manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell HC900 Use and care manual

Honeywell HC900 Use and care manual

Other manuals for HC900

7

Other Honeywell Controllers manuals

Honeywell PRO 2000 Series User manual

Honeywell

Honeywell PRO 2000 Series User manual

Honeywell SSW2-1M User manual

Honeywell

Honeywell SSW2-1M User manual

Honeywell 40014 User manual

Honeywell

Honeywell 40014 User manual

Honeywell Aquastat L7224U User manual

Honeywell

Honeywell Aquastat L7224U User manual

Honeywell SDW 30 User manual

Honeywell

Honeywell SDW 30 User manual

Honeywell SmartValve SV9510 User manual

Honeywell

Honeywell SmartValve SV9510 User manual

Honeywell DC1010 User manual

Honeywell

Honeywell DC1010 User manual

Honeywell Tradeline H1008A Operation manual

Honeywell

Honeywell Tradeline H1008A Operation manual

Honeywell UDC2500 User manual

Honeywell

Honeywell UDC2500 User manual

Honeywell MS4120S Operation manual

Honeywell

Honeywell MS4120S Operation manual

Honeywell ML6874 Operation manual

Honeywell

Honeywell ML6874 Operation manual

Honeywell INCOMM L510 User manual

Honeywell

Honeywell INCOMM L510 User manual

Honeywell S4565 Series User manual

Honeywell

Honeywell S4565 Series User manual

Honeywell T775A User manual

Honeywell

Honeywell T775A User manual

Honeywell DC1000 SERIES User manual

Honeywell

Honeywell DC1000 SERIES User manual

Honeywell ML7420A6025T User manual

Honeywell

Honeywell ML7420A6025T User manual

Honeywell HVC0001 User manual

Honeywell

Honeywell HVC0001 User manual

Honeywell HR92UK User manual

Honeywell

Honeywell HR92UK User manual

Honeywell ZG 215VN User manual

Honeywell

Honeywell ZG 215VN User manual

Honeywell MS7503A2023 User manual

Honeywell

Honeywell MS7503A2023 User manual

Honeywell UDC2500 User manual

Honeywell

Honeywell UDC2500 User manual

Honeywell Mini-AT User manual

Honeywell

Honeywell Mini-AT User manual

Honeywell S9240F2051 User manual

Honeywell

Honeywell S9240F2051 User manual

Honeywell 10260S Series User manual

Honeywell

Honeywell 10260S Series User manual

Popular Controllers manuals by other brands

Digiplex DGP-848 Programming guide

Digiplex

Digiplex DGP-848 Programming guide

YASKAWA SGM series user manual

YASKAWA

YASKAWA SGM series user manual

Sinope Calypso RM3500ZB installation guide

Sinope

Sinope Calypso RM3500ZB installation guide

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

Isimet

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS sv-ip5a user manual

LSIS

LSIS sv-ip5a user manual

Airflow Uno hab Installation and operating instructions

Airflow

Airflow Uno hab Installation and operating instructions

ABB ACS580-01 drives Hardware manual

ABB

ABB ACS580-01 drives Hardware manual

Panasonic GM1 Series Reference manual

Panasonic

Panasonic GM1 Series Reference manual

Emerson SW93 owner's manual

Emerson

Emerson SW93 owner's manual

AutoAqua Smart ATO micro SATO-120P manual

AutoAqua

AutoAqua Smart ATO micro SATO-120P manual

Panasonic FP? Positioning Unit RTEX Technical manual

Panasonic

Panasonic FP? Positioning Unit RTEX Technical manual

Alpha IP MIOB 21001 manual

Alpha IP

Alpha IP MIOB 21001 manual

Siemens OpenAir GMA 1 Series Mounting instructions

Siemens

Siemens OpenAir GMA 1 Series Mounting instructions

Surecom SR-629 user manual

Surecom

Surecom SR-629 user manual

Regulus SRS1 T Installation and operation manual

Regulus

Regulus SRS1 T Installation and operation manual

3M MicroTouch EX113 reference guide

3M

3M MicroTouch EX113 reference guide

KUHN TKS user manual

KUHN

KUHN TKS user manual

S&C PMH Instructions for operation

