manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security System
  8. •
  9. Honeywell ADEMCO 5809 Assembly instructions

Honeywell ADEMCO 5809 Assembly instructions

N8583V3 7/05 Rev. A
ADEMCO 5809
Rate-Of-Rise Heat Detector
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 5809 Rate-of-Rise Heat Detector is a wireless
device used with ADEMCO alarm systems that support 5800
series devices.
The 5809 combine both rate-of-rise and fixed temperature
sensors. The 5809’s rate-of-rise thermostat senses the rise in
temperature and signals an alarm if the rise is 15°F (8°C) or
more per minute. Fires typically cause a rapid rise in
temperature in the surrounding area. A built-in fixed
temperature sensor will also signal an alarm if the ambient
temperature rises above 135°F (57°C).
WARNING: The 5809’s fixed temperature sensor will be
permanently damaged if the 5809 is installed, stored or shipped
in environments where temperature exceeds 120°F.
NOTES:
• If the fixed temperature sensor activates, the 5809
must be replaced.
• An installation site where the ambient temperature
exceeds 100°F for extended periods is not
recommended.
A 3-volt lithium battery powers the 5809. If the battery voltage
gets too low, the 5809 send a low battery signal to the control
panel.
The 5809 also include a tamper switch, which causes a trouble
signal to be sent to the control if the unit is removed from the
mounting base.
A built-in activation button, located on the detector assembly, is
used when programming the unit’s serial number at the control
and when testing the unit.
INSTALLING THE BATTERY
Important Notes:
• Use 3-volt lithium battery: Duracell DL 123A or
Panasonic/Sanyo/Varta/Tekcell CR123A.
• Observe polarity.
• When replacing the battery, wait at least 30 seconds
after removing the old battery, before installing the
new one.
Remove the detector assembly from its mounting base and
install a 3-volt lithium battery as shown below.
BATTERY
5809EN-003-V0
PROGRAMMING THE UNIT
The transmitter’s serial number must be enrolled in the control
panel before usage in the system. Refer to the Installation and
Setup Guide for which this device is to be used for
programming procedures for enrolling transmitter serial
numbers. Before programming do the following:
1. Remove the detector assembly from its mounting base by
twisting the detector assembly counter-clockwise and
withdraw from the base.
2. Install the battery (if not already installed). Observe
polarity!
3. Enter the control’s programming mode and follow the
control’s programming instructions. When programming
this transmitter at the control, note the following:
• Input Type = 3 (Supervised RF)
• Loop number = 1
Transmit from the detector when prompted (momentarily
depress the activation button shown below). You can also
manually enter the detector’s serial number.
4. Test the detector after enrolling into the system. Refer to
the Testing section.
5809EN-001-V0
ACTIVATION
BUTTON
DETECTOR
ASSEMBLY
INDEX
TA B
TAMPER
SWITCH
MOUNTING THE DETECTOR
You can mount the 5809 on a wall or ceiling within the
protection area:
• Wall Mounting: Mount the detector 4” - 6” from the
ceiling.
• Ceiling Mounting: Mount the detector at least 4” from
any wall. Make sure the normal ceiling temperature
will not exceed 100°F.
• Refer to NFPA Standard 72 for detector spacing and
other requirements. Maximum spacing for UL
installations is 50’x50’.
• Avoid mounting the detector near heat generating
devices (e.g. ovens, heat vents, furnaces, boilers).
IMPORTANT:
Heat detectors should be used for property protection.
Reliance should not be placed solely on heat detectors for
life safety. When life safety is involved, smoke detectors
MUST also be used. Detectors must not be painted.
WIRELESS TRANSMISSION PATH TEST
A good RF transmission path must be established from the
proposed mounting location before permanently installing the
