warranty provided with this unit. Wiring must be completed in
accordance with the codes and practices applicable to the jurisdiction for the actual installation.
WARNING: Non-serviceable product. Send to HBX Controls Inc. only for service.
WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer
and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
WARNING: a) Use copper conductors only if the terminal is acceptable only for connections to copper wire; b) Use aluminum
conductors only or use aluminum or copper-clad aluminum condctors only if the terminal is acceptable only for connection to
aluminum wire; or c) use copper or aluminum conductors or use copper, copper-clad aluminum, or aluminum conductors if the
terminal is acceptable for connection to either copper or aluminum wire.
WARNING: Use only copper conductor supply wire suitable for at least 105 °C
WARNING: All circuits must have a common disconnect and be connected to the same pole of the disconnect.
WARNING: Wiring connected in the bottom wiring chamber must be rated to at least 300V.
Disconnect Power Source
The presence of low voltage(24VAC) or high
voltage(120VAC) could result in personal injury or
permanent damage to components or equipment.
Point of Interest
This point claries pertinent information, or brings your
attention to an action that may have adverse effects on
the installation process.
Drawing Reference
Refer to the specied electrical or mechanical drawing at
the back of the manual.
SAFETY SYMBOLS
SAFETY WARNINGS
RECEIPT & INSPECTION
After receiving, inspect the unit for any possible physical damage that may have occurred during transportation.
After unpacking the unit make sure the box contains:
• 1 x Terminal Screwdriver (2.5 mm)
• 1 x Manual
• 1x Remote outdoor outdoor sensor (OUT-0100)
• 2x Universal Sensor (029-0022)
• 2x Cable ties

HBX CPU-0600 Control
Version 1.0.0
Page 3
131
mm
5.157”
248
mm
9.764”
66
mm
2.598”
3.937”
99.9
mm
222
mm
8.740”
RELAYS
240VAC 5A Max
INPUT
120VAC 15A Max
ZON-0600
ZONE CONTROLLER
ECO-0600
GEOTHERMAL CONTROL
65.96
mm
2.597”
Specications:
4 x thermistor Input (10k Ohm)
2 x Demand output relays 24VAC 2A
4 x Relay Outputs 240VAC 5A (Dry Contacts)
1x Input 120VAC +/- 10% 50/60Hz 15A Max
3 x Pump Relay 240VAC 5A
Combined relay power should not exceed 15A
Weight:
0.408Kg
Dimensions:
131mm W x 246mm H x 66.71mm
5.16in W x 9.83in H x 2.64in
ETL Listings:
Meets CSA C22.2 No. 24
Meets UL Standard 873
ETL Control No. 3068143
Storage:
50°F to 104°F (10ºC to 40ºC)
CPU-0600
WiFi: 2.4GHz Network Only
FCC ID: 2AHMRESP125
Torque: 0.3687811ft-lb
TECHNICAL DATA AND DIMENSIONS
TECHNICAL DATA AND DIMENSIONS
CPU-0600 TECHNICAL DATA
DIMENSIONS
RELAYS
240VAC 5A Max
INPUT
120VAC 15A Max
ECO-0600
ZONE CONTROLLER
ECO-0600
GEOTHERMAL CONTROL

