Honeywell Excel 10 User manual

Other manuals for Excel 10

3

This manual suits for next models

3

Other Honeywell Controllers manuals

Honeywell CENTRALINE EAGLE User manual

Honeywell

Honeywell CENTRALINE EAGLE User manual

Honeywell V4055A User manual

Honeywell

Honeywell V4055A User manual

Honeywell T775A User manual

Honeywell

Honeywell T775A User manual

Honeywell SW2 User manual

Honeywell

Honeywell SW2 User manual

Honeywell S05 Series User manual

Honeywell

Honeywell S05 Series User manual

Honeywell CENTRA LINE EAGLEHAWK NX Installation and operation manual

Honeywell

Honeywell CENTRA LINE EAGLEHAWK NX Installation and operation manual

Honeywell ML6174 Series User manual

Honeywell

Honeywell ML6174 Series User manual

Honeywell 9782 Series User manual

Honeywell

Honeywell 9782 Series User manual

Honeywell ML6161E User manual

Honeywell

Honeywell ML6161E User manual

Honeywell Spyder 5 User manual

Honeywell

Honeywell Spyder 5 User manual

Honeywell T775L Series User manual

Honeywell

Honeywell T775L Series User manual

Honeywell Pneumatic Controls User manual

Honeywell

Honeywell Pneumatic Controls User manual

Honeywell ControLinks R7999A User manual

Honeywell

Honeywell ControLinks R7999A User manual

Honeywell HVC0001 User manual

Honeywell

Honeywell HVC0001 User manual

Honeywell Enhanced Micro TDC 3000 User manual

Honeywell

Honeywell Enhanced Micro TDC 3000 User manual

Honeywell Novar ES3.S Programming manual

Honeywell

Honeywell Novar ES3.S Programming manual

Honeywell R7184A User manual

Honeywell

Honeywell R7184A User manual

Honeywell HCE80R User manual

Honeywell

Honeywell HCE80R User manual

Honeywell UDC3500 Installation and operating instructions

Honeywell

Honeywell UDC3500 Installation and operating instructions

Honeywell UDC3200 series User manual

Honeywell

Honeywell UDC3200 series User manual

Honeywell N20 Series Operation manual

Honeywell

Honeywell N20 Series Operation manual

Honeywell ML7295E User manual

Honeywell

Honeywell ML7295E User manual

Honeywell VU443A Operation manual

Honeywell

Honeywell VU443A Operation manual

Honeywell MS7503A2023 User manual

Honeywell

Honeywell MS7503A2023 User manual

Popular Controllers manuals by other brands

Digiplex DGP-848 Programming guide

Digiplex

Digiplex DGP-848 Programming guide

YASKAWA SGM series user manual

YASKAWA

YASKAWA SGM series user manual

Sinope Calypso RM3500ZB installation guide

Sinope

Sinope Calypso RM3500ZB installation guide

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

Isimet

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS sv-ip5a user manual

LSIS

LSIS sv-ip5a user manual

Airflow Uno hab Installation and operating instructions

Airflow

Airflow Uno hab Installation and operating instructions

ABB ACS580-01 drives Hardware manual

ABB

ABB ACS580-01 drives Hardware manual

Panasonic GM1 Series Reference manual

Panasonic

Panasonic GM1 Series Reference manual

Emerson SW93 owner's manual

Emerson

Emerson SW93 owner's manual

AutoAqua Smart ATO micro SATO-120P manual

AutoAqua

AutoAqua Smart ATO micro SATO-120P manual

Panasonic FP? Positioning Unit RTEX Technical manual

Panasonic

Panasonic FP? Positioning Unit RTEX Technical manual

Alpha IP MIOB 21001 manual

Alpha IP

Alpha IP MIOB 21001 manual

Siemens OpenAir GMA 1 Series Mounting instructions

Siemens

Siemens OpenAir GMA 1 Series Mounting instructions

Surecom SR-629 user manual

Surecom

Surecom SR-629 user manual

Regulus SRS1 T Installation and operation manual

Regulus

Regulus SRS1 T Installation and operation manual

3M MicroTouch EX113 reference guide

3M

3M MicroTouch EX113 reference guide

KUHN TKS user manual

KUHN

KUHN TKS user manual

S&C PMH Instructions for operation

S&C

S&C PMH Instructions for operation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc.
All Rights Reserved
95- 7485- 3
Excel 10
W7763C,D,E CHILLED CEILING
CONTROLLERS
INSTALLATION INSTRUCTIONS
The Excel 10 Chilled Ceiling Controller is available in the
following three models:
1. W7763C—with integral setpoint adjustment,
temperature sensor, and bypass push-button.
2. W7763D—with integral setpoint adjustment only.
