HBX HydroBloc 0100 User manual

HBX Control Systems Inc.
Installation Manual
HydroBloc 0100
Version 2.10

Control Systems Inc.
Comfort
Control
Innovation
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 1
&""!&!&%
9?=:/@.?4:9
Safety Symbol & Warnings ....................................... 2
Receipt, Inspection and Name plate information. 2
Description and Main Parts ..................................... 3
090=,7&0.394.,7,?,
Pump Curve ................................................................4
Dimensions ................................................................ 4
)4=492,9/9>?,77,?4:9
Wiring ...........................................................................5
Installation ...................................................................5
Fitting Assembly ....................................................... 6
Hydrobloc Assembly ................................................ 6
#=:2=,88492*+
Multicolor Backlit Display......................................... 7
Dial Operation & Set/Status Mode......................... 8-10
D/=:-7:.0,?492
Dial Operation & Set/Status Mode ....................... 7
Status Screen .............................................................. 8
Programing ................................................................. 9
Programing Adjustments ......................................... 9-10
D/=:-7:.::7492
Dial Operation & Set/Status Mode ....................... 11
Status Screen .............................................................. 12
Programing ................................................................. 13
Programing Adjustments ......................................... 13-14
;;74.,?4:9=,B492>
),==,9?D91:=8,?4:9
Table of Contents

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc
Hyd oBloc M a n u a l Page 2
*++$"!"!&$"$
This manual will help with the installation, parameter
setting, troubleshooting and general maintenance
requirements for the HydroBloc. To guarantee the safe
and reliable operation of this HydroBloc, you must first
read this manual in detail and take particular note to any
and all warnings or caution directives prior to connecting
to AC power.
"97D>@4?,-7D<@,74140/49/4A4/@,7>B4?3
1:=8,7?=,4949249070.?=4.,7,9/(
.:9?=:7>>3:@7/,??08;??3049>?,77,?4:9:1
?34>0<@4;809?9.:==0.?B4=492,9/
49>?,77,?4:9B477,110.??30B,==,9?D
;=:A4/0/B4?3?34>@94?)4=4928@>?-0
.:8;70?0/49,..:=/,9.0B4?3?30.:/0>
,9/;=,.?4.0>,;;74.,-70?:?305@=4>/4.?4:9
1:=?30,.?@,749>?,77,?4:9
&30*+4>,84.=:;=:.0>>:=
-,>0/.:9?=:770=,9/,>>@.34>9:??:-0
=02,=/0/,>,>,10?D7484?.:9?=:7#70,>0
.:9>@7?,9/49>?,77?3030,?492:=.::7492
,;;74,9.049,..:=/,9.0B4?3?30
8,9@1,.?@=0=>=0.:8809/,?4:9>
%&+%+ "%)$!!%
$#&!%#&"!
! #&!"$ &"!
This HYD-0100 has gone through rigorous quality
control tests at the factory before shipment. After receipt
and before installation perform the following checks:
$0.04;?
After receiving, inspect the unit for any possible
physical damage that may have occurred during
transportation.
9>;0.?4:9
After unpacking the unit make sure the box contains:
• HYD-0100 HydroBloc
• Terminal Block
• 3 Fittings:
– Delivery Fitting with Pressure and
Temperature Sensor
– Return Connection
– Supply Fitting
• 4 3/4” Unions
• 1 Interconnect Wire
• 1 Outdoor Sensor
• 3 O-Rings
• 3 Stainless Steel Fitting Clips
• 1 Stainless Steel Backplate
• 1 Universal Sensors
• 1 Screwdriver
• 1 Cable Tie
• 1 Stainless Steel Temperature Sensor Clip
Make sure the part number on the unit corresponds to
the part number on the original box.
!,80;7,?091:=8,?4:9
The exterior label contains specific information unique
to your HBX HydroBloc and identifies some of the
basic features. The label displays the serial number
which will match the serial number on your actual
HydroBloc, the lot number, the bar code and the
products ETL number.
HYD-0100
HydroBloc
Mixing Control
HYD-0100
HydroBloc Mixing Control
Made In
Canada
Lot Number: 0000001
Serial Number: 0004-0907
Date: 09/14/07
Lot Number:
Serial Number:
Date:
3068143
V1.0V1.0V1.0V1.0V1.0
C?=080,E,=/
This action poses a serious threat that could
result in personal injury or death, as well as
permanent damage to the equipment. Proceed
with caution.
:/0=,?0,E,=/
This action may cause personal injury or have
adverse effects on the installation process if
handled incorrectly.
4>.:990.?#:B0=%:@=.0
The presence of low voltage(24VAC) or high
voltage(120VAC) could result in personal injury
or permanent damage to components or
equipment.
#:49?:1 9?0=0>?
This point clarifies pertinent information, or
brings your attention to an action that may have
adverse effects on the installation process.
© HBX C o n t o l Systems Inc. 20 1 2