HBX CPU-0600 Control
Version 1.0.0
Page 4
WIRING
We recommend all signal wiring to be a minimum of 18AWG shielded wire at a maximum of 500ft.
M
odulation Output 1
M
odulation Output 2
M
odulation Output 3
Heat Demand
DHW Demand
Sensor Inputs 1
Sensor Inputs 2
Staging Output 1
Staging Output 2
Staging Output 3
Staging Output 4
Supply Power 120 VAC
Pump Output 3
Pump Output 2
Pump Output 1
DO NOT CONNECT
POWER HERE
GR
POWER
120
17
N
L
1615
5A
1
Pump 1
9 10
1 2
Pump 2
11 12
2
5A
HBX CPU-0600 Central Processing Unit
0
8
7
I
HD
0
109
I
Demand
Inputs
1
1211
2
13
Sensor
Inputs
3
1514
4
16
Sensor
Inputs
21
1
43
2
65
3
Mod Staging
Ouput
4
STG 4
7 8
43
5 6
32
3 4
2
1
1 2
1
Staging Output
STG 3
STG 2STG 1
5A
3
Pump 3
13 14
3
CPU-0600
Input Power
DHW
Class 2 Circuits
Class 2 Circuits
WIRING AND INSTALLATION
CPU-0600 Installation
The CPU-0600 is designed to be wall mounted or installed in a separate electrical enclosure. The
unit should be installed inside and protected from falling water and high humidity conditions.
With all the covers in place, it is designed to protect any individual from accidental electrical
shock. It is not suitable for installation in hazardous locations and should not be close to any
electromagnetic elds.
• Identify the four mounting holes on the CPU-0600, mark on the wall the desired location of
mounting
• Pre-drill, anchor and fasten four screws for mounting
• Hang CPU-0600 and fasten tight to desired locations
• Complete wiring connections in accordance with terminal locations
MOUNTING
HOLES
2. DEMAND OUTPUTS
7,8: Demand signal 1: Apply a heat demand from a dry
contact or 24v
9,10: Demand signal 2: Used for DHW or setpoint demand
3. SENSOR INPUTS
11, 12: Boiler Temperature in Staging Mode. Setpoint 1
temperature in DiFF/Dual Setpoint Mode.
12, 13: System temperature in Mixing Mode. Setpoint 2
temperature in DiFF/Dual Setpoint mode.
14, 15: Outdoor temperature.
15, 16: Used for DHW tank temperature.
1. MODULATING OUTPUTS
1, 2: (0-10 VC) Can be used for a modulating boiler or valve
3, 4: (0-10 VDC) Can be used for a modulating boiler or valve
5, 6: (0-10 VDC) Can be used for a modulating boiler or valve
5. AUXILIARY OUTPUTS
9, 10: Aux 1 - Can be used as a system pump, Injection pump
11, 12: Aux 2 – Can be used as a system pump, DHW pump, Boiler
pump, Valve up
13, 14: Aux 3 - Can be used as a system pump, DHW pump, Boiler
pump, Valve down
6. INPUT POWER
15, 16, 17: 120 VAC +/- 10% 50/60Hz 15A Max
4. STAGING OUTPUTS
1, 2: Boiler Stage 1 (Primary) or Stage 5, 9, 13 (Secondary)
3, 4: Boiler Stage 2 (Primary) or Stage 6, 10, 14 (Secondary)
5, 6: Boiler Stage 3 (Primary) or Stage 7, 11, 15 (Secondary)
7, 9: Boiler Stage 4 (Primary) or Stage 8, 12, 16 (Secondary)

