FBII XL-1S User manual

XL-1S
SECURITY SYSTEM
HOOKUP AND INSTALLATION INSTRUCTIONS
Subsidiary of Pittway Corp.
149 Eileen Way, Syosset, NY 11791
N9471V1 06/98

ii
THANK YOU for your purchase of the FBII
XL-1SILVER.
The purpose of the manual is to give you a brief overview of the XL-1S control panel, and provide
instructions for installing a basic system. FBII is always available to serve YOU. Our SALES and
TECHNICAL SUPPORT staff are available to assist you in any way possible.
FOR
TECHNICAL SUPPORT,
CALL TOLL FREE:
(800) 645-7492
Before you call Technical Service, be sure you:
;
Check the wiring diagram and verify your connections.
;
Check all fuses.
;
Assure that the transformer and backup battery voltages are supplying the proper voltage levels.
;
Verify your programming information.
;
Read this manual thoroughly.
;
Consult the Troubleshooting Section of this Manual.
;
Note the proper model number of this product, and the version level (if known) along with any
documentation that came with the product.
;
Have your company name and telephone number ready.
This information will allow us to service you more quickly and effectively. Please, remember to BE PATIENT
while waiting on the telephone; your call will be answered as soon as possible.
FOR YOUR CONVENIENCE, a System Planning Worksheet and a Programming Worksheet is included at
the back of this manual. These can be removed to help you record account information.

iii
Table of Contents
••••••••••••••••••••••••••••••••••••••••••••••••••
XL-1S to XL-2 Comparison ..................................................................................................................................v
Conventions Used in This Manual .................................................................................................................vii
Section 1 - Introduction...................................................................................................................................1–1
Section 2 - System Wiring and Hookup........................................................................................................2–1
System Wiring Diagram ...................................................................................................................................2–1
Terminal Connections.......................................................................................................................................2–2
Auxiliary Device Current Draw Worksheet ....................................................................................................2–6
Wiring Information for Keypads & Other Devices..........................................................................................2–7
Keypads & Other Devices.................................................................................................................................2–7
Section 3 - PC Board Mounting......................................................................................................................3–1
Mounting the PC Board....................................................................................................................................3–1
Section 4 - Keypad Mounting..........................................................................................................................4–1
XK-104 Keypad..................................................................................................................................................4–1
Mounting 6805 Keypad.....................................................................................................................................4–2
Section 5 - Keypad Layout...............................................................................................................................5–1
Keypad Sounder................................................................................................................................................5–3
Section 6 - System Operations........................................................................................................................6–1
Power Up/System Reset....................................................................................................................................6–1
Arming the System............................................................................................................................................6–1
Stay Arming.......................................................................................................................................................6–1
Instant Arming..................................................................................................................................................6–1
Stay/Instant Arming .........................................................................................................................................6–2
Disarming ..........................................................................................................................................................6–2
Reset...................................................................................................................................................................6–2
Bypass................................................................................................................................................................6–2
Auto Unbypass ..................................................................................................................................................6–3
Manual Unbypass .............................................................................................................................................6–3
User Code Programming...................................................................................................................................6–3
User Deletion.....................................................................................................................................................6–4
Keypad Emergency Conditions ........................................................................................................................6–4
Section 7 - Installer Modes..............................................................................................................................7–1
Installer Mode 1 (Installer Keypad Programming).........................................................................................7–1
Installer Mode 2 (System Log View)................................................................................................................7–1
Installer Mode 3 (Unattended Download).......................................................................................................7–2
Installer Mode 4 (On-Line Download) .............................................................................................................7–2
Section 8 - System Programming ..................................................................................................................8–1
General...............................................................................................................................................................8–1
Programming Questions...................................................................................................................................8–1
Zone Programming..........................................................................................................................................8–10
Section 9 - Data Entry via LED & LCD Keypads .......................................................................................9–1
Entering Programming Mode via Either LED or LCD Keypads ...................................................................9–1
What You See on the LED Keypad ..................................................................................................................9–1
What You See On The LCD Keypad ................................................................................................................9–2
How to Enter Data ............................................................................................................................................9–2

