HK Instruments DPT-PRIIMA-MOD Series User manual

Copyright HK Instruments 2022 www.hkinstruments. Installaonversion1.02022
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-Priima-MOD Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
Thank you for choosinganHK InstrumentsDPT-Priima-MOD series
transmier.DPT-Priima-MODisamulfunconalhighaccuracytrans-
mierformeasuringvolumeow,velocity,andstacanddierenal
pressure.Itisdesignedforcleanroomsandotherdemandingapplica-
ons.Themeasurementscanbereadandtheconguraondonevia
Modbuscommunicaon.DPT-Priima-MODcanalsobeusedwithsev-
eraldierentmeasurementprobessuchasFloXact™orpitottube,and
airdampers.
DPT-Priima-MODmodelscomewithalocaldisplayandanautomac
zeropointcalibraon.Calibraoncercateavailableasanopon.
DPT-Priima-MODiscommonlyusedinapplicaonsrequiringhigh
measurementaccuracy:
•monitoringpressureincleanrooms
•monitoringpressuredierenceacrossthebuildingenvelope
•monitoringpressureandow
SPECIFICATIONS
Performance
Measurement ranges:
±120 Pa*, ±240 Pa, ±620 Pa, ±1240 Pa, ±2490 Pa
(selectableviamenuormodbus)
*defaultrange
Accuracy (at applied pressure):
0.4 % ±0.4 Pa
(Including:generalaccuracy,linearity,hysteresis,long
termstability,andrepeonerror)
Overpressure:
Proofpressure:10kPa
Burstpressure:30kPa
Zero point calibraon:
Automacautozero,manualpushbuonorviaModbus
register
Response me:
0.4−20s,selectableviamenuorviaModbusregister
(63%ofthechange)
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
 CodingSystem:8-bitbinary
 BitsperByte:
1 start bit
  8databits,leastsignicantbitsent
  rst
  1bitforparity
  1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Pressure units (select via menu):
Pa,kPa,mbar,inWC,mmWC,psi
Flow units (select via menu):
Volume:m3/s,m3/h,cfm,l/s
Velocity:m/s,/min
Measuring element:
MEMS,noow-through
Environment:
Operangtemperature:-5...50°C
Temperaturecompensatedrange0...50°C
Storagetemperature:-40...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:102.0x71.5x36.0mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case:ABS
Lid:PC
Pressurengs:Brass
Tubing:Silicone
Protecon standard:
IP54
Display
2-linedisplay(12characters/line)
 Line1:Volumeorvelocitymeasurement
 Line2:Pressuremeasurement
Size:46.0x14.5mm
Electrical connecons:
4-screwterminalblock
Wire:0.2–1.5mm2(16–24AWG)
Cable entry:
Strainrelief:M16
Knockout:16mm
Pressure ngs
Maleø5.2mm
+Highpressure
-Lowpressure
Electrical
Supply voltage:
24 VAC or VDC ± 10 %
Power consumpon:
<1W
<2.2WduringAZ-calibraon
Output signal:
viaModbus
Conformance
Meetsrequirementsfor:
  CE:  UKCA:
EMC:  2014/30/EU S.I.2016/1091
RoHS:  2011/65/EU S.I.2012/3032
WEEE:  2012/19/EU S.I.2013/3113
APPLICATIONS
INTRODUCTION WARNING
RoHS
COMPLIANT
Copyright HK Instruments 2022 www.hkinstruments. Installaonversion1.02022
DPT
SCHEMATICS
DIMENSIONAL DRAWINGS
Figure 1a - Surface mounng
MOUNTING THE DEVICE CONTINUED
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
Conneconfordisplay
Terminalblock
Menubuons
ZERO
A
24V
GND
SELECT
UP
DOWN
B
A
BPressuresensor
Led
DPT
4.3
Thepressuretubesareconnectedtoaowmeasurementprobe(i.e.FloXact),ortothe
measurementportsspeciedbythefanmanufacturer.PleaseseetheFloXactinstallaon
guideorthefanmanufacturer’stechnicalspecicaonsformoreinformaon.
YES NO NO
INSTALLATION
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefand
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
STEP 2: WIRING DIAGRAMS
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable.
2)Connectthewiresasshowningure2.
3)Tightenthestrainrelief.