HBX CPU-0600 Control
Version 1.0.0
Page 5
CPU-0600 INSTALLATION
CONTROL MODE
The CPU-0600 is designed to be wall mounted or installed in a separate electrical enclosure. The unit should be
installed inside and protected from falling water and high humidity conditions. With all the covers in place, it is
designed to protect any individual from accidental electrical shock. It is not suitable for installation in hazardous
locations and should not be close to any electromagnetic elds.
• Identify the four mounting holes on the CPU-0600, mark on the wall the desired location of mounting
• Pre-drill, anchor and fasten four screws for mounting
• Hang CPU-0600 and fasten tight to desired locations
• Complete wiring connections in accordance with terminal locations
The programming instructions for the CPU-0600
are broken down into the ve control modes listed
below. When the control is rst plugged in you are
asked to select which control mode you would like
your CPU-0600 to operate in.
STAGING MODE (DEFAULT) – Programming for this
mode can be found on pages 6 through 14. This
mode is used when running boilers only. The boiler
congurations available in this mode are three
(3) modulating, On/Off boiler, two (2) stage On/
Off boiler, three (3) stage On/Off boiler and four
(4) On/Off boiler. Staging expandability is possible
with additional CPU-0600 controllers. In this mode
the control is able to control DHW and operate a
boiler, system, and DHW pump(s).
MIXING MODE – Programming for this mode can be found on pages 15 through 24. This mode is used when
running mixing pumps or valves. Mixing congurations include PMIp, Modulating, and Floating Action Valve. In
this mode the control can run up to four (4) on/ off boilers or three (3) mod boiler(s).
DIFFERENTIAL SETPOINT MODE – Programming for this mode can be found on pages 25 through 28. This mode
is used when running a differential setpoint. In differential mode, the control will also send a modulating signal
output based on how far the control is from the differential. This can be used to run a pump in modulating
applications for constant ow.
DUAL SETPOINT MODE – Programming for this mode can be found on pages 29 through 31. This mode is used
when one or two independent setpoints are needed. Each setpoint is set up individually and each has its own
thermistor input and relay outputs: Each setpoint has its own normally open and normally closed contacts
(which can be used for heating and/or cooling).
PUMP SEQUENCER MODE – Programming for this mode can be found on pages 32 through 34. This mode is used
to provide pump control for two pumps in a duty, standby situation. This control allows the system to sequence
and cycle pumps, override pumps and turn the pumps off when the outdoor temperature goes above a
certain value (WWSD)
In the event you select the wrong control mode, please cycle power to the
controller and it will display the control mode option screen.
SensorLinxTM Mobile App
The SensorlinxTM mobile app is available for Apple iOS (APP Store) and
Android® devices (Google Play). The mobile app allows for remote
monitoring and control for HBX Controls devices.
Now available on the Apple App Store and Google Play

HBX CPU-0600 Control
Version 1.0.0
Page 6
WI-FI – Indicates that the control is connected to a
2.4 GHz Wi-Fi network.
BOILER SUPPLY – Indicates the boiler supply
temperature and target. If there is a demand for
heating the box will be bordered with a red outline,
and the staging output(s) in the lower wiring
chamber will be closed.
BOILER RETURN – Indicates the boiler return
temperature.
OUTDOOR – The outdoor temperature will be
displayed. This option will also display if the control
is in WWSD (Warm Weather Shutdown).
DHW TANK – It will display the DHW temperature
and target. If there is a demand for DHW the zone
will be bordered with a red outline.
STAGES – Indicates how many boilers are being
utilized in your system setup. When a boiler is
activated by a heat demand the boiler will light up
in respect to their classication.
MODULATING STAGES – Indicates how many
modulating boilers are being utilized in your system
setup. When a modulating boiler is activated by a
heat demand the modulating boiler percentage
will start at the minimum mod percentage (%).
When there is no demand (off) the modulating
percentage (%) will displayed as 0%.
PUMPS – When a pump is activated by a call you
will see pump (P1) ,(P2), (P3) light up in respect to
their classication, their associated contacts PUMP
1, PUMP 2, PUMP 3 can be found in the lower wiring
chamber will be closed.
DEMANDS – When the delegated demand is active
it will light up (DEMAND 1 - HD) or (DEMAND 2 –
DHW/SETPOINT) thus in turn the associated demand
in the upper wiring chamber will be closed.
STAGING MODE: MAIN SCREEN
1
2
3
4
5
6
7
8
9
Accessing the menu of the CPU-0600 is done by pressing the menu button (3
lines) in the top right corner.

HBX CPU-0600 Control
Version 1.0.0
Page 7
The CPU-0600 allows for expandability for more boiler
staging between controllers. A maximum of four (4)
controllers can be utilized for a maximum of 16 boiler
stages. When using more than one CPU-0600, to allow
them to communicate wirelessly between each other,
they will need to follow a sequential order.
STAGE SEQUENCE SETUP – This setting will allow you to
select the stage sequence in your systems setup.
The rst sequence is labelled Primary and represents
sequence 1-4.
• Primary (Stages 1-4)
• Secondary (Stages 5-8) *CPU-0600 #2
• Secondary (Stages 9-12) *CPU-0600 #3
• Secondary (Stage 13-16) *CPU-0600 #4
CONTROL ID – If the Sequence was set to the Primary
then the number under Control ID will represent this
CPU-0600’s ID. If the CPU Sequence was set to any
sequence other than Primary, that CPU-0600’s Control
ID can be set to match the value of the Primary CPU-
0600 Control ID and the CPU-0600’s will then LINK
automatically. The CPU-0600’s will be LINKED when the
Sequence Link symbol appears on the top left of the
Main Screen for both controllers.
Control ID
Stage Sequence
STAGING MODE: STAGE SEQUENCE SETUP