S&C

S&C PMH Instructions for operation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1/2018 Controller CPU and Scanner Module Kit # 51-52-33-126 1
ControlEdge HC900 Controller
Controller CPU and Scanner Module
Installation and Replacement
Controller CPU 900C50/900C50S - (current revision number)
Controller CPU 900C30/900C30S - (current revision number)
Controller CPU 900C70/900C70S - (current revision number)
Scanner 1 900S50/900S50S - (current revision number)
Scanner 2 (for redundant controller) 900S75/900S75S - (current revision number)
Document Number Form: 51-52-33-126
Effective Date: 1/2018
Supersedes: 9/2013
Summary Enclosed is a new Controller CPU, Scanner 1, or Scanner 2 module for your
ControlEdge HC900 Controller. Use the following procedures to install or
replace a module.
Controller CPU Table 1 and 3
Scanner 1 Table 2 and 3
Scanner 2 Table 4
Although it is best practice to remove power when replacing modules, the
ControlEdge HC900 CPU and Scanner modules may be removed and inserted under power.
See the ControlEdge HC900 Controller Installation and User’s Guide for more information.
ControlEdge HC900 Hardware Controller
Rack Assembly
1. Rack, available in 4- 8-, or 12-slot versions
2. Power Supply
3. Controller CPU or Scanner 1 Module
(for Scanner 2, see Figure 4)
4. Grounding bars (for I/O wiring; optional)
5. Input/Output modules
6. I/O Terminal Blocks
Figure 1
WARNING
2 Controller CPU and Scanner Module Kit # 51-52-33-126 1/2018
Contents
Each Controller CPU and Scanner module is supplied in a shipping container and static protective
shipping bag. For protection, leave the modules in their shipping containers until ready for installation.
Each container has a label identifying the contents.
C30 Controller
C50 Controller
C70 Controller
Scanner 1 Port
(S50)
Scanner 2 Port
(S75)
Safety C30S
Controller
Safety C50S
Controller
Safety C70S
Controller
Safety Scanner 1
Port (S50S)
Safety Scanner 2
Port (S75S)
Installation Guidelines
The Controller CPU and Scanner modules may only be inserted into a dedicated slot location in the
rack. The modules are labeled on the LEFT side of the module: for example, C30, C50, C70, Scanner
1 Port (S50), Scanner 2 Port (S75) and Safety versions C30S, C50S, C70S, C75S, Scanner 1 Port
(S50S), Scanner2 Port (S75S).
Most of the components in an I/O expansion rack are identical to those used in the Controller Rack.
The Controller CPU is installed in the controller rack (Figure 1, item 3) whereas the Scanner 1 or
Scanner 2 is installed in the I/O expansion rack (Figure 2).
1/2018 Controller CPU and Scanner Module Kit # 51-52-33-126 3
Controller CPU Installation Procedure
Follow the procedure in Table 1 to install a Controller CPU module in a controller rack.
Table 1 –Controller CPU Installation
Step
Action
1
Orient the controller rack to have the open side of the enclosure facing forward
with the power supply module located on the left and I/O module slots on the
right (See
).
2
Remove the Controller CPU module from its shipping container.
3
On the new CPU set/verify serial port switch settings.
Only one port may be a Modbus Master. It can be assigned to either port.
A small slotted screwdriver or paperclip works well; avoid using pencils because
their residue can damage the switch.
SW3
4
Insert the module into the dedicated slot location in the rack adjacent to the
power supply. Orient the module with module name at top. Align the module
printed circuit board with the card guide slots in the chassis. Press the CPU
module into the slot until the rear connector engages the mating connector of the
rack backplane. (See Figure 2)
Figure 2
5