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd obloc M a n u a l Page 3
$0?@=9:990.?4:9
System and Boiler/ Chiller Return
'94:9>
(3/4’’)
074A0=D4??492B%09>:=
Out to system load
%?,4970>>%?007&08;0=,?@=0%09>:=74;
This clip to holds the pressure sensor in place.
#=0>>@=0,9/&08;0=,?@=0%09>:=
Sensor indicates both ongoing system temperature and
pressure.
&0=849,77:.6
Seven pin terminal block used to hook up sensor inputs,
boiler demand, and heat demand inputs.
4=#@=20=
Purges air from the hydronic system.
Viewing from top left and moving right in a clockwise direction:
424?,74>;7,D
Multi-colour backlight that indicates all parameters.
@7?41@9.?4:9:9?=:74,7
Turn left, turn right, and enter when pressed.
(#@8;
Adjustable three speed pump.
D/=:7:. :@9?492:70
%@;;7D4??492
Boiler/ Chiller input.
:@9?492=,.60?
Stainless steel bracket that is used to fix fitting positions and help with
wall mounting.
:@9?492=,.60?:70
Heat
°F
System
Temp
90.0
Status
1. Digital Display
13. Terminal Block
12. Pressure and
Temperature Sensor
11. Stainless Steel
Temperature
Sensor Clip
10. Delivery Fitting
9. 3/4” Unions
8. Return
Connection
2. Multifunction
Control Dial
3. 120V Pump
4. HydroBloc
Mounting Hole
6. Mounting
Bracket
7. Mounting
Bracket Hole
5. Supply
Fitting
%$#&"! !#$&%
The HBX HYD-0100 is a boiler control and mixing tool designed as a hybrid mixing system with a built-in pump
and control functionality. Outdoor reset technology operates utilizing fully programmable reset curves.

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc
Hyd oBloc M a n u a l Page 4
0
5
10
15
20
25
30
024681012
Head (Ft)
Flow (USGPM)
P
Speed 1
Speed 2
Speed 3
!$&!&
9;@?(:7?,20
120 VAC, ± 10%, 60Hz, 2A
C&30=84>?:=9;@?>
Boiler (Chiller)/ Outdoor
C:470=34770="@?;@?$07,D>
125VAC 2A
C#=0>>@=0&08;0=,?@=0%09>:=
System Sensor
4.=:;=:.0>>:=
16Bit, 20MHz
,92@,20>
English
)0423?
4.53 G (10 lbs)
4809>4:9>
309mm (12.180”) W x 255mm (10.039”) H x 169mm
(6.661”) D
&4>?492>
Meets CSA C22.2 No. 24
Meets UL Standard 873
ETL Control No. 3068143
%?:=,20
%?:=049,.70,9/=D;7,.0
Temperature: +10ºC to +40ºC
Humidity: 0 to 95% (air conditioned environment)
0.039”
6.457”
4.724”
12.180”
12.180”
6.690”
3.898”
2.494” 1.705”
7.718”
2.462”
6.661”
#' #'$("$'#%
!%"!%
© HBX C o n t o l Systems Inc. 20 1 2