HBX CPU-0600 Control
Version 1.0.0
Page 8
• Sync Code: Sync code of the CPU-0600.
• Wi-Fi Network : displays current SSID network
connected to
• Wi-Fi Password: displays network password
connected to
• Wi-Fi Strength – displays Signal strength of the
network connected to
Wi-Fi Strength
Wi-Fi Password
Wi-Fi Network
Sync Code
STAGING MODE: CONTROL STATUS

HBX CPU-0600 Control
Version 1.0.0
Page 9
OUTDOOR RESET – This is used in the outdoor reset
design calculation. This option should be set to reect
your specic city or region. (OFF/-40°F to 127°F)
BOILER SETPOINT – When a heat demand is present
and the control is not in WWSD, the control will target
this temperature for heating. (OFF/2°F to 210°F)
MAX BOILER TEMP – This is used in the outdoor reset
design calculation, and also serves as the maximum
setting for the boiler. This is the maximum boiler
temperature for the coldest day. (OFF/2°F to 210°F)
MIN BOILER TEMP: This is the minimum boiler
temperature. Set this to the temperature you would
like the boiler to be when the outdoor temperature
approaches WWSD. (OFF/2°F to 210°F)
USE WEB OUTDOOR TEMP: This setting can be used for
outdoor temperature reading via the web instead
of installing an outdoor sensor. The control must be
connected to a Wi-Fi network and the user must set
the controller to a building via the Sensorlinx mobile
app for this setting to work. (ON/OFF)
WARM WEATHER SHUTDOWN (WWSD): This setting is
used to set the temperature in which the CPU-0600
will go into WWSD. If the system rises above this
temperature, the system will be shut off. In WWSD the
boilers and all pumps will shut off.
(35°F to 120°F) Default: 70°F
WWSD TIME: This setting is used as a lag time for
WWSD. This will hold the control from entering WWSD
until this time has elapsed. The timer starts when the
outdoor temperature hits WWSD. This setting is useful
in the shoulder seasons when there are large outdoor
temperature swings.
(0°F to 240°F) Default 0°F
WWSD Time
WWSD
Use Web Outdoor Temp
Outdoor Reset
Boiler Setpoint
WWSD Time
WWSD
Use Web Outdoor Temp
Min Boiler Temp
Max Boiler Temp
Outdoor Reset
STAGING MODE: DESIGN TEMPERATURES
This option will appear when outdoor reset is set to OFF

HBX CPU-0600 Control
Version 1.0.0
Page 10
NUMBER OF ON/OFF STAGES – This setting will allow you
to select the number of boiler stages in your system
(0-16)
DIFFERENTIAL – Adjust this setting to the desired
differential for the boiler. This will center the differential
around the setpoint.
(eg. 20°F would be 10°F Below and 10°F Above)
(2°F to 100°F)
2 STAGE BOILERS – This setting will allow you to select
the number of 2 stages boiler in your system.
(ON/OFF)
LoLo/HiHi Rotation – The Lo/Lo - Hi/Hi function of the
Control instructs a heating system containing two dual
stage boilers to engage the rst stage of each boiler
prior to igniting the second stage of either boiler. The
Control will turn on the second stages of the boilers as
the call for heat is required.
(ON/OFF)
STAGE ON LAGTIME – When the boiler is set for more
than 1 stage, this setting will be set for the minimum
lagtime between boiler stages. This is a time delay
between stages. Even if the differential has been
exceeded this time must elapse before that stage can
come on.
(1Min -240Min)
STAGE OFF LAGTIME – This feature is used to set how
you would like to stage the boilers off When the boiler
is set for more than 1 stage, this setting will be set for
the minimum OFF lagtime between boiler stages.
(1S– 240S)
ROTATE TIME – The time of rotation between boilers.
This setting is in hours of run time. This means that
the boilers are going to rotate when the rst boiler
exceeds the second by the rotate time.
(OFF/1H to 240H)
Stage Off Lagtime
Rotate Time
Rotate Cycles
Number of MOD Stages
Stage On Lagtime
LoLo HiHi Rotation
2 Stage Boilers
Differential
Number of On/Off Stages
STAGING MODE: BOILER SETUP