detector. To determine that there is good signal reception from
the proposed location, perform the test procedure described in
TESTING THE DETECTOR section.
Once a good RF transmission path is confirmed, mount the
detector as follows:
ÊN8583V3uŠ
N8583V3 7/05 Rev. A
1. Surface mount the unit’s plastic base to a wall or ceiling, or
mount the plastic base to either a 4” junction box or 3-1/4-
octagon box.
NOTE: The anti-twist mounting hole is for use when
installing the device directly to wallboard to prevent the
base from being twisted off when servicing the device.
2. Install the detector assembly to the base by aligning the
detector assembly index tabs to the index tab recesses in
the base, pushing in, and secure by turning the detector
assembly clockwise.
5809EN-002-V0
INDEX TAB
RECESS
INDEX TAB
RECESS
ANTI-TWIST
MOUNTING
HOLE
MOUNTING
HOLES
TESTING THE DETECTOR
This test procedure should be performed to determine a good
RF transmission path and again after installation is completed.
CAUTION: The rate-of-rise heat sensor is intended for one-time
use. Prolonged heat during testing can damage
the unit. If used carefully following the
instructions below, the heat from a portable hair
dryer can be used to test the unit. If the round
disk on top of the detector detaches, the detector
must be replaced.
1. Activate the control panel’s test mode.
2. Use either method (a) or (b) to activate the detector:
(A) Press and release the activation button on the PC
board assembly,
OR
(B) Holding a portable hair dryer about 12 to 18
inches away from the detector, turn the dryer on
and aim the warm air at the side of the detector.
CAUTION: Aiming the dryer directly at the round disk on the
detector can damage the detector, requiring the unit
to be replaced.
3. The system’s keypads should beep and the detector’s
ID should be displayed.
4. Exit the control’s test mode.
Unit is intended for dry, indoor use only.
MAINTAINING PROPER OPERATION
To maintain the detector in proper working condition, it is
important that you observe the following:
Replace the battery when the system indicates that the 5809
has reported a low battery condition.
Units should never be relocated without the advice or
assistance of the alarm service company.
SPECIFICATIONS
Power: 3V lithium battery (Duracell DL123A, Panasonic
CR123A, Sanyo CR123A, Varta, Tekcell (CR123A)
CAUTION: Risk of fire, explosion, and burns. Do not recharge,
disassemble, heat above 212°F (100°C) or
incinerate. Dispose of used batteries promptly.
Keep away from children.
Operating Temperature: 40°to 140°F (6°to 60°C)
Rate-of-Rise Temperature: 15°F (8°C) increase per minute
NOTE: Rate of rise sensor does
not operate above 38°C)
Fixed Temperature: 135°F (57°C)
Maximum Spacing: 50ft x 50ft UL, 30ft x 30ft FM
(refer to National Fire Alarm
Code Standard NFPA 72 for
application requirements)
Dimensions: 4.4” diameter/ 2/2” deep
TO THE INSTALLER
The rate-of-rise mechanism may be subject to reduced
sensitivity over time. Annual testing of the rate-of-rise
operation is recommended.
Regular maintenance and inspection (at least annually) by the
installer and frequent testing by the user are vital to
continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing
and offering a regular maintenance program to the user as well
as acquainting the user with the proper operation and
limitations of the alarm system and its components parts.
Recommendations must be included for a specific program of
frequent testing (at least weekly) to ensure the system’s proper
operation at all times.
FCC ID: CFS8DL5809EN-1
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
INDUSTRY CANADA
IC: 573F-5809EN1
FOR WARRANTY INFORMATION AND LIMITATIONS OF THE
ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION AND
SETUP GUIDE FOR THE RECEIVER/CONTROL PANEL WITH
WHICH THIS DEVICE IS USED.
165 Eileen Way, Syosset, New York 11791
Copyright © 2005 Honeywell International Inc.
www.honeywell.com/security

