Hitachi HARC70-CE1 User manual

INSTALLATION AND OPERATION MANUAL
MANUAL DE INSTALACIÓN Y
FUNCIONAMIENTO
INSTALLATIONS- UND BETRIEBSHANDBUCH
MANUEL D’INSTALLATION ET DE
FUNCTIONNEMENT
MANUALE D’INSTALLAZIONE E D’USO
ÅÃ×ÅÉÑÉÄÉÏÅÃÊÁÔÁÓÔÁÓÇÓÊÁÉ
ËÅÉÔÏÕÑÃÉÁÓ
Do not perform installation work, without referring to our installation manual.
.
.
.
.
No realice trabajos de instalación sin consultar el manual de instalación
Führen Sie die Installationsarbeiten, gemäß dem Installationshandbuch durch
N'effectuez jamais de travaux d'installation, sans vous référer au manuel d'installation
Non effettuare interventi d'installazione essere eseguiti attenendosi alle istruzioni
contenute in questo manuale
Ìçí åêôåëåßôå åñãáóßåò åãêáôÜóôáóçò ÷ùñßò íá áíáôñÝîåôå óôï åã÷åéñßäéï
åãêáôÜóôáóçò.
HARC70-CE1
BMS Connection Adapter
(Building Management System)
ENGLISH
ESPAÑOL
DEUTSCH
FRANÇAIS
ITALIANO


SAFETY SUMMARY 1
/
1
ENGLISH
1. SAFETY SUMMARY
ÕWARNING:
-This product is used for BMS connection adapter for HITACHI Water Chilling Units.
-Do not place the adapter in a place where flammable gas, or oil mist may stay exit, it will
cause a fire, a fire disaster, deformation of machines, corrosion or breakage
-a place where oil mist or steam drifts.
-a place where sulfide gas form as hot spring drifts.
-In the case that a medical equipment generating electro-magneticwaves is installed near
the Water Chillers, pay an attention to the radiation direction does not occur.
-It is recommended that a space of 3 m or more between HARC70-CE and the medical
equipment, radios, etc. be provided.
-Do not place the adapter in a place to be exposed to direct sunlight.
-Install action:
-Install properly this adapter by following this manual to avoid any electric shock, fire
disaster and injury by falling down HARC70-CE1.
-Check to ensure that the adapter is fixed firmly to avoid injury by falling.
-To avoid the fire or fire disaster, do not install the adapter in a place where there is
possibility of generation or flow of flammable gases.
-Electrical Work:
-To avoid any electric shock, ask for the work to the shop having qualification for
electrical works.
-To avoid any electric shock and disaster, perform electrical wiring according to local
regulations.
-To avoid electric shock, and fire disaster, use the prescribed cable to connect of Water
Chiller units, (model HARC70-CE1)
-Turn off electrical power before electric wiring work when the cover of HARC70-CE1
is opened.
2. SYSTEM CONSTITUTION
2.1. SYSTEM CONSTITUTION
The Internal Constitution of BMS connection using HARC70-CE1 is indicated in the Figure1.1.
Read this manual together with the “Installation & Operation Manual” for other units which are
connected. As for the other equipment which composes the system, read the handling manual
which was attached to each.
(*1) LONWORKS ® is the Register Trade Mark of Echelon Corporation in United States and other countries.
Fig. 1.1. Example of System Constitution
Upper Monitoring System (BMS)
The range which
Hitachi provides
LonWorks ® (*1) Network
HARC70-CE1
Chiller Unit
HARC70-CE1
Chiller Unit Chiller Unit Chiller Unit Chiller Unit

2
/
2SYSTEM CONSTITUTION
2.2. NAME OF PARTS
Name of Each Part of HARC70-CE1 is indicated in the Table 1.2.
Fig. 1.2. Name of Each Part of HARC70-CE1
Fig. 1.3. Outer Appearance of HARC70-CE1
Power Source Dis
p
la
y
LED
Light is ON when the power is supplied.
Transmission Dis
p
la
y
form U
pp
er S
y
stem LED
Transmission state with U
pp
er Monitorin
g
E
q
ui
p
ment.
Transmission Dis
p
la
y
LED
Transmission state with Water Chiller units.
POW CONTROL
SYSTEM G/W
HITACHI
IRP PAC
Display of type
Upper cover
Lower cover