HBX CPU-0600 Control
Version 1.0.0
Page 11
ROTATE CYCLES: Set the number of cycles at which
you would like to rotate the boilers. One cycle is
described as the boiler going on and then off.
(OFF/1 to 240)
NUMBER OF MOD STAGES – This setting will allow you to
select the number of modulating stages.
MODULATING TIME – This setting sets the time
between the steps when the boiler needs to increase
or decrease the ring rate. Each step is 1% for all
situations.
(1S to 240S)
MIN MOD PERCENT – This setting is used to set the
lowest modulating level the boiler can go down to.
This will also be the starting point whenever there is a
new demand.
(1% to 99%)
MOD OUT SETPOINT – In this mode the 0-10VDC signal
does not directly run the burner. The 0-10VDC signal
is interpreted by the boiler as a setpoint. The boiler in
this mode will modulate the burner to achieve that
setpoint. ex: 4VDC is equal to 140°F
(ON/OFF)
Mod Out Setpoint
Min MOD Percent
Modulating Time
Number of MOD Stages
Rotate Cycles
Rotate Time
Stage Off Lagtime
Stage On Lagtime
2 Stage Boilers
Differential
Number of On/Off Stages
STAGING MODE: BOILER SETUP
If you select more than three (3) stages you will need additional(s) CPU-0600
as the CPU-0600 can do a maximum for three (3) modulating stages per
controller.
If you are using modulating boilers and On/OFF boilers together in a system the
modulating boiler(s) will stage rst.

HBX CPU-0600 Control
Version 1.0.0
Page 12
This setting is used to congure the pump(s)
component in your system.
• Pump 1- The chosen pump type will close the
lower contact at 1-2 (PUMP1)when a demand is in
place. Pump choice options: Boiler, System, DHW,
App, None
• Pump 1 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump 1 to run after the call
associated with it has been removed.
• Pump 1 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 1 be delayed to
run after the call associated with it has been
activated.
• Pump 2- The chosen pump type will close the
lower contact at 3-4 (PUMP2) when a demand is in
place. Pump choice options: Boiler, System, DHW,
App, None
• Pump 2 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump2 to run after the call
associated with it has been removed.
• Pump 2 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 2 be delayed to
run after the call associated with it has been
activated.
• Pump 3- The chosen pump type will close the
lower contact at 3-4 (PUMP2) when a demand is in
place. Pump choice options: Boiler, System, DHW,
App, None
• Pump 3 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump2 to run after the call
associated with it has been removed.
• Pump 3 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 2 be delayed to
run after the call associated with it has been
activated.
• Pump Exercise Time (0-240 Hrs) the amount of time
that need to pass before the pumps will exercise
the system pumps. (0 = no exercising)
Pump Exercise Time
Pump 3 Start Delay
Pump 3 Post Purge
Pump 3
Pump 2 Start Delay
Pump 2 Post Purge
Pump 2
Pump 1 Start Delay
Pump 1 Post Purge
Pump 1
STAGING MODE: PUMP SETUP
PUMP OPTIONS
System – If there are any heating calls the pump
contact will close
Boiler – If there are any heating calls the pump contact
will close
DHW – if there is a DHW call the pump contact will
close
App – if the virtual app switch is activated this pump
contact will close
None – No pumps are being utilized in your system
setup