ItisrecommendedtouseshieldedtwistedpaircableforModbuscabling.
Thecableshieldmustbeearthedonlyinonepoint,normally,attheendof
themaincable.
Figure 2 - Wiring diagram
B
A
24 V
GND
+ Power supply
24 VDC / 24 VAC
Modbus
STEP 1: MOUNTING THE DEVICE
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Pressure
Flow
Static pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected
Copyright HK Instruments 2022 www.hkinstruments. Installaonversion1.02022
CONFIGURATION CONTINUED
STEP 3: CONFIGURATION
3)If
Commonprobe
selected:selectmeasurementunitsusedinthe
formula(akaFormulaunit)(i.e.l/s)
NOTE:Theowunit
none
isselectedbydefaultandthedisplay
showsonlythepressurereading.
1)AcvatethedeviceMenubypushingtheselectbuon
 for2seconds
2)Selectthefunconingmodeoftheowmeter:
-Select
Manufacturer
whenconnecngDPT-Priima-MODtoa
fanwithpressuremeasurementpoints
-Select
Commonprobe
whenusingDPT-Priima-MODwitha
commonmeasurementprobethatfollowstheformula:
 q=k∙√∆P
(i.e.FloXact)
MANUFACTURER
Common probe
SELECT
UP
DOWN
Common probe Flakt Woods
SELECT
UP
DOWN
FORMULA UNIT
l/s
SELECT
UP
DOWN
4)SelectK-value
a.Ifmanufacturerselectedinstep2:
EachfanhasaspecicK-value.SelecttheK-valuefromfanmanufac-
turer’sspecicaons.
Manufacturer: K-value:
Fläktwoods k=0.3...99
Rosenberg k=37...800
Nicotra-Gebhardt k=50...4700
Comefri  k=10...2000
Ziehl  k=10...1500
ebm-papst k=10...1500
Gebhardt k=50...4700
Nicotra  k=50...5300
8)Responseme:Selectresponsemebetween0.4–20s.
RESPONSE TIME
20 s
SELECT
UP
DOWN
12)Pushselectbuontosavechangesandtoexitmenu.
SELECT
EXIT MENU
SELECT
b. If
Commonprobe
selectedinstep1:
Each common probe has a specic K-value. Select the K-value from
commonprobemanufacturer’sspecicaons.
AvailableK-valuerange:0.001...9999.000.
K-VALUE
9000.000
SELECT
UP
DOWN
9)SelecttheaddressforModbus:1...247.
10)Selectthebaudrate:9600/19200/38400.
ADDRESS
99
SELECT
UP
DOWN
BAUD RATE
9600
SELECT
UP
DOWN
11)Selecttheparitybit:None/Even/Odd.
PARITY BIT
NONE
SELECT
UP
DOWN
STEP 4: ZEROING THE DEVICE
NOTE! Always zero the device before use.
Tozerothedevicethreeoponsareavailable:
1)Autozerocalibraon(manualzeroingnotrequired)
2)ManualPushbuonzeropointcalibraon
3)ViaModbusregister
1)Autozerocalibraon
Autozerocalibraon(-AZ)isanautozerofunconintheformofan
automaczeroingcircuitbuiltintothePCBboard.Theautozerocali-
braonelectronicallyadjuststhetransmierzeroatpredetermined
meinter vals(every10minutes).Thefunconeliminatesalloutput
signaldriduetothermal,electronicormechanicaleects,aswellas
theneedfortechnicianstoremovehighandlowpressuretubeswhen
performinginialorperiodictransmierzeropointcalibraon.The
autozeroadjustmenttakes4secondsaerwhichthedevicereturnsto
itsnormalmeasuringmode.Duringthe4secondadjustmentperiod,
theoutputanddisplayvalueswillfreezetothelatestmeasuredvalue.
Transmiersequippedwiththeautozerocalibraonarevirtuallymain-
tenancefreeandmanualzeroingisnotrequired.
5)Selectpressureunitfordisplay:Pa,kPa,mbar,inWC,mmWC,psior
none.
PRESS.UNIT
Pa
SELECT
UP
DOWN
7)Selectowunitfordisplay:
Flowvolume:m3/s,m3/h,cfm,l/s,none(default)
Velocity:m/s,f/min,none
FLOW UNIT
m3/s
SELECT
UP
DOWN
6)Selectdesiredpressurerange:
±120 Pa, ±240 Pa, ±620 Pa, ±1240 Pa, ±2490 Pa
PRESS. RANGE
±120 Pa
SELECT
UP
DOWN
Copyright HK Instruments 2022 www.hkinstruments. Installaonversion1.02022
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsoraproduconawisfound,thesellerisobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
byrepairing the defecve productor bydelivering free of chargeto
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