Secure the Controller CPU module top and bottom with the captive mounting
screws. Torque settings 0,4 - 0,5 Nm (3.5 –4.4 Lb-In.)
6
Do not install the battery at this time. See instructions in the Controller
Installation and User’s Guide (document #51-52-25-154) for additional Controller
CPU setup information and battery installation.
4 Controller CPU and Scanner Module Kit # 51-52-33-126 1/2018
Follow the procedure in Table 2 to install a Scanner 1 module in an expansion I/O rack.
Table 2 Scanner 1 Installation
Step
Action
1
Orient the I/O expansion rack to have the open side of the enclosure facing forward
with the power supply module located on the left and I/O module slots on the right (See
).
2
Remove the Scanner 1 module from the shipping container. Set scanner address for
the I/O rack using the switches on SW3. A small slotted screwdriver or paperclip works
well; avoid using pencils since the residue can damage the switch.
Switches 5, 6, 7, 8 must be OFF.
Only 1 switch position may be ON.
Switch 1 ON = Scanner 1
Switch 2 ON = Scanner 2
Switch 3 ON = Scanner 3
Switch 4 ON = Scanner 4
Figure 3 shows setting for Rack 2
ON
12 3 45 6 78
SW3
ON
12345678
SW3
Honeywell
Figure 3 - Scanner 1 switch
3
Insert the module into its dedicated slot location in the rack adjacent to the power
supply. Orient the module with the module name on the left side. Align the module
printed circuit board with the card guide slots in the chassis. Press the Scanner
module into the slot until the rear connector engages the mating connector of the rack
backplane. (See Figure 2)
4
Secure the Scanner module top and bottom with the captive mounting screws.
Torque settings 0,4 - 0,5 Nm (3.5 –4.4 Lb-In.)
1/2018 Controller CPU and Scanner Module Kit # 51-52-33-126 5
Controller CPU or Scanner 1 Replacement
Follow the procedure in Table 3 to replace a Controller CPU or Scanner 1 module in an existing rack.
Table 3 Controller or Scanner Module replacement
Step
Action
1
Before replacing the Controller CPU module verify a copy of the current configuration
file is available and a method of loading the file is understood. See Process Control
Designer User’s Guide or ControlEdge HC900 Control Station User’s Guide.
2
Remove power from the rack. (recommended)
3
Remove the screws that secure the module assembly to the rack.
4
Pull the assembly to remove. For Controller CPU modules, go to step 6.
5
Remove the Scanner 1 module from the shipping container.
Note: Verify module faceplate colour (Blue or Orange) matches the original faceplate.
Set scanner address for the I/O rack using the switches on SW3. A small slotted
screwdriver or paperclip works well; avoid using pencils since the residue can
damage the switch.
switches 5, 6, 7, 8 must be OFF.
Only 1 switch position may be ON.
Switch 1 ON = Scanner 1
Switch 2 ON = Scanner 2
Switch 3 ON = Scanner 3
Switch 4 ON = Scanner 4
Image shows setting for Rack 2
ON
12 3 4 5 67 8
SW3
ON
1234 56 78
SW3
Honeywell
Scanner 1 switch
6
On the new CPU set/verify serial port switch settings. See Table 1 Step 3.
7
Insert the new module into the dedicated slot location in the rack. Orient the module
with module name on the left side. Align the module printed circuit board with the card
guide slots in the chassis. Press the module into the slot until the rear connector
engages the mating connector of the rack backplane. (See Figure 2)
8
Secure the module top and bottom with the captive mounting screws.
Torque settings 0,4 - 0,5 Nm (3.5 –4.4 Lb-In.)
9
Re-apply power to the rack.
10
See instructions in the Controller Installation and User’s Guide
(document #51-52-25-154) for additional Controller CPU setup information and