HBX CPU-0600 Control
Version 1.0.0
Page 13
USE DHW TANK – Once this option is enabled you will
be able to program the remaining options for your
DHW setup.
(ON/OFF)
FAST DHW – (Only Applies to Multiple Boiler Operation)
This option will allow all the boilers to come on
immediately when there is a call for DHW. The boilers
will still stage off at the normal differential. This option
allows for faster DHW heating.
(ON/OFF)
DHW BOILER SETPOINT – This option allows you to set
the maximum boiler temperature when the DHW
demand is on. This will override the calculated boiler
target from the designs.
(34°F to 200°F)
DHW TARGET – This option allows you to select your
DHW target temperature in the tank.
(34°F to 200°F)
DIFFERENTIAL – This is the differential for the DHW tank.
Set this parameter to the desired differential for the
DHW tank.
(2°F to 100°F)
DHW INTERLOCK – This setting will disable the boiler
pump to turn on when there is a DHW call.
(ON/OFF)
DHW PRIORITY – This selection will allow the DHW
demand to override the heating system for a max of
60 minutes in order to satisfy the DHW demand. Once
60 minutes have passed and there is still unsatised
heat demand, the control will automatically switch
back to accommodate the demand for heat.
(ON/OFF)
DHW Priority
DHW Interlock
Differential
DHW Target
DHW Boiler Setpoint
Fast DHW
Use DHW Tank
STAGING MODE: DHW SETUP

HBX CPU-0600 Control
Version 1.0.0
Page 14
PERMANENT HD – This setting indicates that the CPU-
0600 is in a permanent heat demand. This can be
used instead of attaching a thermostat.
(OFF/ON)
RUN TIMES – This setting will allow you to view your
boiler(s) run times.
• RESET RUN TIMES – Selecting this option will clear
the stage accumulated hours counter for your
boiler(s).
DEGREES – Use this setting to change the display
format from Celsius (°C) to Fahrenheit (°F). (°F/°C)
Default: °F
Degrees
Wi-Fi Settings
Run Times
Permanent HD
Stage 4
Reset Run Times?
Stage 3
Stage 2
Stage 1
STAGING MODE: SETUP MENU

HBX CPU-0600 Control
Version 1.0.0
Page 15
WI-FI – Indicates that the control is connected to a
2.4 GHz Wi-Fi network.
BOILER – Indicates the boiler temperature and
target. If there is a demand for heating the box will
be bordered with a red outline, and the staging
output(s) in the lower wiring chamber will be
closed.
SYSTEM – Indicates the system temperature and
target. When in boiler protection the box will have
a yellow outline.
OUTDOOR – The outdoor temperature will be
displayed. This option will also display if the control
is in WWSD (Warm Weather Shutdown).
DHW TANK – It will display the DHW temperature
and target. If there is a demand for DHW the zone
will be bordered with a red outline.
STAGES – Indicates how many boilers are being
utilized in your system setup. When a boiler is
activated by a heat demand the boiler will light up
in respect to their classication.
MODULATING STAGES- Indicates how many
modulating boilers are being utilized in your system
setup. When a modulating boiler is activated by a
heat demand the modulating boiler percentage
will start at the minimum mod percentage (%).
When there is no demand (off) the modulating
percentage (%) will displayed as 0%.
PUMPS/VALVE – When a pump/valve is activated
by a call you will see pump (P1) ,(P2), (P3) light up
in respect to their classication, their associated
contacts PUMP 1, PUMP 2, PUMP 3 can be found in
the lower wiring chamber will be closed.
DEMANDS - When the delegated demand is active
it will light up (DEMAND 1 - HD) or (DEMAND 2 –
DHW/SETPOINT) thus in turn the associated demand
in the upper wiring chamber will be closed.
MIXING MODE: MAIN SCREEN
1
2
3
4
5
6
7
8
9
Accessing the menu of the CPU-0600 is done by pressing the menu button (3
lines) in the top right corner.