Table of Contents (cont’d)
••••••••••••••••••••••••••••••••••••••••••••••••••
iv
Section 12 - System Defaults.........................................................................................................................10–1
Section 11 - Summary of Keypad Functions.............................................................................................11–1
User Functions ................................................................................................................................................11–1
Installer Mode .................................................................................................................................................11–1
Appendix A - Central Station Reporting Formats ...................................................................................A–1
Standard (3X1) .................................................................................................................................................A–1
4X2.....................................................................................................................................................................A–2
Appendix B - Troubleshooting ......................................................................................................................B–1
Appendix C - XL-1S System Planning Worksheet.....................................................................................C–1
Appendix D - XL-1S System Programming Worksheet ...........................................................................D–1
Appendix E - Warnings and Limitations ....................................................................................................E–1
Appendix F - FCC Statement and Telephone Problems......................................................................... F–1
Appendix G - Warranty ...................................................................................................................................G–1

v
XL-1S to XL-2 Comparison
••••••••••••••••••••••••••••••••••••••••••••••••••
The XL-1S is an enhanced version of the XL-2 control panel. Some new features have been added and others
have been modified. The following is a quick comparison.
XL-1S NEW & MODIFIED FEATURES XL-2 SIMILAR FEATURES
Call Waiting /PBX Dialing - 1 digit entry
(program quest. #01 & #02) Multiple digits required
Smoke Power or Programmable
Trigger #1 Output/Terminal P1-T1
(program quest. #07)
Smoke Power Only
Programmable Trigger #2
Output/Terminal P1-T2 (program quest.
#07)
NONE
CS Test Timer Offset (program quest.
#14) NONE
Cancel Code (program quest. #18)NONE; Restore Code Only
European Ring Detect (program quest.
#05) NONE
Exit Error Warning (always enabled) NONE
Bypass In Stay - Any Controlled Zone can
be Bypassed in Stay Mode (program quests.
#10-13)
Interior Zones Only Bypassed in Stay Mode
System Stabilization on Power Up - to
Eliminate Motion Detector False Alarms NONE
Fast Loop Response (10 msec) Option
by Zone (program quests. #10-13) NONE
AC (50/60 HZ) Based System Real Time
Clock (program quest. #05) Software Based System Timing
Bell Supervision - New NFPA 72
Requirement (program quest. #13) NONE
Stay Mode 40 Sec. Dialer Delay w/Bell
& Keypad Sounder Warning for All
Zones (program quest. #05)
Stay Mode Entry Delay w/Keypad Sounder
Warning for Exit/Entry Zones Only
LED Zone Display & Keypad Sounder
during Entry (always enabled) Keypad Sounder Only
XL-1S FEATURE CHANGES XL-2 SIMILAR FEATURES
5 Zones - 4 Programmable & Wired
Panic or Keyswitch Zone (program
quest. #10-13)
7 Zones - 6 Programmable & Wired
Panic or Keyswitch Zone
System Wide Restore Code Enable
(program quest. #19) Restore Codes selectable by each zone
System Wide 15 Sec. Dialer Delay for
controlled zones (program quest. #07) 15 Sec. Dialer Delay selectable by each zone
User 5 - Arm Only User capability
removed User 5 - Arm Only User optional

XL-1S to XL-2 Comparison (cont’d)
••••••••••••••••••••••••••••••••••••••••••••••••••
vi
Ring Count Options: 0, 4, 8, 12, (program
quest. #07) Ring Count Options: 0 - 15
Quick Commands (Quick Arm, Quick
Forced Arm & Quick Bypass)
capability removed
Quick Arm & Quick Forced Arm/Quick
Bypass programmable
= Reset (* key) always enabled for Fire
Alarms Only Reset (* key) programmable for Both
Burglar & Fire Alarms
LCD Keypad Descriptors NOT
Programmable (Default = Zone 1, Zone 2,
etc.)
LCD Keypad Descriptors Programmable
CS Reporting Formats (Ext. & Partial
Ext.) capability removed CS Reporting Formats (Ext. & Partial Ext.)
programmable
CS Test Keypad Ringback always
Silent CS Test Keypad Ringback always Audible

vii
Conventions Used in This Manual
••••••••••••••••••••••••••••••••••••••••••••••••••
Before you begin using this manual, it is important that you understand the meaning of the following symbols
(icons).
ULThese notes include specific information which must be followed if you are installing this system
for a UL Listed application.
These notes include information that you should be aware of before continuing with the
installation, and which, if not observed, could result in operational difficulties.
This symbol indicates a critical note that could seriously affect the operation of the system, or
could cause damage to the system. Please read each warning carefully. This symbol also
denotes warnings about physical harm to the user
.