andinstallaonworknotdonebytheseller.Theseleconofmateri-
alsfordevicespronetocorrosionisthebuyer’sresponsibility,unless
otherwise is legally agreed upon. Should the manufacturer alter the
structureofthedevice,thesellerisnotobligatedtomakecomparable
changestodevicesalreadypurchased.Appealingforwarrantyrequires
thatthebuyerhascorrectlyfullledhis/herduesarisenfromthede-
liveryandstatedinthecontract.Thesellerwillgiveanewwarrantyfor
goodsthathavebeenreplacedorrepairedwithinthewarranty,how-
everonlytotheexpiraonoftheoriginalproduct’swarrantyme.The
warrantyincludestherepairofadefecvepartordevice,orifneeded,
anewpartordevice,butnotinstallaonorexchangecosts.Underno
circumstanceisthesellerliablefordamagescompensaonforindirect
damage.
2)ManualPushbuonzeropointcalibraon
NOTE:Supplyvoltagemustbeconnectedatleastonehourpriorto
zeropointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)PushdownthezerobuonunltheLEDlight(red)turnsonand
thedisplayreads“zeroing”(displayopononly).(seegure3)
c)Thezeroingofthedevicewillproceedautomacallyin4seconds.
ZeroingiscompletewhentheLEDturnso,andthedisplayreads
0(displayopononly).
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
3)ViaModbusregister
Makesurethereisnopressureintheductwhenthezeroingisdone
viaModbusregister.
b)Pushdownthezerobuon(joysck)unltheLEDlight(red)
turnsonandthedisplayreads“zeroing”(displayopononly).(see
Figure6)
c)Thezeroingofthedevicewillproceedautomacally.Zeroingis
completewhentheLEDturnso,andthedisplayreads0(display
opononly).
d)Reinstallthepressuretubes,ensuringtheHighpressuretubeis
connectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
Pressdownbuon
LEDturnsON
Displayreads“Zeroing”
LED
Figure 3
ZEROING THE DEVICE CONTINUED
STEP 5: MODBUS REGISTERS
Register Parameter descripon Data Type Value Range
3x0001 Programversion 16 bit 0...9900 0,00...99,00
3x0002 PressurereadingPa 16 bit -24900...24900* ± 2490.0 Pa
3x0003 PressurereadingkPa 16 bit -24900...24900* ±2.4900kPa
3x0004 Pressurereadingmbar 16 bit -24900...24900* ± 24.900 Pa
3x0005 PressurereadingmmWC 16 bit -25400...25400* ±253.91mmWC
3x0006 PressurereadinginWC 16 bit -10000...10000* ±10.000inWC
3x0007 Pressurereadingpsi 16 bit -3610...3610* ±0.3611psi
3x0008 Flowm3/s 16 bit 0...10000 0...100m3/s
3x0009 Flowm3/h 16 bit 0...30000 0...30000m3/h
3x0010 Flowcfm 16 bit 0...30000 0...30000cfm
3x0011 Flowl/s 16 bit 0...3000 0...3000l/s
3x0012 Velocitym/s 16 bit 0...1000 0...100m/s
3x0013 Velocityf/min 16 bit 0...5000 0...5000f/min
Funconcode04-Readinputregister
MODBUS REGISTERS CONTINUED
Funconcode05-Writesinglecoil
Register Parameter descripon Data Type Value Range
0x0001 Zeropointcalibraon Bit 0 0...1 On-O
WARRANTY POLICY
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
*)Thevalueandrangearedeterminedbytheselectedpressurerange±120Pa,±240Pa,±620Pa,
±1240Pa,±2490Pa.Thevaluesshowninthetablewhenthelargestareaisselected.
Funcon code 03 - Read input holding register, Funcon code 06 -
Writesingleregister,Funconcode16-Writemulpleregisters
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16 bit 0...8
0=FläktWoods,1=Rosenberg,
2=Nicotra-Gebhardt,3=Comefri,
4=Ziehl,5=ebm-papst,6=Gebhardt,
7=Nicotra,8=Commonprobe
4x0002 Formulaunit(ifmanufacturer
selecon=commonprobe) 16 bit 0...5 0:m3/s,1:m3/h,2:cfm,3:l/s,
4:m/s,5:f/min
4x0003 K-factorinteger 16 bit 0...9999 0...9999
4x0004 K-factordecimal 16 bit 0...999 0...999
4x0005 Responseme 16 bit 0...20 0=0.4s,1=1s,2=2s...20=20s
4x0006 PressureRange 16 bit 0...4 0=±120Pa,1=±240Pa,2=±620Pa,
3=±1240Pa,4=±2490Pa

