manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell Notifier XP6-R User manual

Honeywell Notifier XP6-R User manual

Other Honeywell Control Unit manuals

Honeywell ADEMCO 4229 Assembly instructions

Honeywell

Honeywell ADEMCO 4229 Assembly instructions

Honeywell S7800A1167 User manual

Honeywell

Honeywell S7800A1167 User manual

Honeywell VRN Series User manual

Honeywell

Honeywell VRN Series User manual

Honeywell S89E User manual

Honeywell

Honeywell S89E User manual

Honeywell VISTA User manual

Honeywell

Honeywell VISTA User manual

Honeywell Velociti AOM-2RF User manual

Honeywell

Honeywell Velociti AOM-2RF User manual

Honeywell CentraLine CLIOL822A Operation manual

Honeywell

Honeywell CentraLine CLIOL822A Operation manual

Honeywell 4286 Setup guide

Honeywell

Honeywell 4286 Setup guide

Honeywell BCU 370 Manual

Honeywell

Honeywell BCU 370 Manual

Honeywell D04FM User manual

Honeywell

Honeywell D04FM User manual

Honeywell Kromschroder GIK Series User manual

Honeywell

Honeywell Kromschroder GIK Series User manual

Honeywell DR 300 User manual

Honeywell

Honeywell DR 300 User manual

Honeywell DS05 User manual

Honeywell

Honeywell DS05 User manual

Honeywell ESSER IQ8MCP User manual

Honeywell

Honeywell ESSER IQ8MCP User manual

Honeywell AlarmNet IGSMHS Assembly instructions

Honeywell

Honeywell AlarmNet IGSMHS Assembly instructions

Honeywell AlarmNet 7847i-E Assembly instructions

Honeywell

Honeywell AlarmNet 7847i-E Assembly instructions

Honeywell HS10S User manual

Honeywell

Honeywell HS10S User manual

Honeywell SILENT KNIGHT IDP-Control User manual

Honeywell

Honeywell SILENT KNIGHT IDP-Control User manual

Honeywell TRADELINE VR8345M User manual

Honeywell

Honeywell TRADELINE VR8345M User manual

Honeywell VGF21 Operation manual

Honeywell

Honeywell VGF21 Operation manual

Honeywell VQ400 Series User manual

Honeywell

Honeywell VQ400 Series User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell EXCEL 12 W7704B1002 User manual