viii

1–1
SECTION 1
Introduction
••••••••••••••••••••••••••••••••••••••••••••••••••
The XL-1S Security System is a state of the art microprocessor-based control/communicator.
Programming can be performed through any of the compatible keypads or the system can be
uploaded and downloaded remotely using the EZ-Mate PC Downloader Software. In addition,
remote control actions (arming, disarming, bypassing, etc.) can be performed by the software.
Programming options are stored in non-volatile reprogrammable EEPROM memory and that
information which has been programmed will not be lost in the event of a complete loss of
power. Other features of the XL-1S include:
•5 Zones (4 fully programmable plus a wired panic zone or keyswitch zone)
•2 types of compatible keypads (LCD & LED, four wire devices with up to four per system)
•6 user codes with capability for ambush code
•Fast Loop Response (10 msec) selectable by zone
•NFPA 72 Bell Supervision
•CS Test Timer Offset
•English readout keypads available
•Upload/Download with remote commands with answering machine bypass
•Default Lockout option to prevent hostile account takeovers
•Indications on keypad for AC loss, Low Battery and Communication Failure
•Central Station reporting for Alarms, Troubles, Restores, Bypasses, Openings, Closings,
Ambush, Panic, 24HR. Test, Cancels, AC loss, and Low Battery
•Can be programmed as a Local System (No CS Reporting)
•4 wire smoke detectors with Fire Verification logic plus smoke power reset
•Exit Error Warning
•European Ring Detect
•2 programmable trigger outputs for various functions (including armed/ready indication
and glass break detector reset)
•Input Power: 12VAC 20VA; 12VDC, 4 - 7 AH
•Output Power: 11.5 - 13.1VDC, 500mA
•Bell Output Power: 10 - 15.5VDC, 1A

