  9. Honeywell SUPER TRADELINE S8610U User manual

Honeywell SUPER TRADELINE S8610U User manual

Table 1. Typical wiring connections.
Connector
Label Size or Type Description
MV 1/4 inch Main Valve connection
MV/PV 1/4 inch Common terminal for gas valves
PV 1/4 inch Pilot Valve connection
BRN GND 1/4 inch Burner Ground
24V GND 1/4 inch Return path to transformer
24V 1/4 inch Optional—24 Vac power connection for Vent
Damper
TH-W 1/4 inch Connector for “Call for Heat” signal from
thermostat
P1 6-pin keyed
plug
Connector for Vent Damper connection (used
to control a connected damper in atmospheric
appliances)
P2 ECOM 3-pin EnviraCOM™ communications connector
P4 (Jumper) Jumper Provides a lockout for the DIP switch settings
SENSE
JUMPER
WIRE
Wire with
3/16 inch
quick
connect
Connects to the REMOTE SENSE connector
for installations with a single spark rod (local
flame sensing)
NOTE: For installations with remote flame
sensing (separate spark and sensor rods), this
jumper wire is clipped as close to the circuit
board as possible and the wire is discarded.
REMOTE
SENSE
3/16 inch Flame Sensor connector
For single rod installations, connect the
SENSE JUMPER WIRE to this terminal
connector.
For dual rod installations, connect the flame
sense wire from the burner/igniter to this ter-
minal connector.
SPARK 1/4 inch High voltage sparking electrode
SETTINGS AND ADJUSTMENTS
DIP SWITCH (S1) SETTINGS
When replacing an existing ignition control with the S8610U,
refer to 69-1955 for the correct DIP switch settings.
Important
Do not power the ignition control prior to setting the DIP
switches.
The following timing parameters may be set with this 2-position
DIP switch.
PREPURGE
To select Prepurge, set SW1 according to Table 2.
TRIAL FOR IGNITION (TFI)
To select the Trial for Ignition timing, set SW2 according to
Table 2.
Table 2. DIP Switch (S1) Settings.
Prepurge Trial For Ignition SW1 SW2
None 90 seconds OFF OFF
30 seconds 90 seconds ON OFF
None 15 seconds OFF ON
30 seconds 15 seconds ON ON
NOTE: The default factory settings (all OFF) are in Bold in
Table 2.
Fig. 2. DIP Switch (S1) and Jumper (P4) Location.
Fig. 3. DIP Switch (S1)—shown with factory default
settings (OFF) for SW1 and SW2.
LED STATUS AND TROUBLESHOOTING
The ignition control module has two LEDs; one for flame sens-
ing and one for system status:
Fig. 4. Location of LEDs.
FLAME LED (YELLOW)
Indicates flame presence and strength. See Table 3.
STATUS LED (GREEN)
Indicates system operation status and error conditions. See
Table 4 and the “Troubleshooting Guide” in 69-1955.
Table 3. Yellow LED Flame Codes.
Yellow LED Flash
CodeaIndicates
Recommended
Service Action
Heartbeat Normal Flame Signal Not applicable
2 Weak Flame Signal—
System will operate
reliably but flame signal
is less than desired.
NOTE: This indication
may flash temporarily
during or shortly after
lightoff on some
applications.
Perform routine main-
tenance to assure opti-
mum flame signal.
Table 3. Yellow LED Flame Codes. (Continued)
1 Marginal Flame
Signal—System may
not operate reliably over
time.
Service call
recommended.
NOTE: This indication
may flash temporarily
during or shortly after
lightoff on some appli-
cations.
Check gas supply, pilot
burner, flame sense
wiring, contamination
of flame rod, burner
ground connection.
OFF Flame Signal below
minimum threshold for
system operation.
Check gas supply, pilot
burner, flame sense
wiring, contamination