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 5
)$!!!%&&"!
)$!
&0=849,7,9/
Thermostat Input
Run wire straight from thermostat.
&0=849,7,9/
Outdoor Sensor
Place outside on the North side of the building
(if possible).
&0=849,7,9/
Boiler/ Chiller Sensor
This sensor is put on the main boiler/chiller loop.
&0=849,7,9/
Boiler/ Chiller Contacts
This contact is used to send the demand signal for the
boiler/ chiller to turn on.
:9:?,;;7D;:B0=30=0,>?30?30=8:>?,?49;@?
1@9.?4:9>:9.7:>0/.:9?,.?>
2
3
1
4
5
6
7
Thermostat
Boiler/
Chiller
Sensor
Outdoor
Sensor
Boiler/
Chiller
Contacts
Set
%+%& %!%"$&& !&"#&"!%&'#
When using the Hydrobloc in an injection setup you must cut the wire from the existing system/pressure
sensor and use the extension wire to attach that line to a strap on system sensor (sold seperately). There is
also an Interconnect Wire that needs to be connected (included)
Green
White
Yellow
Brown
Interconnect Wire (Red Heatshrink)
Supplied Extra Strap-on Sensor B
You must splice a strap-on sensor to the green (ground) and the yellow (signal) wire. Then you must place
the wire between the newly connected yellow wire and the brown wire. This will then allow you to mount
the sensor on the main system loop to use the Hydrobloc in a primary/secondary application. (No pressure
indicated on display)
Thermostat
Outdoor
Sensor Boiler/
Chiller
Sensor
Boiler/
Chiller
Contacts

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
$0?@=9:990.?4:9
This fitting is to be installed on the lower left hand
side of the Hydrobloc.
4??49274;
Secure all three fittings to the Hydrobloc.
&0=849,77:.6
Seven pin terminal block used to hook up sensor inputs,
boiler/ chiller demand, and demand inputs.
!%&&"!
&&!%% +
To place each fitting into the port on the Hydrobloc
first place the o-ring over the fitting. Once the o-ring is
in place firmly twist and press the fitting into its
appropriate position as shown in the diagram below.
+$""%% +
,.6;7,?0
Installed on the wall to mount the Hydrobloc.
%@;;7D4??492
This fitting is to be installed on the lower right hand
side of the Hydrobloc.
074A0=D4??492
This fitting is to be installed on the top left hand side
of the Hydrobloc closest to the front of the
Hydrobloc.
Hyd oBloc M a n u a l Page 6 © HBX C o n t o l Systems Inc. 20 1 2

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 7
'&""$&%#+
The Multicolor Backlit Display is one of the keu features of the HBX controls HYD-0100. Depending on which
mode of operation is selected the screen color will change to indicate information about the status of the system.
Heat
°F
System
Temp
90.0
Status
!#'&"!
There are 2 modes for the control, ;=:2=,88492 and >?,?@>>.=009>. The
;=:2=,88492 screen is identified by the %&4.:9 on in the top/middle left
corner. The >?,?@> screen is indicated by the %&&'%4.:9 on in the
top/middle left corner.
By pressing the dial in for more than 1 second will allow the user to access the
;=:2=,88492 section of the control.
Heat demand is indicated by the HEAT indicator on in the top left corner of
the screen.
Heat
°F
System
Temp
90.0
Status
Heat
°F
System
Temp
90.0
Set
+$""&!"#$&"!%&&'% "
+$"""#$&"! "&!"$""!
Heat
°F
System
Temp
90.0
Status
Heat
°F
System
Temp
90.0
Status
Cool
%.=009:7:@=>0,?492
Light Blue - No heat demand
Red - Heat demand and boiler running
Yellow/Green - Heat demand ON, boiler running but
in boiler protection
Dark Blue - Heat demand ON and boiler satisfied
The Hydrobloc is capable of operating in heating or cooling mode. During initial power up of the hydrobloc the user
may select either mode by rotating the dial. To change modes, cycle power to the unit and select the desired operation
mode.
%.=009:7:@=>::7492
Light Blue - No cool demand
Yellow -green - Cool demand ON and chiller satisfied
Dark Blue - Cooler demand ON and and chiller
running.
#$"$ !*+

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
°F
System
Temp
90.0
Status
%?,?@>%.=0094,7 ,94;@7,?4:9
In this mode turning the dial left or right will show the different status
screens on the control.
°F
Boiler Temp
140.0
Status
°F
Out Temp
10.0
Status
°F
Setpoint
System
Temp
90.0
Status
°F
System
Temp
90.0
Status
:470=&08;0=,?@=0
"@?/::=&08;0=,?@=0
4C0/%D>?08&08;0=,?@=0
%0?;:49?
4C0/%D>?08&08;0=,?@=0
°F
Setpoint
Boiler Temp
140.0
Status
:470=&08;0=,?@=0%0?;:49?
PSI
System 0.0
Status
%D>?08#=0>>@=0
Hyd oBloc M a n u a l Page 8 © HBX C o n t o l Systems Inc. 20 1 2
))%
Arrow showing in bottom left corner
indicates that the Hydrobloc is in
Warm Weather Shut Down (WWSD).
+$""&!%&&'%%$!%
(,7A0#:>4?4:99/4.,?:=
°F
Boiler Temp
140.0
Status
°F
Boiler Temp
140.0
Status
?4>;:>>4-70?:149/?30A,7A0;:>4?4:949/4.,?:=,9/?30.:7/B0,?30=>3@?/:B9)%>D8-:7>
,8:92>,80>?,?@>>.=009