XL-1S Hookup and Installation Instructions
1–2

2–1
SECTION 2
System Wiring and Hookup
••••••••••••••••••••••••••••••••••••••••••••••••••
System Wiring Diagram
CONTROL PANEL
POWER
DETAIL A
12 13
1 2 3 4
ZONE
SMOKE DETECTOR
9.5 - 12.2VDC
LISTED
HOUSEHOLD
THERMOSTAT
ESL 104
MODEL ESL2048
EOL RELAY
RED
BLACK
BROWN
BROWN
2.2K EOL RESISTOR
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
UL INSTALLATIONS REQUIRE LISTED
END-OF-LINE DEVICE. USE RESISTOR
FROM EOL22 KIT. LOOK FOR LISTING
MARK ON ITEM.
WARNING:
THIS UNIT INCLUDES AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT
PLUS SMOKE DETECTOR) SHALL NOT EXCEED
60 SECONDS. NO OTHER INITIATING DEVICES
SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
CIRCUIT CONTROL UNIT SMOKE DETECTOR
(ZONE) DELAY-SEC MODEL DELAY-SEC
_______ _____20______ ______ __________
PRODUCT COVERED UNDER
US PATENT #4,791,658
WARNING: To prevent risk from
electrical shock, de-energize the system
control unit and disconnect the telephone
lines before servicing this unit.
XL-1S
FCC Registration Number AE398E-69554 AL-E Ringer Equivalence 0.0B
References: Hookup and Installation Instructions N9471 and Owner’s Manual N9472 LOAD NO.: 7
NOTES:
1. Connect to a grounded metal water pipe (16ga. at 15 ft.)
2. Total AUX. power available (including keypad power) is 500mA max
(300mA max for UL installations). Used for connection of devices rated
from 11.5 to 13.1VDC.
3. System must be tested on a weekly basis. For information, refer to manual.
4. Do not connect the transformer to a switch controlled receptacle.
Power varies with transformer (SEE NOTE 2).
5. Installation of equipment and wiring methods are required to be in accordance
with the National Electrical code and ANSI/NFPA No. 74.
6. Battery capacity for Emergency Standby is a minimum of 4 hours.
Under normal conditions this battery will last 3 years. Use only exact
replacements.
7. Maximum of 4 keypads. Available keypads include: XK-104 and 6805.
8. Limited energy cable must be used.
9. Non-replaceable fuse (F3). Return to manufacturer if blown. Do not solder in field.
10. Maximum for UL installations: Entry Delay, 45 sec.; Exit Delay, 60 sec.
11. For connection of VS-299 Siren Driver. Constant positive (+) unregulated output.
12. The PANIC or KEYSWITCH connected to terminals 5 & 7 is to be no more than 3 ft.
from the control unit with no barriers in between.
13. Programmable trigger outputs. If used for smoke detector power reset
see Detail A. See manual for programming information.
Use model XL-2GTC trigger cable.
SYSTEM DEFAULT RESET JUMPERS
TRANSFORMER
12VAC, 20VA
(Connect to 24 HR.
120VAC, 60 Hz Outlet
SEE NOTE 4)
+
-
SIREN
-
+
+_
_
+
SMOKE
DETECTOR
POWER
(9.5-12.2VDC,
50mA max)
BELL
2216 17 18 19 20 219 10 11 12 13 14 15
CONSTANT DC POWER (+)
10-15.5VDC
(SEE NOTE 11)
KEYPAD
(SEE NOTE 7)
BLACK
YELLOW
GREEN
RED
FIRE & BURGLARY
ALARM OUTPUT
(11.5-13.1VDC,
1A max)
HOME
TELCO
BROWN
GRAY HOME
GREEN
RED TELCO
AUX POWER
12VDC Reg., 500mA Max.
(SEE NOTE 2)
+
_
PANIC
2.2K
2.2K
4
3
2
1
EARTH GND.
(SEE NOTE 1)
5
6
7
8
2.2K
2.2K
ZONE 1
ZONE 2
ZONE 3
ZONE 4
JP1 JP2
To re-load factory default values, remove all power
(AC & DC). Short JP1 to JP2. With short still applied,
re-apply power (AC then DC), wait 5 seconds, then
remove short with power still applied.
ZONE
1
2
3
4
PANIC
(+)
1
3
4
6
7
(-)
2
2
5
5
5
TERMINALS
CONNNECTIONS FOR HOUSEHOLD FIRE/BURGLAR ALARM SYSTEM
P1
VBELL
T1
T2
+
BLACK
RED
12V, 4-6AH
BATTERY
MODEL 1240A
(SEE NOTE 6)
_
TRIGGER
OUTPUTS
(SEE NOTE 13)
Aux. Power
Bell Power
F3
Battery
4 Amps
This fuse is
NOT replaceable.
(SEE NOTE 9)
F1
F2
3 Amps
1 Amp
MODEL 368 CORD
TO RJ31X OR
CA31A JACK
SYSTEM STABILIZATION MODE: Upon initial powerup of the system, all of the lights on the LED
keypad(s) will go ON and then go OFF for approximately 2 min. 10 secs and/or the LCD keypad(s) will
display STAND BY! for approximately 2 min. 10 secs. This occurs on a total powerup (if ARMED or
DISARMED in its prior state) or after a system reset. If the total system power is lost then upon power
restoral, the system will return to the previous arming state. The 2 min. 10 secs. interval is used to allow
motion detectors (interior zones) to stabilize on power up in order to prevent false alarms. THIS OPTION
CAN BE DISABLED BY MOMENTARILY (5 second minimum) PUTTING A JUMPER BETWEEN TERMINALS
13 AND 12.