3. W7763E—no integral setpoint adjustment, sensor, or
push-button.
The models all have similar housings and mounting pro-
cedures.
IMPORTANT
It is recommended that devices be kept at room
temperature for at least 24 hours before applying
power to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
INSTALLATION
W7763 Chilled Ceiling Controllers can be mounted on a
panel or wall or onto a standard 60-mm wall outlet box using
No. 6 (3.5-mm) screws. See Fig. 1 for outside dimensions
and Fig. 2 for subbase mounting dimensions.
The controller can be mounted in any orientation desired;
however, for thermal reasons, W7763C Controllers must not
be mounted on a ceiling.
Wiring
All wiring must comply with applicable electrical codes and
ordinances. Refer to job or manufacturers’ drawings for
details.
Power
Input power provided must be 24 Vac (±20%), 50 or 60 Hz.
For US installation, power must come from an energy-limited
Class II Power Source (transformers must not exceed
100 VA). More than one W7763 Controller can be powered
by a single transformer.
CAUTION
Turn off power prior to connecting to or removing con-
nections from any terminals to avoid electrical shock
or equipment damage.
Use the heaviest gauge wire available, up to 14 AWG
(2.5 mm2)with a minimum of 18 AWG (1.0 mm2) for all power
wiring.
1-13/16 (46) 4-9/16 (116)
3-3/8
(86)
Fig. 1. Excel 10 Chilled Ceiling Controller outside dimensions in in. (mm).
BEFORE INSTALLATION
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7763C,D,E CHILLED CEILING CONTROLLERS
95-7485-3 2
Fig. 2. Subbase mounting dimensions.
IMPORTANT (US only)
If the W7763 Controller is used on UL 1995 Heating
and Cooling Equipment and the transformer
primary power is more than 150 Vac, connect the
transformer’s secondary to earth ground. For these
applications, only one Excel 10 controller can be
powered by each transformer.
Communications
Wire the controller's LONWORKS® network using level IV 22
AWG (Belden part number 9D220150) or plenum-rated level
IV 22 AWG (Belden part number 9H2201504) nonshielded,
twisted pair, solid conductor wire. When possible, use
Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US
part numbers). See E-Bus (LONWORKS® network) Wiring
Practices, form number 74-2865, for more information
including maximum lengths.
Pull the cable to each controller on the LONWORKS® network
and connect to terminals 19 and 20.
The W7763 Chilled Ceiling Controller utilizes a free topology
transceiver (FTT10A) Link Power compatible LONWORKS®
network that allows daisy-chain, loop, and star network con-
figurations or any combination thereof. Depending upon the
LONWORKS® network configuration used, one or two ter-
mination modules, part number 209541B, may be required.
Different connections to the termination module are
necessary, depending upon whether it is used in a singly- or
doubly-terminated network configuration. See Excel 10
FTT/LPT 209541B Termination Module Installation
Instructions, form 95-7554.
NOTES:
— The LONWORKS® network is insensitive to polarity,
eliminating installation errors due to miswiring.
— Do not bundle output wires with sensor, digital input or
communications bus wires. Maintain a minimum 3 in.
(76 mm) separation between LONWORKS® network and
Triac output and power supply wiring.
— During installations, try to avoid areas of high electro-
magnetic noise (EMI).
— Chilled Ceiling Controllers have a 3.5-mm LONWORKS®
network jack for easy network access.
— For more information see E-Bus (LONWORKS® network)
Wiring Guidelines, form number 74-2865.
Wall Modules
A variety of Excel 10 wall modules can be used with W7763
Chilled Ceiling Controllers. See T7460 Wall Modules In-
stallation Instructions, form number 95-7610; T7560 Digital
Wall Module Installation Instructions, form number 95-7620;
and T7770 Wall Modules Installation Instructions, form
number 95-7538 for installation details.
NOTE: Wall Modules with fan speed switches must not be
used with W7763 Chilled Ceiling Controllers.
W7763
C
HILLED
C
EILIN
G
CO
NTR
O
LLE
R
W7763 CHILLED CEILING CONTROLLER
TERMINATION
MODULE (209541B)
19
20
19
20
BROWN
ORANGE
Fig. 3. Termination module connection (daisy-chain network configuration).