SYSTEM CONSTITUTION 2
/
3
ENGLISH
2.3. NAME OF TERMINAL PORTIONS AND SETTING POSITIONS OF DIP SWITCHES
Names and functions are indicated Fig. 1.4. This indicates the figure without the cover of
HARC70-CE1. Read “Section 4” for Connecting Method of each Terminal and Setting of
Dip Switches.
Fig. 1.4. Name of Terminals and Dip Switch Setting Portion
(1) 8 Pins DSW [S202]
Read 5.1 “Setting of Dip Switch” to set the address of HARC70-CE1. 8 Pins DSW are used for Self-Inspection.
For details, refer to the 6.1 “Self Checking of HARC70-CE1”.
(2) 8 Pins DSW [S201]
Read 5.1 “Setting of Dip Switch” for the detail and function of HARC70-CE1.
(3) 7-Segment
Read 5.2 “Test Run” 5.3 “Indication of Abnormality” for the details of 7-Segment’s display.
PSW [M.CLR]
Push Switch for checking
connected unit
q
uantit
y
8P DSW [S202]
Dip Switch System
Setting of
HARC70-CE1
8P DSW [S201]
Dip Switch for Setting
Functions of HARC70-CE1
7-Segment
Present state of
HARC70-CE1
Power Source
Terminal to connect
to AC220∼240V
Power Source
Earth Terminal
to be ground for
surge absorber
Terminal for
Transmission for
Upper System to
connect Transmission
line for Upper System
Monitoring
Terminal for Unit
Transmission to
connect Water
Chiller units
POW CONTROL
SYSTEM G/W
MCLR LON-SERV.
AC / AC / E LON / H-LINK
S201 S202 LON H-LINK
HITACHI
Service Pin for
LonWorks
PSW [LON-SERV]
IIRP PAC

3
/
4INSTALLATION WORK
2.4. SPECIFICATIONS
Table 2.1. Hardware Specifications
Item Specifications
Power Source AC220/240V±10% (50/60Hz)
Power Consumption 10W(max)
Outer Dim W170×L75×H80 (mm)
Mass 440g
Installation Condition Indoor
Tempreture Condition 0~45°C
Humidity Condition 10~80°C (No dewing)
Table 2.2. Telecommunication Specifications for Water Chillers
Item Specifications
Communication Unit Water Chillers
Communication Line Nonpolar two wire system
Telecommunication System Half-duplex Operation
Synchronous System Asynchronous Communication Method
Telecommunication Speed 9600 bps
Wiring Length 1000 m (Total length)
Quantity of Connection
Model: HARC70-CE1 Water Chiller Unit ×4
Table 2.3. Telecommunication Specifications for Upper System
Item Specifications
Communication Unit Upper Monitoring Equipment
Transmission Protocol Lon Talk Protocol (*1)
Access Method Predicted persistent CSMA/CD System
Coded System Differential Manchester Code
Telecommunication Speed 78000 bps
Wiring Length 1000 m (Bus Total length)
(*1) Lon Talk is Register Trade Mark of Echelon Corporation in United States and other countries.
3. INSTALLATION WORK
The procedure from the installation to power supply are explained inTable 3.1.
Table 3.1. Handling Procedures
No Item Content
1 Selection of Installation Position Attention item in case of establishment
2 Installation Work Installation Method and Attention item
3 Wiring Connection Manner Power and Communication Wiring Method
4 Setting of Dip Switch Caution of Dip Switch and Setting Method
5 Power Supply Points to be Checked

INSTALLATION WORK 3
/
5
ENGLISH
3.1. INSTALLATION
Selection of Installation Position Select a place for installation which can meet the Following
conditions.
-a place that described in “Before Installation of this manual”.
-a place in a metallic cabinet which is grounded and is shut tightly.
3.2. INSTALLATION PROCEDURES
-Install the HARC70-CE1 by keeping the screw terminal board at the lower side.
-Installation methods are as follows:
a) Mounting on DIN Rail (35mm) (DIN Rail: Field-Supplied)
1. Hook the edge of the HARC70-CE1 at
theUpper part on the DIN Rail.
2. Press the another edge to the railuntil
the HARC70-CE1 is fully fixed.
Procedure:
Upper
Lower
HITACHI CONTROL
SYSTEM G/W
Screw Terminal
HITACHI CONTROL
SYSTEM G/W
(Horizontal Installation)
Correct Installation Wrong Installation