XL-1S Hookup and Installation Instructions
2–2
Terminal Connections
TERMINALS DESCRIPTION
1(+) & 2(-) Zone 1 (Requires 2.2K EOL resistor) [Default = DELAY]
3(+) & 2(-) Zone 2 (Requires 2.2K EOL resistor) [Default = INTERIOR]
4(+) & 5(-) Zone 3 (Requires 2.2K EOL resistor) [Default = PERIMETER]
6(+) & 5(-) Zone 4 (Requires 2.2K EOL resistor) [Default = PERIMETER]
ZONE INFORMATION:
Normally closed devices may be wired in series and/or normally open
devices in parallel with the 2.2k ohm end of line resistor on all zones
(Refer to the wiring diagram). The standard loop response time is 280 ms
on all zones. Each zone can be programmed for Fast Response (10 ms)
in programming (see questions #10-13). The factory default values for
each zone is listed in the table above, however any zone can be
programmed for the following types: Delay, Perimeter, Interior, Fire, 24
Hr. Alarm, or 24 Hr. Trouble. Further explanation of the zone types can
be found in the System Programming section of this manual.
NOTE: Loop response is defined as the minimum time required for a
fault to trip a zone.
5 & 7 PANIC CIRCUIT OR KEYSWITCH:
Normally Open PANIC circuit. This hardwired panic is a 24-hour zone
that can be programmed for silent or audible operation. The panic circuit
will activate with each violation, therefore a latched device is not
recommended. A momentary device is recommended. For UL
installations, the panic switch connected to these terminals is to be
located no more than 3 feet from the control unit, with no intervening
barriers (this is a supervision requirement only). If the keyswitch option
is selected (see programming question #05, location 2), then each
activation of the keyswitch will arm and disarm the system.
NOTE: EOL resistor is not required on this zone and is not supervised.
This zone does not report restore codes. If a supervised zone with restore
reporting ability is desired, then program one of the 4 ZONES as a 24Hr.
Alarm. If used as a keyswitch, then triggers are available for either an
arming or ready status indication (see programming question #07,
location 4).
8 EARTH GROUND:
Connect this grounding lug to a cold water pipe utilizing #18AWG wire at
a distance of no greater than 15 ft. Use a non-corrosive metal strap firmly
secured to the pipe to which the lead is electrically connected and
secured. If the premises pipes terminate in PVC, this terminal must be
connected to a six- (6) foot grounding rod.
9 10 11 12 KEYPADS:
A maximum of 4 keypads, either XK-104 or 6805, may be wired to these
terminals. The connections are as follows; 9 (BLACK = negative), 10
(YELLOW = data in), 11 (GREEN = data out) and 12 (RED = positive
power). Each keypad draws approximately 30mA. Maximum keypad
length is 500 feet using 22-gauge wire. NOTE: In some installations, it
may be necessary to use shielded wire to prevent radio frequency
interference.

Section 2 - System Wiring and Hookup
2–3
9 (-) & 12 (+) REGULATED POWER (11.5 - 13.1VDC):
The total regulated output power for motion detectors and other external
devices is 500mA at 11.8 - 12.5V for residential applications, or 12.0 -
12.5V for commercial applications, with less than 100 mVPP ripple. The
total regulated output capacity of the XL-1S includes the power available
from these terminals (9 & 12) as well as the power used by the keypads
and smoke detectors. Therefore, to determine the total power available
from these terminals subtract the power consumed by the keypads and
smoke detectors. See Auxiliary Device Current Draw Worksheet.
12 (+) 13 (-) SMOKE DETECTOR POWER OR TRIGGER #1 OUTPUT:
SMOKE DETECTOR POWER: This system will accept 9.5 - 12VDC four (4)
wire smoke detectors only. Approximately 50mA of current is available at
these terminals for powering all detectors and an EOL relay model
ESL2048. For UL installations see wiring diagram for hookup. NOTE:
Trigger #1 must be selected for smoke detector power (see program
question #07, location 3).
These terminals adhere to the fire verification and reset logic, which is
explained in the zone types section of this manual. Manual reset of smoke
detector power can be accomplished by entering a valid user code after
clearing alarm memory or using the asterisk (*) key.
14 15 16 17 TELEPHONE LINE:
Connect the model 368 cord as follows; 14 (GREEN = Telco Tip), 15 (RED
= Telco Ring), 16 (BROWN = Home Tip), 17 (GRAY = Home Ring). Insert
the plug into an USOCRJ31X jack (or a CA31A jack for Canadian
installations).
The FCC registration number is (AE398E-69554 AL-E), and the ringer
equivalence is (0.0B). The system should not be connected to party lines,
or coin operated phones.
If this control panel will be used for uploading, downloading or remote command applications, the
telephone line connected to the control panel
must not
be shared with a fax machine or modem.
Furthermore, this device should not be connected to a phone line that has call waiting, unless the
call waiting interrupt numbers are programmed into the panel dialing sequence.
18(+) CONSTANT DC POWER:
This terminal delivers constant unregulated 10.0-15.5VDC power for
devices requiring a constant power such as VS279. It is connected to a
bell fuse (F3). NOTE: Constant power for these devices can also be
obtained by splicing the RED (+) battery lead with an in-line fuse of 3
Amps.
19(+) & 20(-) BELL OUTPUT:
The total output power available for sounding devices is 1 amp at 10.5 -
15.5 VDC for residential applications, or 12.0 - 14.4 VDC for commercial
installations (750 mA for UL installations). These terminals will deliver
CONSTANT output on BURGLARY, AUDIBLE PANIC and BELL TEST.
On a FIRE condition, a PULSED output will be generated. There are
separate bell cutoff times programmable for Burglary and Fire conditions
within the programming sequence. For UL Household Fire Warning
System installations, the speaker must be mounted indoors for best
audibility. Also, for UL installations, use only one speaker. NOTE: Before
connecting sounding devices please consult their specifications for proper