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 9
°F
System
Temp
90.0
Set
°F
Boiler Temp
190.0
Set
0>429:470=&08;0=,?@=0
This is the design boiler temperature.
It is used in the outdoor reset design
calculation and is also the maximum
setting for the boiler.
(50°F-200°F) Default: 190°F
°F
Set
07.4@>:=,3=09304?
Use this setting to change the display
format from °C to °F.
(°C/°F) Default: °F
PSI
System
Set
4C492/5@>?809?
%00+=,B492 Once
" is selected the Hydrobloc will
no longer show pressure and it will
use the Strap-On System Sensor to
sense the temperature. By using a
different system sensor this allows us
to still provide boiler protection.
Note: +:@B4773,A0?:,??,.3?30
90B>D>?08>09>:=?:?307:B
?08;>D>?08;2
(On/Off) Default: On
°F
System
Temp
90.0
Set
#=:2=,884923,920 :/0
To change a setting you must press the dial in momentarily and an arrow will
appear in the top left corner of the screen. This will indicate the control is in
the programming change mode. While in the change mode the user will be able
to change the setting of that selection by turning the dial to the left to decrease
the setting and to the right to increase the setting. Once you have finished
changing the setting press the dial momentarily and the arrow in the top left
corner will disappear. This will indicate that the user is no longer in
programming change mode.
#=:2=,88492%.=:77 :/0
To enter this mode the dial must be pressed in for more than 1 second. When
the SET indicator comes on release the button, you will now be in
programming scroll mode.
In this mode turning the dial to the left or right will scroll through the
programming options on the control. Each setting will be indicated by the
icons around the screen as well as the temperature of that setting. There are 11
settings to be set in the programming scroll mode.
If you allow the control to idle in Programming Scroll Mode for thirty seconds the control will automatically return
to status mode.
+$""&!#$"$ !
+$""&!#$"$ !'%& !&%

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
If the min boiler temperature is set
to " then the boiler demand will
always be on when a heat demand is
present.
This is used when you would like the
modulating boiler to control itself.
(Off-200°F) Default: 120°F
Heat Off
Set
Diff
°F
Boiler 20.0
Set
Max
°F
Out Temp
75.0
Set
0,?08,9/
ON: This setting indicates that the
Hydrobloc is in a permanent heat
demand. Used instead of attaching a
thermostat.
On1: Puts the Hydrobloc in
permanent pump demand (pump
alwaysON).
(On/On1/Off) Default: Off
:470=4110=09?4,7
This setting is used to set the boiler
differential.
(10°F-50°F) Default: 20°F
Hyd oBloc M a n u a l Page 10 © HBX C o n t o l Systems Inc. 20 1 2
°F
System
Temp
135.0
Set
0>429%D>?08&08;0=,?@=0
This is the design low temperature
system temperature. It is used in the
outdoor reset design calculation for
the low temperature reset curve.
(50°F-200°F) Default: 135°F
Room
°F
Temp
70.0
Set
0>429$::8&08;0=,?@=0
This is the design room temperature.
It is used in the outdoor reset design
calculation. Set it to the approximate
desired room temperature.
(0°F-120°F) Default: 70°F
°F
Out Temp
10.0
Set
0>429"@?&08;0=,?@=0
This is the design outdoor
temperature. It is used in the outdoor
reset design calculation. Set this
temperature to the temperature at
which you would like to hit your
maximum temperature in from the
control.
(-50°F-100°F) Default: -10°F
Min
°F
Boiler Temp
120.0
Set
49:470=&08;0=,?@=0
This is the minimum boiler
temperature. This setting will vary
depending on the type of boiler
you’re running. This is boiler supply
temperature so keep that in mind
when selecting this feature.
Min
°F
System
Temp
70.0
Set
49%D>?08&08;0=,?@=0
This is the minimum system
temperature. Set this temperature to
the minimum temperature you would
like to see in the low temperature
system loop.
(20°F-150°F) Default: 70°F
))%
This setting is used to set the
temperature at which the Hydrobloc
will go into WWSD. Above this
temperature the system will be shut
off.
(20°F-150°F) Default: 75°F
%D>?08%0?;:49?";0=,?4:9 To set a point on the System Output Temperature adjust the Min System
Temperature to be the same as the design system temperature.