4
/
6WIRING CONNECTION METHOD
b) Fixing Method by Screw (M4) (Screws: Field-supplied)
4. WIRING CONNECTION METHOD
ÕATTENTION:
-Read and understand SAFETY SUMMARY of this manual before wiring work.
-Do not perform wiring this work by a person expect certified ones.
4.1. INSTALLATION OF WIRING
1. Regarding HARC70-CE1, transmission line
for water chillers and transmission line for
Upper system monitoring equipment are
required.
2. Wiring Method.
Nº Equipment for
connecting Specification of wiring
1Power Source Line
for Water Chillers AC220-240V 2mm2two cores
shield
2 Earth Cable Follow local standards.
3Upper Monitoring
Equipment
Follow the instructions by
the person who manages the
upper system equipment. (*2)
4Transmission Line
for Water Chillers 1P-0.75mm2twisted pair
cable (*1)
(*1) The cable always use the Twist-Pair Cable.
Connection Cable: Field-supplied.
1. Open the both upper and lower
cover of HARC70-CE1 horizontally.
Procedure:
3. Close the both upper
and lower cover.
2. By using screw (M4 Screw, 2 Positions),
fix HARC70-CE1 on the wall.
HITACHI CONTROL SYSTEM G/W
HARC70-CE1
p
Upper Monitoring
Equipment
r
AC220/240V
Power Source
q
s
Water Chiller Unit Water Chiller Unit

WIRING CONNECTION METHOD 4
/
7
ENGLISH
(*2) LONWORKS Network Cable
Use the cable that is recommended by Echelon Co. and follow the instruction of the
manufacturer who produces the Upper equipment.
Cable Type and Characteristics
Cable Diameter of
Wire/AWG Electric
Resistivity Ω/km
Electric
Capacity
nF/km
Vprop%
of Light
Velocity
Belden 85102, Single/Twist pair,
Q’ty of Core 19/29, Without Shield,
150°C 1.3mm/16 28 56 62
Belden 8471, Single/Twist pair,
Number of Core 19/29, Without
Shield, 60°C 1.3mm/16 28 72 55
Level VI 22AWG, Single Core,
Without Shield 0.65mm/22 106 49 67
JY(St)Y2×2×0.8, 4Lines Spiral
Twist, Single Core, With Shield 0.8mm/20.4 73 98 41
TIA568A Category 5, 24AWQ,
Twist Pair 0.51mm/24 168 46 58
In case of using Cable with shield, connect the shield through film resistance of metal that 470kΩ,
1/4W (wattage), Degree.
4.2. ELECTRICAL WIRING
1. Turn OFF the main power switch to the wiring that connects to HARC70-CE1 and water chiller
before electrical wiring.
2. Connect the wiring following the below Table. The number in Table indicates the refererence of
sub-chapter 4.1 “Wiring Method” (page 4/6).
Section No Wiring Method Remark
1 Ø 220-240V Power
Source — HARC70-CE1 p
Power
Line
Earthing Wire q
Upper System —
HARC70-CE1 rNon-polar
Control
Circuit
HARC70-CE1 —
Water Chillers sNon-polar
AC / AC / E
AC / AC / E
LON / H-LINK
LON / H-LINK