XL-1S Hookup and Installation Instructions
2–4
current draw. Otherwise, the bell fuse (F3) may be blown. An option
exists to supervise the bell output terminals if zone 4 is programmed as a
fire zone (see program questions #10-13); refer to the following notes:
P1: VBELL (+) T1 (-) TRIGGER #1 OUTPUT:
P1-VBELL (+) & P1-T1 (-) or terminals 12 & 13 can be used for a trigger
#1 output. See programming question #07, location 3 for valid trigger
types. NOTE: In order to connect devices to the triggers use connector
XL-2GTC (trigger cable). Unless otherwise specified, the trigger output is
normally floating and actively sinks on activation (switched negative).
NFPA 72 REQUIREMENT: All the
interconnecting pathways, (cable, wire,
etc.) between the alarm system initiating
device (control panel) and the signaling
device (bell, speaker, siren, etc.) shall
be monitored for an occurrence of an
open circuit, which prevents the normal
operation of the system. An occurrence
of an open circuit shall be indicated by a
distinctive trouble signal.
BELL SUPERVISION (Mechanical Bell) - To meet the NFPA 72 requirement
program zone 4 as a Fire Zone (program question #13, locations 1
& 2). The bell is then supervised for an open circuit (not a short circuit)
across the bell output terminals; the keypad will indicate that a Fire
Trouble condition has occurred and Fire Trouble is reported to the CS if
enabled (program question #18, location 3). If the bell is already ringing,
the supervision will not take effect until after bell cutoff time. See the
diagram on the next page:
Mechanical Bell
22
(
+
)
23
(
-
)
Bell Out
p
ut
SIREN SUPERVISION (Self Contained Siren/Speaker) - To meet the NFPA 72
requirement program zone 4 as a Fire Zone (program question #13,
location 1). The siren is then supervised for an open circuit (not a short
circuit) across the bell output terminals; the keypad will indicate that a
Fire Trouble condition has occurred and Fire Trouble is reported to the
CS if enabled (program question #18, location 3). If the siren is already
sounding, the supervision will not take effect until after bell cutoff time.
NOTE: Use FBII models ZR-815C, ZR-815EC or ZR-830EC. See the
diagram below:
Self Contained Siren/S
p
eaker
22
(
+
)
23
(
-
)
Bell Out
p
ut
SPEAKER SUPERVISION (VS-299 Siren/Driver) - To supervise a speaker
connected to the VS-299 Siren Driver connect terminal 1 of the
VS-299 to the positive terminal of any zone programmed as a 24
Hour Trouble zone (program questions #10 - 13, locations 1 & 2).
The speaker is then supervised for an open circuit across the speaker
terminals (4 & 5) of the VS-299 and a code is reported to the CS if
enabled (program question #10 - 15, locations 3 & 4). Also, the connection
between the bell output terminals and the VS-299 Siren Driver may be
supervised by programming zone 4 as a Fire Zone (program