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 11
+$""""!
"#$&"!%&%&&'% "
Min
°F
System
Temp
70.0
Set
!#'&"!
There are 2 modes for the control, ;=:2=,88492 and >?,?@>>.=009>.
The ;=:2=,88492 screen is identified by the %&4.:9 in the top/middle
left corner. The >?,?@> screen is indicated by the %&&'%4.:9 in the
top/middle left corner.
By pressing the dial in for more than 1 second will allow the user to access
the ;=:2=,88492 section of the control.
Cool demand is indicated by the "" indicator in the top left corner of
the screen.
System
Temp
Status
°F
70.0
Care must be taken to prevent condensation forming on any exposed piping, panels or devices which
cold water flows through. To avoid condensation, the chilled water temperature must be set above the
ambient dew-point temperature.
System
Temp
Set
Cool
°F
70.0

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 12 © HBX C o n t o l Systems Inc. 20 1 2
+$""""!%&&'%%$!%
Min
°F
System
Temp
70.0
Set
Status
%?,?@>%.=0094,7 ,94;@7,?4:9
In this mode turning the dial left or right will show the different
status screens on the control.
°F
Boiler Temp
140.0
Status
°F
Out Temp
10.0
Status
°F
Setpoint
System
Temp
90.0
Status
°F
System
Temp
90.0
Status
°F
Setpoint
Boiler Temp
140.0
Status
PSI
System 0.0
Status
°F
Boiler Temp
140.0
Status
°F
Boiler Temp
140.0
Status
°F
Boiler Temp
140.0
Status
°F
Out Temp
10.0
Status
°F
Setpoint
System
Temp
90.0
Status
°F
System
Temp
90.0
Status
34770=&08;0=,?@=0
"@?/::=&08;0=,?@=0
4C0/%D>?08&08;0=,?@=0
%0?;:49?
4C0/%D>?08&08;0=,?@=0
°F
Setpoint
Boiler Temp
140.0
Status
34770=&08;0=,?@=0%0?;:49?
PSI
System 0.0
Status
%D>?08#=0>>@=0
)%
Arrow showing in bottom left corner
indicates that the Hydrobloc is in Cold
Weather Shut Down (CWSD).
(,7A0#:>4?4:99/4.,?:=
°F
Boiler Temp
140.0
Status
°F
Boiler Temp
140.0
Status
Stage
60.0
Stage
80.0
Stage Stage
?4>;:>>4-70?:149/?30A,7A0;:>4?4:949/4.,?:=,9/?30.:7/B0,?30=>3@?/:B9)%>D8-:7>
,8:92>,80>?,?@>>.=009

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 13
°F
System
Temp
70.0
Set
Temp
Set
Cool
°F
Stage
40.0
0>429:470=&08;0=,?@=0
This is the design chiller temperature.
It is used in the outdoor reset design
calculation and is also the maximum
temperature setting for the chiller.
(20°F to 100°F) Default: 40°F
Set
F
.
07.4@>:=,3=09304?
Use this setting to change the display
format from °C to °F.
(°C/°F) Default: °F
PSI
System
Set
4C492/5@>?809?
%00+=,B492 Once
" is selected the Hydrobloc will
no longer show pressure and it will
use the Strap-On System Sensor to
sense the temperature.
Note: +:@B4773,A0?:,??,.3
?3090B>D>?08>09>:=?:?30
7:B?08;>D>?08;2
(On/Off) Default: On
System
Temp
Set
Cool
°F
70.0
#=:2=,884923,920 :/0
To change a setting you must press the dial in momentarily and an arrow will
appear in the top left corner of the screen. This will indicate the control is in
the programming change mode. While in the change mode the user will be able
to change the setting of that selection by turning the dial to the left to decrease
the setting and to the right to increase the setting. Once you have finished
changing the setting press the dial momentarily and the arrow in the top left
corner will disappear. This will indicate that the user is no longer in
programming change mode.
#=:2=,88492%.=:77 :/0
To enter this mode the dial must be pressed in for more than 1 second. When
the SET indicator comes on release the button, you will now be in
programming scroll mode.
In this mode turning the dial to the left or right will scroll through the
programming options on the control. Each setting will be indicated by the
icons around the screen as well as the temperature of that setting. There are 11
settings to be set in the programming scroll mode.
If you allow the control to idle in Programming Scroll Mode for thirty seconds the control will automatically return
to status mode.
+$""""!#$"$ !
+$""""!#$"$ !'%& !&%