HBX CPU-0600 Control
Version 1.0.0
Page 16
• Sync Code - Sync code of the CPU-0600
• Wi-Fi Network - displays current SSID network
connected to
• Wi-Fi Password - displays network password
connected to
• Wi-Fi Strength - displays Signal strength of the
network
The CPU-0600 allows for expandability for more boiler
staging between controllers. A maximum of four (4)
controllers can be utilized for a maximum of 16 boiler
stages. When using more than one CPU-0600, to allow
them to communicate wirelessly between each other,
they will need to follow a sequential order.
STAGE SEQUENCE SETUP – This setting will allow you to
select the stage sequence in your systems setup.
The rst sequence is labelled Primary and represents
sequence 1-4.
• Primary (Stages 1-4)
• Secondary (Stages 5-8) *CPU-0600 #2
• Secondary (Stages 9-12) *CPU-0600 #3
• Secondary (Stage 13-16) *CPU-0600 #4
CONTROL ID – If the Sequence was set to the Primary
then the number under Control ID will represent this
CPU-0600’s ID. If the CPU Sequence was set to any
sequence other than Primary, that CPU-0600’s Control
ID can be set to match the value of the Primary CPU-
0600 Control ID and the CPU-0600’s will then LINK
automatically. The CPU-0600’s will be LINKED when the
Sequence Link symbol appears on the top left of the
Main Screen for both controllers.
Wi-Fi Strength
Wi-Fi Password
Wi-Fi Network
Sync Code
Control ID
Stage Sequence
MIXING MODE: CONTROL STATUS
MIXING MODE: STAGE SEQUENCE SETUP

HBX CPU-0600 Control
Version 1.0.0
Page 17
OUTDOOR RESET – This is used in the outdoor reset
design calculation. This option should be set to reect
your specic city or region.
(OFF/-40°F to 127°F)
BOILER SETPOINT – When a heat demand is present
and the control is not in WWSD, the control will target
this temperature for heating. This option will appear
when outdoor reset is set to off
(OFF/2°F to 210°F)
SYSTEM SETPOINT – : When a heat demand is present
and the control is not in WWSD, the control will target
this system temperature.
(20°F to 180°F)
MAX BOILER TEMP – This is used in the outdoor reset
design calculation, and also serves as the maximum
setting for the boiler. This is the maximum boiler
temperature for the coldest day.
(OFF/2°F to 210°F)
MIN BOILER TEMP: This is the minimum boiler
temperature. Set this to the temperature you would
like the boiler to be when the outdoor temperature
approaches WWSD.
(OFF/2°F to 210°F)
MAX SYSTEM TEMP: This is used to setup the maximum
temperature for your low temperature system on the
coldest day.
(20°F to 180°F)
MIN SYSTEMP TEMP: This is used to setup the lowest
temperature you would like in the low temperature
system. The setpoint will hit this when the outdoor
temperature approaches WWSD. (20°F to 180°F)
Default: 120°F
WWSD Time
WWSD
Min Boiler Temp
Max System Temp
Min System Temp
Use Web Outdoor Temp
Outdoor Reset
Max Boiler Temp
MIXING MODE: DESIGN TEMPERATURES

HBX CPU-0600 Control
Version 1.0.0
Page 18
USE WEB OUTDOOR TEMP: This setting can be used for
outdoor temperature reading via the web instead
of installing an outdoor sensor. The control must be
connected to a Wi-Fi network and the user must set
the controller to a building via the Sensorlinx mobile
app for this setting to work.
(ON/OFF)
WARM WEATHER SHUTDOWN (WWSD): This setting is
used to set the temperature in which the CPU-0600
will go into WWSD. If the system rises above this
temperature, the system will be shut off. In WWSD the
boilers and all pumps will shut off.
(35°F to 120°F) Default: 70°F
WWSD TIME: This setting is used as a lag time for
WWSD. This will hold the control from entering WWSD
until this time has elapsed. The timer starts when the
outdoor temperature hits WWSD. This setting is useful
in the shoulder seasons when there are large outdoor
temperature swings.
(0°F to 240°F) Default: 0°F
WWSD Time
WWSD
Use Web Outdoor Temp
System Setpoint
Boiler Setpoint
Outdoor Reset
MIXING MODE: DESIGN TEMPERATURES
If the control disconnects from the Wi-Fi after 2 hours or longer it will go to the
coldest day of the year set in your outdoor reset design or maximum boiler
temperature.
Table of contents
Other HBX Control System manuals