5
/
8TEST RUN
5. TEST RUN
NOTE:
The mark “Ù”indicates position of dips switches.
5.1. SETTING OF DIP SWITCH
1. Open the covers of HARC70-CE1 for lower
cover and setting of Dip Switch at the near
side.
2. By setting of 8 Pins Dip Switch ad shown
below, normal operation is available.
Setting of 8 Pins Dip Switch
5.2. TEST RUN
1. Check to ensure that “Electrical Wiring” and “Setting of Dip Switch” are completed.
2. Turn ON the power source according to the following.
-Turn ON the power source for Water Chiller Unit.
-Turn ON the power for HARC70-CE1.
3. Check the operation of HARC70-CE1.
Step 7-Segment Display Condition Remarks
1—Power source OFF
2 End of system initialization
3 Under Checking of Water Chiller
connection Q’ty
4 Normal Transmission between
HARC70-CE1 and Water Chillers
4. Check the quantity of connected Water Chiller.
The quantity of the connected Water Chiller is indicated by pressing Push Switch (PSW[M.CLR])
with “00” on 7-Segment.
5. As described above, Test Run of HARC70-CE1 will be finished.
5.3. INDICATION OF ABNORMALITY
Abnormality can be checked by indication of 7-Segment for HARC70-CE1.
7-Segment
Display Phenomenon Content of Abnormality Remarks
Install Abnormal
of connection with
Water Chillers
Telecommunication Failure
with Water Chillers.
Abnormal
Communication
with Water Chillers
No response for 70 seconds
after one Telecommunication
with Water Chillers.
Abnormal
Communication
with Water Chillers
No response for 180 seconds
after one Telecommunication
with Water Chillers.
DSW5
DSW8
ON ON

SERVICE AND CHECKING FOR HARC70-CE1 6
/
9
ENGLISH
6. SERVICE AND CHECKING FOR HARC70-CE1
6.1. SELF CHECKING FOR HARC70-CE1
Abnormality can be checking by indication of 7-Segment of HARC70-CE1 according to procedures
below.
1. TURN 8 Pins DSW ON power by leaving all 8 Pins DSW at the “OFF”. (The 7-Segment is OFF)
2. TURN only No.1 pin of 8 Pins DSW at the “ON” side.
3. TURN only No.1 pin at “OFF” side and TURN No.2 pin at the “ON” side.
(When doing this checking, please set End Terminal Resistance on H-LINK.)
4. TURN only No.2 pin at “OFF” side and TURN No.3 pin at the “ON” side.
5. TURN only No.3 pin at “OFF” side and TURN No.4 pin at the “ON” side.
Normal
8 Pins DSW
S202
ON
Indication 7-Segment
Abnormal
8 Pins DSW
S201 ×
ON ×
,
Indication 7-Segment
Normal Abnormal
8 Pins DSW
S201
ON
,
Indication 7-Segment
This pin quantity set at the
“ON” side on the 8 Pins dip
switch
‘S202’ of 1∼5 pin indicated at
the right side. 7-Segment
indicates “3” at the left side.
8 Pins DSW
ON
S201
#
Indication 7-Segment
The above indication is repeated.
8 Pins DSW
S201
ON

6
/
10 SERVICE AND CHECKING FOR HARC70-CE1
6.2. ACTION WHEN ABNORMAL
The following table indicates possible trouble-shooting upon the abnormal operation in unit.
Power source of HARC70-CE1 should be turned OFF, before starting of check.
Trouble-shooting
Nº Phenomenon Items to be checked Actions
Check if power source cable is connected. Connect the power source cable
correctly.
Check if power source is supplied.
Power source voltage should be
measured. If the measured voltage
shows outside of normal range of
100~240±10%[V], wire systems and
wiring procedures should be
inspected and examined.
Check if LED (POW) is lit.
Lighting OFF indicates that there is
possibility of the failure of internal
power source. Contact to your
nearest service centre.
Check if terminal screws are loosened. Ensure to retighten the terminal
screws.
Check (PAC) for transmission display is lit.
Check the transmission circuit of
chiller unit by the self-inspection
function. And check the circuit if
transmission circuit of chiller unit is
operating normally.
Check if (IRP) for transmission display is lit.
Check the upper transmission
circuit by self-inspection function.
And check the circuit if transmission
circuit of upper equipment is
operating normally.
1
Despite of power
source is ON, there is
no apparent operation
in HARC70-CE1.
(No indication on
7-segment is shown)
Check if (IRP) for transmission display
is regularly blinked.
(1~2sec interval)
Lighting OFF indicates that there is
possibility of the failure of internal
power source. Contact to your
nearest service centre.
Check if the address of the chiller unit is set
correctly.
Address should be re-set with
referring to the installation
maintenance manual and
operation manual.
Check if transmission cable with chiller unit is
disconnected. Connection of wire should be
examined.
Check if manufacturer’s specified transmission
cable connected with chiller unit is used. Use Twist pair cable (0.75mm2).
Check if transmission cable connected with chiller
unit is wired along the power source wire. Provide a space of at least 150mm
between wires.
Check if end terminal resistance and quantity on the
transmission cable between chiller unit and
HARC70-CE1 are set correctly with chiller unit.
Only one end resistance should be
set in one system. (Resistance
between wire is approx. 150Ω.)
Check if transmission circuit is operating normally
upon the self-inspection. End resistance should be set to the
transmission wire of chiller unit.
Check if the power source of chiller unit is ON. Chiller unit should be turned ON.
Check if transmission cable between chiller unit and
HARC70-CE1 are disconnected. Connection of wiring should be
examined.
Check if (PAC) for transmission display is ON.
Check transmission circuit of chiller
unit by self-inspection. And confirm
if transmission circuit of chiller unit
is operating normally.
2
Despite of power
source is ON,
Apparently, none of
reaction is seen.
(It shows “11” on the
7-segment.) After
displayed “00” on the
7-segment with check
mode, the actual
Chiller unit quantity
shows unconformable
to address.
Check if LED (PAC) for transmission display is OFF.
Check transmission circuit of chiller
unit by self-inspection. And confirm
if transmission circuit of chiller unit
is operating normally.