Section 2 - System Wiring and Hookup
2–5
question #13, locations 1 & 2) and connecting a 10K Ohm, 1/4 W
resistor across the bell output terminals to prevent a continuous
supervisory condition. See the diagram below:
VS-299
Siren Driver
8 Ohm S
p
eaker
5
4
2
7
22
(
+
)
23
(
-
)
Bell Out
p
ut
24 Hour Trouble Zone
1
Positive
(
+
)
10 K
Prevents Continuous Supervisory Condition
SPEAKER SUPERVISION (679S Siren/Driver) - To supervise a speaker
connected to the 679S Siren Driver connect a 5.6K Ohm resistor
between terminal 5 of the 679S and terminal 6 (+) of zone 4
programmed as a Fire zone (program question #13, locations 1 &
2). Replace the 2.2K Ohm EOL resistor on zone 4 with a 5.6K Ohm
resistor. The speaker is then supervised for an open circuit (not a short
circuit) across the speaker terminals (4 & 5) of the 679S. Also, the
connection between the bell output terminals and the 679S Siren Driver
will be supervised. If a supervisory occurs, the keypad will indicate that a
Fire Trouble condition has occurred on zone 4 and Fire Trouble is
reported to the CS if enabled (program question #18, location 3). If the
siren is already sounding, the supervision will not take effect until after
bell cutoff time. See the diagram on the next page:
9
(
+
)
8
(
-
)
679S Siren Driver
Zone 6 Pro
g
rammed
as Fire Zone 5.6K EOL
8 Ohm S
p
eaker
5.6K EOL
Additional
Resitor
5
4
1 or 3
2
Smoke
Detector
Re
p
lace 2.2K EOL w/5.6K
22
(
+
)
23
(
-
)
Bell Out
p
ut
21 & 22 TRANSFORMER:
Connect the 12 VAC 20VA transformer, utilizing 18awg wire at a
distance not to exceed 15 feet from the panel, to an unswitched 120 VAC
outlet.
Do not use any other transformer since this may result in improper
operation or damage to the unit.
The AC/LOW BAT LED on the keypad will remain ON, while AC power
is present. If an AC loss occurs the AC/LOW BAT LED will turn off
immediately. If AC remains OFF for 15 minutes, the system will pulse

XL-1S Hookup and Installation Instructions
2–6
the keypad buzzer and transmit to the central station, if programmed.
THE KEYPAD BUZZER CAN BE SILENCED by entry of any valid user
code. When AC restores the AC/LOW BAT LED will light immediately,
and a restore code will be reported, if programmed.
BACKUP BATTERY: The RED (+) and BLACK (-) flying leads must be connected to a 12 VDC
4-6AH GELL CELL, to serve as backup power in the event of AC loss.
A battery test occurs approximately every 4.5 minutes. Low battery
condition occurs at nominal 11VDC. The keypad AC/LOW BAT LED and
buzzer will PULSE SLOWLY when a low battery condition is detected.
The system reports this condition to the CS if programmed. Battery
restoral will occur WITHIN 4.5 minutes, at the NEXT battery test. THE
BUZZER MAY BE SILENCED by entry of any valid user code.
GROUND START: Ground start capability can be added to the system through addition of
the FBII Model 117 module. Consult the 117 Installation Instructions for
hookup information. With this device some systems can obtain dialtone
where it is not available. At the moment telephone line seizure occurs,
the Telco Tip is momentary connected to earth ground to access dial tone.
NOTE: The 117 module has not been tested for use in UL installations.
P1: VBELL, T1 & T2 TRIGGER OUTPUTS (1 & 2):
The control panel contains two programmable trigger outputs. Trigger #1
terminals are P1-VBELL (+) & P1-T1 (-) and for Trigger #2 P1-VBELL (+)
& P1-T2 (-). See programming question #07, location 4 for valid trigger
types. BY DEFAULT TRIGGER #1 IS ENABLED FOR SMOKE
DETECTOR POWER, WHICH CAN ALSO BE OBTAINED FROM
TERMINALS 12(+) & 13(-). TRIGGER #2 CANNOT BE SELECTED FOR
SMOKE POWER. NOTE: In order to connect devices to the triggers use
connector XL-2GTC (trigger cable). Unless otherwise specified, the
trigger output is normally floating and actively sinks on activation.
Connect to terminal 12 (+) to obtain a POSITIVE reference point. For UL
installations, the trigger outputs shall be connected to devices rated to
operate over the range from 10.1 - 14.0 VDC at 50 mA.
Auxiliary Device Current Draw Worksheet
DEVICE CURRENT DRAW
FOR EACH NUMBER
OF UNITS TOTAL CURRENT
FOR EACH
XK-104 Keypad 30mA ✴
6805 Keypad 60mA ✴
PIR ✴ ✴
Smoke Detector ✴ ✴
Glass Break Detector ✴ ✴
✴ ✴
✴ ✴
TOTAL CURRENT FOR ALL DEVICES =
(500mA max.)
NOTES: ✴Only applies if device is powered from control terminals 12
(+) & 13 (-).
✴✴ If using devices such as PIRs, smoke detectors, etc., refer to
the specifications for that particular device's current draw. If
the total current draw exceeds 500mA, then use an
additional power supply.