of flame rod, burner
ground connection.
a Flash Code Descriptions:
- Heartbeat: Constant 1/2 second bright, 1/2 second dim cycles.
- The flash code number signifies that the LED flashes X times at 2
Hz, remains off for two seconds, and then repeats the sequence.
Table 4. Green LED Status Codes.
Green LED
Flash Code
(X + Y) Indicates
Next System
Action
Recommended
Service Action
OFF No “Call for Heat” Not applicable None
Flash Fast Startup – Flame
sense calibration
Not applicable None
Heartbeat Normal operation Not applicable None
2 5 minute Retry
Delay
Pilot flame not
detected during trial
for ignition.
Initiate new trial
for ignition after
retry delay com-
pleted.
If system fails to
light on next trial
for ignition, check
gas supply, pilot
burner, spark
and flame sense
wiring, flame rod
contaminated or
out of position,
burner ground
connection.
3 Recycle – Flame
failed during run.
Initiate new trial
for ignition. Flash
code will remain
through the igni-
tion trial until
flame is proved.
If system fails to
light on next trial
for ignition, check
gas supply, pilot
burner, flame
sense wiring,
contamination of
flame rod, burner
ground
connection.
Table 4. Green LED Status Codes. (Continued)
4 Flame sensed out
of sequence.
If situation self
corrects within 10
seconds, control
module returns to
normal sequence.
If flame out
of sequence
remains longer
than 10 seconds,
control module
goes to Flash
code 6+4 (see
below).
Check for pilot
flame. Replace
gas valve if pilot
flame present.
If no pilot flame,
cycle “Call for
Heat.” If error
repeats, replace
control.
5 Damper Error:
– Damper required
but not present
– Damper failed
to open within 60
seconds
– Damper failed
to close within 60
seconds
If damper error
corrects, ignition
control resumes
normal operation.
Check damper
connection, damp-
er wiring, and 24V
connection on
control.
Replace damper if
necessary.
7 Flame sense leak-
age to ground.
Control module
remains in wait
mode. When the
fault corrects,
control module
resumes normal
operation after a
one minute delay.
Check flame
sense lead wire
for damage or
shorting. Check
that flame rod is
in proper position.
Check flame rod
ceramic for cracks,
damage or
tracking.
8 Low secondary volt-
age supply.
Control module
remains in wait
mode. When the
fault corrects,
control module
resumes normal
operation after a
one minute delay.
Check transformer
and AC line for
proper input volt-
age to the control.
Check with full
system load on the
transformer.
6+2 5 minute Retry
Delay
– On every third
retry on the same
“Call for Heat”
Initiate new trial
for ignition after
retry delay
completed.
Check gas supply,
pilot burner, spark
and flame sense
wiring, flame rod
contaminated or
out of position,
burner ground
connection.
2 3 4 5 6
M23618
S1 DIP SWITCH
P4 JUMPER
ON
1 2
S1
M23587
M23619
FLAME LED
STATUS LED
69-2042
TECHNICIAN’S QUICK REFERENCE GUIDE
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
Automation and Control Solutions
® U.S. Registered Trademark.
© 2006 Honeywell International Inc.
69-2042 M.S. 12-06
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
S8610U Universal
Intermittent Pilot Gas
Ignition Control
The following service procedure provides a quick overview for
the S8610U series control. For more information, refer to form
69-1955.
WIRING CONNECTIONS
Fig. 1. Typical wiring connections.
Table 4. Green LED Status Codes. (Continued)
6+3 On every 6th flame