SERVICE AND CHECKING FOR HARC70-CE1 6
/
11
ENGLISH
NºPhenomenon Items to be checked Actions
Check if manufacturer’s specified transmission
cable connected with chiller unit is used. Use Twist pair cable (0.75mm2).
Check if transmission cable connected with chiller
unit is wired along power source wire. Provide a space of at least 150mm
between wires.
Check if end terminal resistance and quantity on the
transmission cable between chiller unit and
HARC70-CE1 are set correctly with chiller unit.
Only one end resistance should be
set in one system. (Resistance
between wire will be approx. 150Ω.)
Check if transmission circuit is operating normally
upon the self-inspection. End resistance should be set to the
transmission wire of chiller unit.
3Indication of 7-segment
shows “44”.
(Only HARC70-CE1)
Check if the power source of chiller unit is ON. Chiller unit should be turned ON.
Check if manufacturer’s specified transmission
cable connected to chiller unit is used. Use Twist pair cable (0.75mm2).
Check if transmission cable connected with chiller
unit is wired along power source wire. Provide a space of at least 150mm
between wires.
Check if end terminal resistance and quantity on
the transmission cable between chiller unit and
HARC70-CE1 are set correctly with chiller unit.
Only one end resistance should be
set in one system. (Resistance
between wire will be approx. 150Ω.)
Check if transmission circuit is operating normally
upon the self-inspection. End resistance should be set to the
transmission wire of chiller unit.
4
Indication of 7-segment
shows “61”. After
identify the address
of chiller unit having
abnormal transmission
with Check mode,
check as described in
the right side to the
appropriate chiller unit. Check if the power source of chiller unit is ON. Chiller unit should be turned ON.
5
Control function of
chiller unit over the
upper equipment does
not activate. (entire
control)
Check if chiller unit is set in local mode. Chiller unit should re-set to
remote mode.
Check if manufacturer’s specified transmission
cable connected to chiller unit is used. Use Twist pair cable (0.75mm2).
Check if transmission cable connected with chiller
unit is wired along power source wire. Provide a space of at least 150mm
between wires.
Check if end terminal resistance and quantity on
the transmission cable between chiller unit and
HARC70-CE1 are set correctly with chiller unit.
Only one end resistance should be
set overall. (Resistance between
wire will be approx. 150Ω.)
Check if transmission circuit is operating normally
upon the self-inspection. End resistance should be set to the
transmission wire of chiller unit.
6
Indication of 7-segment
of control PCB in chiller
unit shows “03” alarm.
(transmission
abnormality between
HARC70-CE1
and Chiller unit)
Check if the power source of HARC70-CE1 is ON. HARC70-CE1 should be turned ON.
6.3. PERIODICAL MAINTENANCE
Periodical Maintenance is need to keep a best condition of HARC70-CE1.
Ambient Temperature
-Check the cabinet the internal temperature of HARC70-CE1 is too high or near.
-Check the temperature of HARC70-CE1 is too high.
-Check dusts, fine metal powder, wires exit or not in the cabinet.
Display
-Check the Display is LED (POW).
-Check LED for transmission state (PAC,IRP) is ON/OFF.
-Check 7-Segment does not indicate except “00”.
Attachment, Connected Part
-Check to ensure that the mounting screws, power, transmission cable screws are
tightened firmly.
-Check to ensure that the other screws are tightened firmly.
ÕWARNING:
When cleaning HARC70-CE1, do not use thinner to avoid color change and melting of the
painted surface.