Section 2 - System Wiring and Hookup
2–7
Wiring Information for Keypads & Other Devices
Keypads & Other Devices
If single or multiple devices are connected to a single 4-wire or 2-wire run ("daisy chained")
to the control terminals, determine the current drawn by the unit(s) connected to the single
wire run, then refer to the Wiring Run Table below to determine the maximum wire length
that can be safely used for each wire size.
In some cases, the total current drawn may result in a value not shown in the table. For
example, if you plan to use #22 gauge wire and the total current drawn is 400 mA (a value
between 300 mA and 500 mA), the maximum wire length you should use is approximately 65
ft. (a length between 50 and 80 ft.). Other maximum wire lengths for values of current not
shown in the table can be calculated in a similar manner.
Maximum wire lengths for a device that is "homerun" to the control can also be
determined from the table, based on the current draw of that device alone.
Wiring Run Table For Devices Drawing Power From Terminals 12 (+) & 13 (-)
TOTAL CURRENT DRAWN BY ALL UNITS ON A SINGLE WIRE RUN
WIRE SIZE 50 mA or less 100 mA 300 mA 500 mA
#22 500 ft. (152 m.) 250 ft. (76 m.) 80 ft. (24 m.) 50 ft. (15 m.)
#20 750 ft. (228.6 m.) 380 ft. (116 m.) 130 ft. (39.6 m.) 80 ft. (24 m.)
#18 1300 ft. (396 m.) 650 ft. (198 m.) 220 ft. (67 m.) 130 ft. (39.6 m.)
#16 2000 ft. (609.6 m.) 1000 ft. (305 m.) 330 ft. (100.5 m.) 200 ft. (70 m.)
Examples:
1. What is the maximum distance for one XK-104 keypad drawing 30 mA using # 20 gauge
wire?
Using the table above, the keypad can be placed no greater than 750 ft. away
from the panel.
2. What is the maximum distance for three 6805 keypads drawing 180 mA (60 mA each)
using # 20 gauge wire connected in a single wire run?
Using the table above, the farthest keypad can be placed no greater than 292 ft.
away from the panel.
3. What is the maximum distance for 5 smoke detectors drawing 0.25 mA (5 µA each) using
# 22 gauge wire connected in a single wire run?
Using the table above, the farthest smoke detector can be placed no greater
than 500 ft. away from the panel.

XL-1S Hookup and Installation Instructions
2–8

3–1
SECTION 3
PC Board Mounting
••••••••••••••••••••••••••••••••••••••••••••••••••
Mounting the PC Board
Before mounting the printed circuit board, be certain that the appropriate metal knockouts
have been removed. DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE
CIRCUIT BOARD HAS BEEN INSTALLED.
1. Hang the three mounting clips on the raised cabinet tabs. Observe proper clip orientation
to avoid damage to the clip when mounting screws are tightened and to avoid problems
with insertion and removal of the PC board.
2. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that
the board rests in the slots as indicated in the diagram shown below.
3. Swing the base of the board onto the mounting clips.
4. Place the washer provided over the wire jumpers located within the middle of the PC
board. Secure the PC board to the middle mounting clip of the enclosure through the
washer using the screw provided.
5. Secure the remaining sides of the PC board to the enclosure using the screws provided.
PC Board
KNOCKOUT
DETAIL SIDE VIEW
OF BOARD INSERTED
INTO SLOTS
DETAIL SIDE VIEW
OF CLIP AND BOARD
INSTALLED
B
A
DETAIL SIDE VIEW
OF CLIP INSTALLATION:
A. CABINET TAB
WITHOUT CLIP
B. CABINET TAB
WITH HANGING
CLIP
Metal Cabinet
3rd CLIP
REQUIRED

XL-1S Hookup and Installation Instructions
3–2
NOTE: The front face of the enclosure can be completely removed from the enclosure to gain
unrestricted access to the control panel during installation. The front of the enclosure can be
removed as follows:
1. Open the enclosure to its fully extended position (approx. 90 degrees)
2. Lift the control panel door and remove the door from the enclosure.
Table of contents
Other FBII Security System manuals

FBII
FBII XL Star 4500 User manual

FBII
FBII OMNI-624EU User manual

FBII
FBII OMNI-408EU User manual

FBII
FBII OMNI-400 EU Assembly instructions

FBII
FBII XL-2P User manual

FBII
FBII XL-2 User manual

FBII
FBII XL-20 User manual

FBII
FBII XL-4B User manual

FBII
FBII OMNI-600EU User manual

FBII
FBII Star XL4800 EZ User manual