Control Systems Inc.
HB X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 14 © HBX C o n t o l Systems Inc. 2012
Set
Cool 0FF.
Min
Out Temp
Set
°F
50.0
Set
Cool
F
Diff
10.0
Room
Temp
Set
Cool
°F
75.0
Out Temp
Set
Cool
°F
100.0
System
Temp
Set
Cool
°F
50.0
::708,9/"!
This setting indicates that the
Hydrobloc is in a permanent demand.
Used instead of attaching a
thermostat.
On1: Puts the Hydrobloc in
permanent pump demand (pump
always ON).
(On/On1/Off) Default: Off
)%
This setting is used to set the
temperature at which the Hydrobloc
will go into CWSD. Below this
temperature the system will be shut
off.
(10°F to 100°F) Default: 50°F
34770=4110=09?4,7
This setting is used to set the chiller
differential
(10° to 50°F) Default: 10°F
0>429:@?&08;0=,?@=0
This is the design outdoor
temperature. It is used in the outdoor
reset design calculation. Set this to
the outdoor temperature at which
you would like to hit your minimum
(coolest) temperatures on the reset
curve.
(20°F to 150°F) Default: 100°F
0>429$::8&08;0=,?@=0
This is the design room temperature.
It is used in the outdoor reset design
calculation. This is the maximum
chilled water temperature.
(20°F to 150°F) Default: 75°F
0>429>D>?08&08;0=,?@=0
This is the design mixed temperature
system temperature. It is used in the
outdoor reset design calculation for
the mixed temperature reset curve.
(20°F to 100°F) Default: 50°F
This is the lowest (coolest) water
temperature used in the mixed
system.
#$"$ !'%& !&%

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
+$)!
Outdoor
Sensor
Indoor
Thermostat
Boiler
Sensor
Boiler/ Chiller
HT
0>.=4;?4:9
This is an example of the Hydrobloc in a typical application. It is used to mix into a low temperature loop.
+$)!
Outdoor
Sensor
Indoor
Thermostat
HT
r/ ChillerelioB
Outdoor
Sensor
Indoor
Thermostat
HT
Outdoor
Sensor
Indoor
Thermostat
HT
Boiler
Sensor
Boiler
Sensor
Boiler
Sensor
Boiler/Chiller
Controller
0>.=4;?4:9
This drawing exhibits the HydroBloc in a multiple-
mixing manifold application.
Hyd oBloc M a n u a l Page 15

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 1 . 1 4
+$)!
Boiler/ Chiller
Outdoor
Sensor
Indoor
Boiler/
Chiller
Sensor
System
Sensor
Thermostat
HT
!:?0
The system temperature/pressure sensor is no longer used. You must use the thermistor extension wire and the extra
strap-on thermistor for this configuration, as well as turn the 4C492/5@>?809? to " in the programing
adjustments of the D/=:7:.;2. See the %D>?08%09>:=??,.3809?section on page 5.
+$)!
Outdoor
Sensor
Outdoor
Sensor
Outdoor
Sensor
0>.=4;?4:9
Each unit of a multi-family dwelling (an
apartment for example) can have independent
outdoor reset control. This provides optimum
comfort as well as offering improved control
and energy efficiency.
Hyd oBloc M a n u a l Page 16 © HBX C o n t o l Systems Inc. 20 1 2
0>.=4;?4:9
This is an example of the HydroBloc being used as an injection pump. (See note below)