Other HK Instruments Measuring Instrument manuals

HK Instruments DPG Series User manual

HK Instruments

HK Instruments DPG Series User manual

HK Instruments CDT 2000 Duct Series User manual

HK Instruments

HK Instruments CDT 2000 Duct Series User manual

HK Instruments DPT-R8 Series User manual

HK Instruments

HK Instruments DPT-R8 Series User manual

HK Instruments MM Series User manual

HK Instruments

HK Instruments MM Series User manual

HK Instruments DPI+/-500-D User manual

HK Instruments

HK Instruments DPI+/-500-D User manual

HK Instruments DPT100 User manual

HK Instruments

HK Instruments DPT100 User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments PHM-V1 User manual

HK Instruments

HK Instruments PHM-V1 User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

HK Instruments DPG Series User manual

HK Instruments

HK Instruments DPG Series User manual

Popular Measuring Instrument manuals by other brands

Velleman DVR8T3 Quick installation guide

Velleman

Velleman DVR8T3 Quick installation guide

NI SCXI-MS100 installation guide

NI

NI SCXI-MS100 installation guide

BEHA UNITEST 93560 instruction manual

BEHA

BEHA UNITEST 93560 instruction manual

Aurora TAVIS TAV-10 user guide

Aurora

Aurora TAVIS TAV-10 user guide

Shenzhen CTB20A quick start guide

Shenzhen

Shenzhen CTB20A quick start guide

Honeywell DR 4300 Replacement Instruction

Honeywell

Honeywell DR 4300 Replacement Instruction

Leica LS10 quick guide

Leica

Leica LS10 quick guide

Hameg HM5014-2 Service manual

Hameg

Hameg HM5014-2 Service manual

Circutor CIRWATT Series installation manual

Circutor

Circutor CIRWATT Series installation manual

Chauvin Arnoux F 65 user manual

Chauvin Arnoux

Chauvin Arnoux F 65 user manual

Raytech T-REX instruction manual

Raytech

Raytech T-REX instruction manual

Keysight SR101EDUA user guide

Keysight

Keysight SR101EDUA user guide

MFJ MFJ-935C instruction manual

MFJ

MFJ MFJ-935C instruction manual

ABB EV3 user manual

ABB

ABB EV3 user manual

Rachio Wireless Flow Meter user manual

Rachio

Rachio Wireless Flow Meter user manual

FRIENDCOM PULSE915-LRW Configuration guide

FRIENDCOM

FRIENDCOM PULSE915-LRW Configuration guide

Hanna Instruments HI771 instruction manual

Hanna Instruments

Hanna Instruments HI771 instruction manual

Endress+Hauser Levelflex FMP51 operating instructions

Endress+Hauser

Endress+Hauser Levelflex FMP51 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.