failure during run on
the same “Call for
Heat.”
Initiate new trial
for ignition after
retry delay
completed.
Check gas supply,
pilot burner, flame
sense wiring,
contamination of
flame rod, burner
ground
connection.
6+4 Flame sensed
out of sequence
for longer than 10
seconds.
Control module
waits until flame
is no longer
sensed and then
goes to soft
lockout. Flash
code continues.
Control module
auto resets from
soft lockout after
one hour.
Check for pilot
flame. Replace
gas valve if pilot
flame present.
If no pilot flame,
cycle “Call for
Heat.” If error
repeats, replace
the S8610U con-
trol module.
ON Soft lockout due
to error detected
during self check
sequences.
Control module
auto resets from
soft lockout after
one hour.
Reset by cycling
“Call for Heat.”
If error repeats,
replace the
S8610U control
module.
a Flash Code Descriptions:
- Flash Fast: rapid blinking.
- Heartbeat: Constant 1/2 second bright, 1/2 second dim cycles.
- A single flash code number signifies that the LED flashes X
times at 2 Hz, remains off for two seconds, and then repeats the
sequence.
- X + Y flash codes signify that the LED flashes X times at 2 Hz,
remains off for two seconds, flashes Y times at 2Hz, remains off for
three seconds, and then repeats the sequence.
7 8 9
SPARK
MV
24V GND
MV/PV
PV
BRN/GND
REMOTE
SENSE
P2 ECOM
TH-W (OPT.)
24V (OPT.)
M23615
SENSE
JUMPER
WIRE
P1 VENT DAMPER
CONNECTOR P4 JUMPER
Terminal
Function
Replacement
Control Old Control Procedural Notes
S8610U S86A,C S86B,D S86E,F,G,H
S90A,B
S8600A,B,C
S8610A,B,C
S8610U1003
S8620C,
S8660D,J
S8670D,J
S8680D,J
S8600F,H,M
S8610F,H,M
S8660E,K
S8670E,K
Main Valve
Operator
MV MV MV MV MV MV —
Main Valve and
Pilot Common
MV/PV MV/PV MV/PV MV/PV MV/PV MV/PV —
Pilot Valve
Operator
PV PV PV PV PV PV —
Burner Ground
Connection
GND
(BURNER)
GND GND GND
(BURNER)
GND
(BURNER)
GND
(BURNER)
—
Transformer
Secondary (un-
switched leg)
24V GND 25V (2) 25V 25V (2)a24V GND 24V GND —
Transformer
Secondary
(switched leg)
24V * 25V (2) 25V 25V (2)a* 24V * 24V * * Important
If the old module had a vent damper connec-
tor but a vent damper was not installed, or if
it did not have a vent damper connector, then
connect the 25V (2) or 24V wire from the old
module to the TH-W terminal on the S8610U.
Do not use the 24V terminal on the S8610U.
If the old module had a vent damper, connect
it to the P1 connector on the module, and
wire the terminals as indicated in Table 1.
25V (2) or 24V used only in systems
where plug-in cable connects damper to
module
TH-W TH-RbTH-RbTH-RbTH-W
(This ter-
minal is not
included on
S90.)
TH-W
TH-WcTH-W TH-Wc
Flame Sensor SENSEd e e e SENSEd e —
Igniter /Sensor SPARK IGN
COILfIGN
COILfIGN COILfSPARK SPARK —
a Terminals may be marked 25V on some models and 24V on later models. These are functionally equivalent.
b If 25V (2) and TH-R have wires connected, disconnect and splice together with solderless connector.
c If TH-R and TH-W are jumpered together, connect 25V (2) lead from S86 to TH-W on S8610U.
d On dual igniter and sensor models, remove jumper wire quick connect from S8610U Remote Sense terminal, then cut jumper wire at circuit
board and discard.
e Leave black jumper connected.
f Use Rajah to quick connector adapter (supplied) or cut Rajah connector off ignition cable at module end and attach insulated quick connect for
connection to S8610U.
Table 5. Conversion from Honeywell Intermittent Pilot Modules.