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7763C,D,E CHILLED CEILING CONTROLLERS
3 95-7485-3
Wiring Details
Connections to the Chilled Ceiling controllers are made at
two internal terminal blocks accessible beneath the front
cover. No tools are required to remove the front cover.
Simply pull away from the subbase as shown in Fig. 4.
Fig. 4. Terminal cover removal.
Fig. 5. Mounting on wall outlet box.
Use a minimum wire size of 20 AWG (0.5 mm2) for all input /
output connections. The maximum length of all input / output
cables and wall module interface cables is 65 ft (20 m). Main-
tain 3 in. (76 mm) minimum spacing between signal lines 1-
10 and Triac output and power supply wiring.
Fig. 8 illustrates the terminal assignments of the controllers.
Table 1 lists Triac output assignments for various actuator
types. Refer to job drawings for specific wiring diagrams.
IMPORTANT
Screw type terminal blocks are designed to accept
no more than one 14 AWG (2.5 mm2) conductor.
Multiple wires that are 14 AWG (2.5 mm2) can be
connected with a wire nut. Include a pigtail with this
wire group and attach the pigtail to the individual
terminal block.
Wire to the terminal blocks as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination. Insure
that the wire entering the terminal block does not ex-
tend above the numbered face of the terminal block to
avoid contact between the wires and the printed circuit
board on the underside of the front cover (see Fig. 6.)
Fig. 6. Terminal block connections.
IMPORTANT
When two or more wires are to be attached to the
same terminal, be sure to twist them together.
Deviations from this rule can result in improper
electrical contact. See Fig. 7. Local wiring codes
may take precedence over this recommendation.
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7763C,D,E CHILLED CEILING CONTROLLERS
Home and Building Control Home and Building Control Home and Building Control Products
Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG
Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17
P.O. Box 524 North York, Ontario D-71101 Schönaich
Minneapolis, MN 55408-0524 M2H 3N7 Germany
USA Canada
http://www.honeywell.com http://www.honeywell.ca http://europe.hbc.honeywell.com
95-7485-3 Rev. 01-01 7157 286 printed in Germany Subject to change without notice
1. STRIP 1/2 IN. (13 MM) FROM WIRES
TO BE ATTACHED AT ONE
TERMAINAL
2. TWIST WIRES TOGETHER WITH
PLIERS (A MINIMUM OF THREE
TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE
INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN
PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD
MECHANICAL CONNECTION.
Fig. 7. Attaching two or more wires at terminal blocks.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
COM1
INPUT3
COM2,3
INPUT2
INPUT1
LED
SETPT
BYPASS
SENSOR
GND E-BUS (LON)
E-BUS (LON)
OUT 1 COM
OUT 1 OPEN
OUT 1 CLOSE
OUT 2 COM
OUT 2 OPEN
OUT 2 CLOSE
24 VAC
24 VAC
24 VAC
24 VAC COM
24 VAC COM
24 VAC
COM
W7763 CHILLED
CEILING CONTROLLER
WALL MODULE
CONNECTIONS
OPEN
OPEN
CLOSE
CLOSE
COM
COM HEAT
120/240 VAC
COOL
-
+
2
2
1
HUMIDITY
0-10V
24 VAC
C
HILLED WATER TEMP
OCCUPANCY SENSOR
CHANGEOVER CONTACT
AIRFLOW CONTACT
WINDOW CONTACT
MOTION SENSOR
L
ON
W
ORKS
NETWORK IN
L
ON
W
ORKS
NETWORK OUT
1
2
Wall module setpoint connection for W7763E only.
Wall module bypass and LED connections for W7763D and E only.
DWM
T7560B
with
integrated
humidity
sensor
1
2
3
4
5
6
7
8
10
9
8
7
6
W7763
Chilled
Ceiling
Controller
…
1
11
T7560B connection to W7763
…
3
There is no logic between input 1 and 2; for example, only one of the inputs can be used for the
window contact, not both. This feature is available only with firmware version 1.0.4 or higher.
3
3
Fig. 8. Chilled Ceiling Controller terminal assignments.
Table 1. Output assignments for various actuator types.
Output type Out 1 Terminal Out 2 Terminal
13 14 15 16 17 18
Floating 24 Vac open close 24 Vac open close
1-stage 24 Vac on/off — 24 Vac on/off —
2-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
3-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
stage 3 stage 3
PWM 24 Vac PWM — 24 Vac PWM —
Thermal 24 Vac on/off — 24 Vac on/off —