Other Honeywell Security System manuals

Honeywell V4000 User manual

Honeywell

Honeywell V4000 User manual

Honeywell MK V User manual

Honeywell

Honeywell MK V User manual

Honeywell Galaxy 2 Series User manual

Honeywell

Honeywell Galaxy 2 Series User manual

Honeywell Notifier P700N User manual

Honeywell

Honeywell Notifier P700N User manual

Honeywell DTPI8M User manual

Honeywell

Honeywell DTPI8M User manual

Honeywell SF340F User manual

Honeywell

Honeywell SF340F User manual

Honeywell Apex Destiny 4100 User manual

Honeywell

Honeywell Apex Destiny 4100 User manual

Honeywell System 1500e User manual

Honeywell

Honeywell System 1500e User manual

Honeywell SILENT KNIGHT RA-2000 User manual

Honeywell

Honeywell SILENT KNIGHT RA-2000 User manual

Honeywell ADEMCO Vista-12C Assembly instructions

Honeywell

Honeywell ADEMCO Vista-12C Assembly instructions

Honeywell DIY Smart Home User manual

Honeywell

Honeywell DIY Smart Home User manual

Honeywell ADEMCO LYNXR Series User manual

Honeywell

Honeywell ADEMCO LYNXR Series User manual

Honeywell Accenta Quick start guide

Honeywell

Honeywell Accenta Quick start guide

Honeywell VISTA-128FBP User manual

Honeywell

Honeywell VISTA-128FBP User manual

Honeywell XC70 User manual

Honeywell

Honeywell XC70 User manual

Honeywell Home SI800MS User manual

Honeywell

Honeywell Home SI800MS User manual

Honeywell FA-300 Alarm Bar User manual

Honeywell

Honeywell FA-300 Alarm Bar User manual

Honeywell ESSER IQ8Alarm User manual

Honeywell

Honeywell ESSER IQ8Alarm User manual

Honeywell LYNX User manual

Honeywell

Honeywell LYNX User manual

Honeywell Lyric Operator's manual

Honeywell

Honeywell Lyric Operator's manual

Honeywell HS321S User manual

Honeywell

Honeywell HS321S User manual

Honeywell Domonial User manual

Honeywell

Honeywell Domonial User manual

Honeywell Fire Lite Alarms SWIFT Datasheet

Honeywell

Honeywell Fire Lite Alarms SWIFT Datasheet

Honeywell Lynx Touch L5100 User manual

Honeywell

Honeywell Lynx Touch L5100 User manual

Popular Security System manuals by other brands

Apxalarm APX32EN quick start guide

Apxalarm

Apxalarm APX32EN quick start guide

AJAX HomeSiren quick start guide

AJAX

AJAX HomeSiren quick start guide

Tynetec Advent xt Programming guide

Tynetec

Tynetec Advent xt Programming guide

Lorex SG21CD7484UQ-A80 instruction manual

Lorex

Lorex SG21CD7484UQ-A80 instruction manual

GE Security Simon user guide

GE Security

GE Security Simon user guide

Bosch Security Systems user guide

Bosch

Bosch Security Systems user guide

ADEMCO VISTA user manual

ADEMCO

ADEMCO VISTA user manual

Cisco PIX 525 datasheet

Cisco

Cisco PIX 525 datasheet

MED 2200 user guide

MED

MED 2200 user guide

MobileHelp IGM-02 Complete user guide

MobileHelp

MobileHelp IGM-02 Complete user guide

Yale HSA6200 Installation, programming, operating

Yale

Yale HSA6200 Installation, programming, operating

ITALIANA SENSORI 8156-ISS021 Installation, operation and maintenance manual

ITALIANA SENSORI

ITALIANA SENSORI 8156-ISS021 Installation, operation and maintenance manual

NAPCO MAGNUM ALERT-825 operating guide

NAPCO

NAPCO MAGNUM ALERT-825 operating guide

Vesta MZ-1 installation guide

Vesta

Vesta MZ-1 installation guide

FBII XL-1S Hookup and installation instructions

FBII

FBII XL-1S Hookup and installation instructions

Magellan MG-6060 Programming guide

Magellan

Magellan MG-6060 Programming guide

DSC Envoy NT9010 installation guide

DSC

DSC Envoy NT9010 installation guide

AEI Security & Communications SOLARGUARD SG4000 Installation & user guide

AEI Security & Communications

AEI Security & Communications SOLARGUARD SG4000 Installation & user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.