RESUMEN DE SEGURIDAD 1
/
13
ESPAÑOL
1. RESUMEN DE SEGURIDAD
ÕADVERTENCIA:
-Este adaptador de conexión BMS se utiliza con las unidades de enfriadores de agua HITACHI.
-No coloque el adaptador en lugares donde pueda existir una salida de gas inflamable o neblina
de aceite, ya que podría producirse un incendio, deformación de maquinaria, corrosión o roturas.
-en lugares donde pueda acumularse neblina o vapor de aceite.
-en lugares donde se forme gas de sulfuro como manantiales térmicos.
-Si se instalan cerca de los enfriadores de agua equipos médicos generadores de ondas
electromagnéticas, preste atención a la dirección de la radiación para evitar que llegue a los
enfriadores de agua.
-Se recomienda dejar un espacio mínimo de 3 metros entre el HARC70-CE y los equipos
médicos, aparatos de radio, etc.
-No se debe colocar el adaptador en un lugar donde quede expuesto a la luz directa del sol.
-Acción de instalación:
-Este adaptador se debe instalar correctamente siguiendo las instrucciones de este manual
para evitar el riesgo de descarga eléctrica, incendio o lesiones en caso de caerse el
HARC70-CE1.
-Asegúrese de que el adaptador está fijado firmemente para evitar el riesgo de lesiones
en caso de caerse.
-Para evitar el riesgo de incendio, no instale el adaptador en lugares donde exista la
posibilidad de que se generen o fluyan gases inflamables.
-Trabajos eléctricos:
-Para evitar el riesgo de descarga eléctrica, los trabajos debe realizarlos un electricista
cualificado.
-Para evitar el riesgo de descarga eléctrica y de incendio, el cableado eléctrico se debe
llevar a cabo de acuerdo con la normativa local.
-Para evitar el riesgo de descarga eléctrica y de incendio, utilice el cable indicado para
conectar las unidades de enfriadores de agua. (Modelo: HARC70-CE1)
-Apague la fuente de alimentación antes de realizar los trabajos de cableado eléctrico
cuando esté abierta la cubierta del HARC70-CE1.
2. ESTRUCTURA DEL SISTEMA
2.1. ESTRUCTURA DEL SISTEMA
En la Figura 1.1 se muestra la estructura interna de la conexión BMS utilizando el HARC70-CE1.
Lea este manual junto con el “Manual de instalación y funcionamiento” de otras unidades que estén
conectadas. Por lo que respecta a los demás equipos que forman el sistema, lea el manual de
manejo que se adjunta a cada uno de ellos.
(*1) LONWORKS ® es una marca comercial registrada de Echelon Corporation en EE.UU. y en otros países.
Fig. 1.1. Ejemplo de estructura del sistema
Sistema de control superior (BMS)
El margen que
proporciona Hitachi
LonWorks ® (*1) Red
HARC70-CE1
Unidad enfriadora
HARC70-CE1
Unidad enfriadora Unidad enfriadora Unidad enfriadora Unidad enfriadora

2
/
14 ESTRUCTURA DEL SISTEMA
2.2. NOMBRE DE LAS PIEZAS
En la Tabla 1.2 se indica el nombre de cada uno de los componentes del HARC70-CE1.
Fig. 1.2. Nombre de cada uno de los componentes del HARC70-CE1
Fig. 1.3. Aspecto exterior del HARC70-CE1
Indicación de fuente de alimentación LED
La luz está encendida cuando se suministra
alimentación eléctrica.
LED indicador de transmisión
Estado de la transmisión con las unidades
de enfriadores de agua.
Indicación de transmisión del LED del sistema su
p
erior
Estado de la transmisión con el e
q
ui
p
o de control su
p
erior
POW SISTEMA DE
CONTROL G/W
HITACHI
IRP PAC
Indicación de tipo
Cubierta superior
Cubierta inferior