Honeywell

Honeywell EXCEL 12 W7704B1002 User manual

Honeywell BA295I User manual

Honeywell

Honeywell BA295I User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

N500-78-00 1 I56-1804-012
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The XP6-R Six Relay Control Module is intended for use in an intelligent alarm
system. Each module is intended for Form-C switching applications, which
do not require wiring supervision for the load circuit. A single isolated set
of dry relay contacts is provided for each module, which is capable of being
wired for either normally open or normally closed for each operation. Each
module has its own address. A pair of rotary code switches is used to set the
address of the first module from 01 to 154. The remaining modules are auto-
matically assigned to the next five higher addresses. Provisions are included
for disabling a maximum of three unused modules to release the addresses to
be used elsewhere. Each XP6-R module also has panel controlled green LED
indicators. The panel can cause the LEDs to blink, latch on, or latch off.
XP6-R Six Relay Control Module
SPECIFICATIONS
Normal Operating Voltage: 15-32VDC
Stand-By Current: 1.90 mA @ 24V
Alarm Current: 32 mA (assumes all six relays have been switched once and all six LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H × 5.8˝W × 1.0˝D
Accessories: CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinets; CAB-4 Series Cabinets
Wire Gauge: 12-18 AWG
Relay Current: 30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
CONTENTS INCLUDE:
(6) 1 × 3 Terminal Blocks
(1) 1 × 4 Terminal Blocks
(2) 11/4˝ (32mm) Stand offs
(4) Machine Screws
(2) Nuts
(1) Shunt (NOTE: For the disable position, not more than one shunt shall be
installed at the same time)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel.
COMPONENTS
Following are descriptions of the XP6-R mounting frameworks. There are two
mounting options for XP6-R modules:
• Up to six XP6-R modules can be installed on a CHS-6 in a CAB-3, CAB-4
or BB-25 cabinet
• One or two XP6-R modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount XP6-R modules in a BB-25, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six XP6-R modules in a single
cabinet row three modules wide and two modules deep.
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
I56-1804-012
RELAY CONTACT RATINGS:
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
INSTALLATION AND MAINTENANCE INSTRUCTIONS
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4 Series cabinets. It
is shipped with two self-threading screws, which are used to fasten the chassis
to the back wall of the cabinet (see Figure 4).
FIGURE 4: MOUNTING THE CHS-6 CHASSIS
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
The BB-XP cabinet comes with the chassis already installed, so no mounting
is necessary.
3. Module Installation
There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will
be installed in front of it. Refer to Figure 5 for instructions. Method two is for
installation of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for method two. All
necessary screws and standoffs are supplied with the modules.
FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE:
2
1
3
Step 1: Insert the bottom of the XP6-R module down into a rear slot on the
chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
The steps in Figures 6A – 6C describe and illustrate module installation when
the rear chassis position and the position in front of it will be filled. Front
position installation is possible only if the rear position is filled with an XP
module.
FIGURE 1. CHS-6 CHASSIS:
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
The BB-XP cabinet has a built-in chassis that will accommodate one or two
XP6-R modules.
FIGURE 2. BB-XP CABINET:
0
1
2
3
4
56789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
4
56789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
The front XP6-R module positions of each chassis are offset below the rear
XP6-R module positions so that all of the status indicators are visible.
Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up
to six XP6-R modules installed on it. Refer to cabinet installation documents
for dimensions.
The BB-XP cabinet houses one or two XP6-R modules on the internal chassis
that is part of the cabinet. Refer to cabinet installation documents for dimen-
sions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in the
back surface of the cabinet.
FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS:
BACKBOX
MOUNTING
HOLES
N500-78-00 2 I56-1804-012
C0236-00
C0236-01
C0235-00
C0234-00
C0249-00
3
2
4
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Make electrical connections by stripping approximately ¼˝ (6.35mm) of
insulation from the end of the wire sliding the bare end of the wire under
the clamping plate, and tightening the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 154). The
remaining modules are automatically assigned to the next five higher
addresses. For example, if the base address switch is set to 28, the next
five modules will be addressed to 29, 30, 31, 32, and 33. DO NOT set
the lowest address above 154, as the other modules will be assigned to
nonexistent addresses.
NOTE: Some panels support extended addressing. In order to set the module
above address 99 on compatible systems, carefully remove the stop on the up-
per rotary switch. If the panel does not support extended addressing, do not
set the lowest addressabove 94.
4. A shunt is provided to disable a maximum of three unused modules.
Modules are disabled from the highest address and work downward. If
two modules are disabled, the lowest four addresses will be functional,
while the highest two will be disabled. For example, if the shunt for Ad-
dress Disable is placed on “two” and the base address switch is set to 28,
the modules will be assigned to 28, 29, 30 and 31.
NOTE: Power must not be applied to the unit when changing functionality of
the shunts.
NOTE: The XP6-R must have power cycled for shunt changes to take effect.
NOTE: All references to power limited represent “Power Limited (Class 2)”.
N500-78-00 3 I56-1804-012
FIGURE 6A. INSTALLATION OF XP6-R MODULE IN A REAR CHASSIS
POSITION, METHOD TWO:
1
Step 1: Install two long standoffs in the lower mounting holes using two 4-40
nuts as shown.
C0225-01
C0226-01
C0249-01
FIGURE 6B.
Step 2: Insert the bottom of the XP6-R module down into a rear slot on the
chassis.
Step 3: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs on the board.
Step 4: Align two 4-40 screws with the two standoffs on the chassis and
tighten.
Step 5: Address and wire the modules according to the instructions in this
manual.
FIGURE 6C. INSTALLATION OF XP6-R MODULE IN FRONT CHASSIS
POSITION:
2
3
1
Step 1: Insert the bottom edge of the XP6-R module down into a front slot of
the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 11/4˝ (31.75mm) standoffs installed on
the rear module.
N500-78-00 4 I56-1804-012
©2014 Notifier
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular instal-
lation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
NOTES:
• The relay contacts on the XP6-R may be connected to either a power-
limited or non power-limited source, this wiring must remain separated
by at least 1/4˝ (6.35 mm) from all power-limited wiring.
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• For easier wiring, assign all power-limited wiring to one side rather than
alternating with non power-limited.
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
N.C.
N.O.
COMMON
ADDRESS 5
N.C.
N.O.
COMMON
ADDRESS 4
N.C.
N.O.
COMMON
ADDRESS 3
N.C.
N.O.
COMMON
ADDRESS 2
N.C.
N.O.
COMMON
ADDRESS 1
N.C.
N.O.
COMMON
ADDRESS 0
– +
– +
SLC
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
6.8"
5.8"
FROM PANEL
OR PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SEE PANEL INSTRUCTION
MANUAL FOR
WIRE REQUIREMENTS
TO NEXT
DEVICE
–+
–
+
–
+
NC
NO
COMMON
RELAY CONNECTIONS
STATUS
INDICATORS
FIGURE 7. WIRING AND PROGRAMMING THE XP6-R MODULE:
C0250-02
PROGRAMMING
The XP6-R module operates with the following Fire Alarm Control Panels:
• AM2020/AFP1010
• AFP-200
• AFP-300/AFP-400
• System 5000 with AIM-200
• AFC-600
• NFS-640
• NFS-3030
The modules are programmed as FRM-1 modules in each system according to
the programming instructions in the appropriate FACP manual.