battery installation.
6 Controller CPU and Scanner Module Kit # 51-52-33-126 1/2018
Scanner 2 Overview
•One Scanner2 Module is installed in
each I/O Rack of a redundant system.
•I/O ports A –connects to CPU-A and
I/O Port B connects to CPU-B of the
redundant C75 Controller CPUs.
•Maintains communications with both
Lead and Reserve C75 CPU’s to
facilitate failover.
•Reads inputs from modules in rack &
writes outputs to modules in rack.
•Required for interface to C75
redundant controllers (cannot use
Scanner1 module with C75’s nor can
Safety be used with Non-Safety).
•May be replaced under power.
•Cannot use with non-redundant
systems.
Scanner 2 Non-Safety Scanner 2 Safety
Scanner 2 Installation Guidelines
The Scanner 2 module may only be inserted into a dedicated slot location in a Remote I/O Rack.
(Figure 4)
Figure 4
Power
Supply
#1
Power
Status
Module
Power
Supply
#2
Dual Port
Scanner
For C75 CPU
Input/Output Modules
8 slot and 12 slot I/O Racks
1/2018 Controller CPU and Scanner Module Kit # 51-52-33-126 7
Scanner 2 Installation or Replacement
Follow the procedure in Table 4 to install or replace a Scanner 2 module in a redundant power rack.
Table 4 Scanner 2 Module installation or replacement
Step
Action
1
If you are installing a new Scanner 2, go to step 6.
If you are replacing the Scanner 2, go to step 2.
2
Remove power from the rack containing the Scanner 2 module to be replaced.
(recommended)
3
Remove the screws that secure the module assembly to the rack. Disconnect the A
and B IO cables noting cable to port assignment
4
Pull the Scanner 2 module to remove.
5
Remove the Scanner 2 module from the shipping container. Note: Verify module
faceplate colour (Blue or Orange) matches the original faceplate.
Position the scanner address switches on the module for the appropriate address
position (see Step 6).
6
Set rack address for the I/O rack using
the Scanner 2 Module switches on SW3
(shown at right).
(Scanner Address = 1 is shown.)
Switches 6-8 must be OFF.
Only 1 switch position may be ON.
Switch 1 ON = Scanner 1
Switch 2 ON = Scanner 2
Switch 3 ON = Scanner 3
Switch 4 ON = Scanner 4
Switch 5 ON = Scanner 5
A small slotted screwdriver or paperclip
works well; avoid pencils.
7
Insert the new module into the dedicated slot location in the rack. Orient the module
with the I/O ports on the bottom. Align the module printed circuit board with the card
guide slots in the chassis. Press the Scanner 2 module into the slot until the rear
connector engages the mating connector of the rack backplane.
8
Secure the new Scanner 2 module top and bottom with the captive mounting screws.
Torque settings 0,4 - 0,5 Nm (3.5 –4.4 Lb-In.)
9
Re-apply power to the rack.
For more information
To learn more about SmartLine Transmitters,
visit www.honeywellprocess.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
51-52-33-126
January 2018
2018 Honeywell International Inc.
Shanghai City Centre, 100 Jungi Road
Shanghai, China 20061
www.honeywellprocess.com
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.
ASIA PACIFIC
Honeywell Process Solutions,
(TAC) hfs-tac-
support@honeywell.com
Australia
Honeywell Limited
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36
Toll Free Fax:
1300-36-04-70
China –PRC - Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
EMEA
Honeywell Process Solutions,
Phone: + 80012026455 or
+44 (0)1344 656000
Email: (Sales)
FP-Sales-A[email protected]
or
(TAC)
hfs-tac-support@honeywell.com
AMERICA’S
Honeywell Process Solutions,
Phone: (TAC) 1-800-423-9883 or
215/641-3610
(Sales) 1-800-343-0228
Email: (Sales)
FP-Sales-A[email protected]
or
(TAC)
hfs-tac-support@honeywell.com