Other manuals for SUPER TRADELINE S8610U

4

Other Honeywell Controllers manuals

Honeywell T775U Series User manual

Honeywell

Honeywell T775U Series User manual

Honeywell HC900 User manual

Honeywell

Honeywell HC900 User manual

Honeywell W7340 Operation manual

Honeywell

Honeywell W7340 Operation manual

Honeywell ML7284 Operation manual

Honeywell

Honeywell ML7284 Operation manual

Honeywell ML6874 Operation manual

Honeywell

Honeywell ML6874 Operation manual

Honeywell Evohome User manual

Honeywell

Honeywell Evohome User manual

Honeywell WV8860C User manual

Honeywell

Honeywell WV8860C User manual

Honeywell T775A User manual

Honeywell

Honeywell T775A User manual

Honeywell M7061 User manual

Honeywell

Honeywell M7061 User manual

Honeywell R7184A User manual

Honeywell

Honeywell R7184A User manual

Honeywell CN34 Series Operation manual

Honeywell

Honeywell CN34 Series Operation manual

Honeywell UDC3500 User manual

Honeywell

Honeywell UDC3500 User manual

Honeywell RA890G User manual

Honeywell

Honeywell RA890G User manual

Honeywell Centraline LION Installation and operation manual

Honeywell

Honeywell Centraline LION Installation and operation manual

Honeywell Touchpoint Plus Release Note

Honeywell

Honeywell Touchpoint Plus Release Note

Honeywell CIPer 50 Installation and operation manual

Honeywell

Honeywell CIPer 50 Installation and operation manual

Honeywell AQUASTAT L4188A User manual

Honeywell

Honeywell AQUASTAT L4188A User manual

Honeywell KromSchroder IC 40 Manual

Honeywell

Honeywell KromSchroder IC 40 Manual

Honeywell HON 670 Guide

Honeywell

Honeywell HON 670 Guide

Honeywell ACS-2plus User manual

Honeywell

Honeywell ACS-2plus User manual

Honeywell Air Alert 96d User manual

Honeywell

Honeywell Air Alert 96d User manual

Honeywell HEGSA002 User manual

Honeywell

Honeywell HEGSA002 User manual

Honeywell TPPL Modbus TCP Assembly instructions

Honeywell

Honeywell TPPL Modbus TCP Assembly instructions

Honeywell CENTRA LINE MERLIN NX Series User manual

Honeywell

Honeywell CENTRA LINE MERLIN NX Series User manual

Popular Controllers manuals by other brands

HAI OmniLT Automation installation manual

HAI

HAI OmniLT Automation installation manual

Shihlin electric SA3 Series instruction manual

Shihlin electric

Shihlin electric SA3 Series instruction manual

NAiS AFP3434 Guide book

NAiS

NAiS AFP3434 Guide book

Regin RDAS7S-24C Mounting instructions

Regin

Regin RDAS7S-24C Mounting instructions

GRAIGAR A.V.R. R220 Installation and Maintenance

GRAIGAR

GRAIGAR A.V.R. R220 Installation and Maintenance

Norac UC5 Topcon X30 quick guide

Norac

Norac UC5 Topcon X30 quick guide

Omron CK5M Series Connection guide

Omron

Omron CK5M Series Connection guide

FixPosition Vision-RTK 2 quick start guide

FixPosition

FixPosition Vision-RTK 2 quick start guide

KIPI ecoMAX860P3-C Installation and operating manual

KIPI

KIPI ecoMAX860P3-C Installation and operating manual

Bosch FHP560 Applications manual

Bosch

Bosch FHP560 Applications manual

Evco EV3802 quick start guide

Evco

Evco EV3802 quick start guide

LOVATO ELECTRIC RGK600 installation manual

LOVATO ELECTRIC

LOVATO ELECTRIC RGK600 installation manual

SurePoint SENTINEL manual

SurePoint

SurePoint SENTINEL manual

CYBELEC CybTouch 8 user manual

CYBELEC

CYBELEC CybTouch 8 user manual

Siemens SEO520 operating instructions

Siemens

Siemens SEO520 operating instructions

Micronix MPA-20 series Reference manual

Micronix

Micronix MPA-20 series Reference manual

Acer AcerAltos 3102RS user guide

Acer

Acer AcerAltos 3102RS user guide

Mitsubishi FX3G-4EX-BD user manual

Mitsubishi

Mitsubishi FX3G-4EX-BD user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.