ESTRUCTURA DEL SISTEMA 2
/
15
ESPAÑOL
2.3. NOMBRES DE LAS PARTES DE LOS TERMINALES Y POSICIONES DE AJUSTE
DE LOS CONMUTADORES DIP
Los nombres y las funciones se indican en la Figura 1.4. En la figura se muestra el HARC70-CE1.
Lea la sección 4 para obtener información sobre el método de conexión de cada terminal y el ajuste
de los conmutadores DIP.
Fig. 1.4. Nombres de los terminales y parte de ajuste de los conmutadores DIP
(1) DSW de 8 patillas [S202]
Lea la sección 5.1 “Ajuste de los conmutadores DIP” para ajustar la dirección de HARC70-CE1.
Los conmutadores DSW de 8 patillas se utilizan para fines de autoinspección. Para obtener más detalles,
consulte la sección 6.1 “Autoinspección del HARC70-CE1”.
(2) DSW de 8 patillas [S201]
Lea la sección 5.1 “Ajuste de los conmutadores DIP” para obtener detalles acerca del funcionamiento
del HARC70-CE1.
(3) Pantalla de 7 segmentos
Lea las secciones 5.2 “Prueba de funcionamiento” y 5.3 “Indicación anómala” para obtener detalles
acerca de la pantalla de 7 segmentos.
8P DSW [S202]
Conmutador DIP para
ajustar el sistema
HARC70-CE1
PSW [M.CLR]
Pulsador para
comprobar la cantidad
de la unidad conectada
8P DSW [S201]
Conmutador DIP para
ajustar las funciones
del HARC70-CE1
Pantalla de
7 segmentos
Estado actual del
HARC70-CE1
Terminal de fuente
de alimentación para
conectar a una fuente
de alimentación
de 220~240 Vca
Terminal de
conexión a tierra
para la puesta a
tierra del limitador
de sobretensiones
Terminal para transmisión
del sistema superior para
conectar la línea de
transmisión para el control
del sistema superior
Terminal para
transmisión
de la unidad
para conectar
las unidades
de enfriadores
de agua
POW SISTEMA DE
CONTROL
G/W
MCLR LON-SERV.
AC / AC / E LON / H-LINK
S201 S202 LON H-LINK
HITACHI
Patilla de servicio
p
ara LonWorks
PSW [LON-SERV]
IIRP PAC

3
/
16 INSTALACIÓN
2.4. ESPECIFICACIONES
Tabla 2.1. Especificaciones de hardware
Elemento Especificaciones
Fuente de alimentación 220/240 Vca±10% (50/60 Hz)
Consumo de energía 10 W (máx.)
Dimensiones exteriores W170×L75×H80 (mm)
Peso 15,52oz
Tipo de instalación Interior
Temperatura 0~45°C
Humedad 10~80°C (sin rocío)
Tabla 2.2. Especificaciones de telecomunicaciones de los enfriadores de agua
Elemento Especificaciones
Unidad de comunicación Enfriadores de agua
Línea de comunicación Sistema no polar de dos cables
Sistema de telecomunicaciones Funcionamiento semidúplex
Sistema síncrono Método de comunicación asíncrona
Velocidad de telecomunicación 9600 bps
Longitud del cableado 1.000 metros (longitud total)
Número de conexiones
Modelo: HARC70-CE1 Unidad de enfriador de agua x 4
Tabla 2.3. Especificaciones de telecomunicaciones del sistema superior
Elemento Especificaciones
Unidad de comunicación Equipo de control superior
Protocolo de transmisión Protocolo Lon Talk (*1)
Método de acceso Sistema CSMA/CD persistente previsto
Sistema de codificación Código Manchester diferencial
Velocidad de telecomunicación 78.000 bps
Longitud del cableado 1.000 metros (longitud total del bus)
(*1) Lon Talk es una marca comercial registrada de Echelon Corporation en EE.UU. y en otros países.
3. INSTALACIÓN
El procedimiento que se debe seguir desde la instalación hasta la comprobación de la fuente
de alimentación se explica en laTabla 3.1.
Tabla 3.1. Procedimientos de manejo
Nº Elemento Descripción
1Selección del lugar
de instalación Un aspecto a tener en cuenta en el caso
de un establecimiento
2 Instalación Método de instalación y aspecto a tener en cuenta
3 Modo de conexión del cableado Método de cableado de la alimentación eléctrica
y la comunicación
4 Ajuste de los conmutadores DIP Precaución que debe observarse al ajustar los
conmutadores DIP
5 Fuente de alimentación Puntos que se han de comprobar