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 17
484?0/),==,9?D
HBX Controls warrants each of its products to be free from defects in workmanship and materials under normal use and service
for a period of 24 months from date of manufacture or 12 months from date of purchase from an HBX Authorized Dealer, if
within the above documented period after date of manufacture.
If the product proves to be defective within the applicable warranty period, HBX on its sole discretion will repair or replace said
product. Replacement product may be new or refurbished of equivalent or better specifications, relative to the defective product.
Replacement product need not be of identical design or model. Any repair or replacement product pursuant to this warranty shall
be warranted for not less than 90 days from date of such repair, irrespective of any earlier expiration of original warranty period.
When HBX provides replacement, the defective product becomes the property of HBX Controls.
Warranty Service, within the applicable warranty period, may be obtained by contacting your nearest HBX Controls office via the
original Authorized Agent and requesting a Return Material Authorization Number (RMA #). Proof of purchase in the form a
dated invoice/receipt must be provided to expedite the issuance of a Factory RMA.
After an RMA number has been issued, the defective product must be packaged securely in the original or other suitable shipping
package to ensure that it will not be damaged in transit. The RMA number must be visible on the outside of the package and a
copy included inside the package. The package must be mailed or otherwise shipped back to HBX with all costs of
mailing/shipping/insurance prepaid by the warranty claimant.
Any package/s returned to HBX without an approved and visible RMA number will be rejected and shipped back to purchaser at
purchaser’s expense. HBX reserves the right, if deemed necessary, to charge a reasonable levy for costs incurred, additional to
mailing or shipping costs.
484?,?4:9:1 ),==,9?40>
If the HBX product does not operate as warranted above the purchasers sole remedy shall be, at HBX’s option, repair or
replacement. The foregoing warranties and remedies are exclusive and in lieu of all other warranties, expressed or implied, either in
fact or by operation of law, statutory or otherwise, including warranties of merchantability and fitness for a particular
purpose/application. HBX neither assumes nor authorizes any other person to assume for it any other liability in connection with
the sale, installation maintenance or use of HBX Controls products.
HBX shall not be liable under this warranty; if its testing and examination discloses that the alleged defect in the product does not
exist or was caused by the purchasers or third persons misuse, neglect, improper installation or testing, unauthorized attempts to
repair or any other cause beyond the range of intended use, or by accident, fire, lightning or other hazard.
484?,?4:9:1 4,-474?D
In no event will HBX be liable for any damages, including loss of data, loss of profits, costs of cover or other incidental,
consequential or indirect damages arising out of the installation, maintenance, commissioning, performance, failure or interruption
of an HBX product, however caused and on any theory of liability. This limitation will apply even if HBX has been advised of the
possibility of such damage.
:.,7,B
This limited warranty statement gives the purchaser specific legal rights. The purchaser may also have other rights which vary from
state to state in the United States, from Province to Province in Canada and from Country to Country elsewhere in the world.
To the extent this Limited Warranty Statement is inconsistent with local law, this statement shall be deemed modified to be
consistent with such local law. Under such local law, certain disclaimers and limitations of this statement may not apply to the
purchaser. For example, some states in the United States, as well as some governments outside the United States (including
Canadian Provinces), may:
Preclude the disclaimers and limitations in this statement from limiting the statutory rights of a consumer (e.g. United ingdom);
Otherwise restrict the ability of a manufacturer to enforce such disclaimers or limitations; or
Grant the purchaser additional warranty rights which the manufacturer cannot disclaim, or not allow limitations on the duration of
implied warranties.

Control Systems Inc.
H B X H Y D 0 1 0 0 H y d r o B l o c
V e r s i o n 2 . 1 0
Hyd oBloc M a n u a l Page 18 © HBX C o n t o l Systems Inc. 20 1 2
!"&%

©HBX Control Systems Inc. 2011
Phone: +1 (403) 720-0029 Fax: +1 (403) 720-0054
Email: info@hbxcontrols.com Web: www.hbxcontrols.com
HBX Control Systems Inc.
4516 - 112th Avenue SE
Calgary, AB T2C 2K2
v3.3
This manual suits for next models
1
Table of contents
Other HBX Control System manuals
Popular Control System manuals by other brands

J&D MAnufacturing
J&D MAnufacturing JD-MV1 Installation & user guide

ROTOTILT
ROTOTILT ICS Direct manual

Intermatic
Intermatic T51211BC supplementary guide

Mitsubishi Electric
Mitsubishi Electric 700 Series Training manual

Crestron
Crestron FlipTop FT2 Series quick start guide

Lennox
Lennox Harmony III Homeowner's manual