INSTALACIÓN 3
/
17
ESPAÑOL
3.1. INSTALACIÓN
Selección del lugar de instalación. Seleccione un lugar que cumpla las siguientes condiciones.
-uno de los lugares descritos en la sección de este manual titulada “Antes de la instalación”.
-en un armario metálico conectado a tierra y cerrado herméticamente.
3.2. PROCEDIMIENTOS DE INSTALACIÓN
-Instale el HARC70-CE1 con el cuadro de terminales de tornillo en la parte inferior.
-Los métodos de instalación son los siguientes:
a) Montaje en un raíl DIN (35 mm) (raíl DIN: suministrado por el instalador)
Parte superior
Parte inferior
SISTEMA DE CONTROL
HITACHI G/W
Terminal
de tornillo
SISTEMA DE CONTROL
HITACHI G/W
(Instalación horizontal)
1. Enganchar el extremo del HARC70-CE1
a la parte superior del raíl DIN.
2. Presionar el otro extremo contra el raíl
hasta que el HARC70-CE1 quede
encajado.
Procedimiento:
Instalación Correcta Instalación Incorrecta

4
/
18 MÉTODO DE CONEXIÓN DEL CABLEADO
b) Método de fijación mediante tornillos (M4) (tornillos: (suministrados por el instalador)
4. MÉTODO DE CONEXIÓN DEL CABLEADO
ÕATENCIÓN:
-Antes de realizar el cableado, lea atentamente la sección RESUMEN DE SEGURIDAD
de este manual.
-Este trabajo lo debe realizar una persona cualificada.
4.1. INSTALACIÓN DEL CABLEADO
1. Para el HARC70-CE1 se necesitan una línea
de transmisión para los enfriadores de agua
y una línea de transmisión para el equipo
de control.
2. Método de cableado.
Nº Elementos que
deben conectarse Especificaciones
del cableado
1Fuente de
alimentación de los
enfriadores de agua
220-240 Vca, 2 mm2,
dos núcleos, blindado
2 Cable de tierra Siga las normas locales
3Equipo de control
superior
Siga las instrucciones de la
persona encargada de la
administración del equipo
superior. (*2)
4Línea de
transmisión de los
enfriadores de agua
Cable de par trenzado
1P - 0,75 mm2(*1)
(*1) Siempre se debe utilizar cable de par trenzado.
Cable de conexión: suministrado por el instalador.
1. Abrir las cubiertas superior e inferior
del HARC70-CE1 horizontalmente.
Procedimiento:
3. Cerrar las cubiertas superior
e inferior.
2. Fijar el HARC70-CE1 a la pared mediante
los tornillos (tornillos M4, 2 posiciones).
SISTEMA DE CONTROL
HITACHI G/W
HARC70-CE1
p
Equipo de control
superior
r
Fuente de
alimentación
de 220/240 V
q
s
Unidad de enfriado
r
de agua Unidad de enfriado
r
de agua
Table of contents
Languages:
Other Hitachi Adapter manuals

Hitachi
Hitachi HARC-BX E User manual

Hitachi
Hitachi HX-RIO3 Series User manual

Hitachi
Hitachi BCL-10UA User manual

Hitachi
Hitachi CP-WU5506 User manual

Hitachi
Hitachi airCloud SPX-WFA Quick start guide

Hitachi
Hitachi GVX-CC64GxBX series User manual

Hitachi
Hitachi PSC-6RAD User manual

Hitachi
Hitachi GVX-CC64G*BX User manual

Hitachi
Hitachi BCL-10UB User manual

Hitachi
Hitachi HX-RIO3 Series User manual