Honeywell ESSER TAM User manual

Manual de Instalación
Módulo de Alarma Técnica (TAL)
Installation Instruction
Technical Alarm Module (TAM)
(Ref. / Part. No. 804863, 804864, 805863, 805864)
798831 Cambios técnicos reservados!
06.2007 EGB Technical changes reserved!
Novar GmbH a Honeywell Company
Dieselstraße 2, D-41469 Neuss
Internet: www.esser-systems.de
E-Mail: [email protected]
E
Durante la revisión de los módulos TAL, deben tenerse en
cuenta la activación de alarmas y conexión a sistemas
centralizados de alarma remotos (como Master Box).
Información adicional y actualizada
Las especificaciones se refieren al la fecha de creación del
documento y pueden ser modificadas o variadas sobre la
normativa aplicada o la información facilitada.
Para obtener la información actualizada para
mantenimiento o configuración de los sistemas, contacte
con su proveedor para que se la facilite o en
www.esser-systems.de.
GB
The alarm activation and triggering of notifying systems e.g.
manned centre link (Master box) must be observed during
any Service of the TAM.
Additional and updated Informations
The product specification relate to the date of issue and
may differ due to modifications and/or amended Standards
and Regulations from the given informations.
For updated informations to commissioning and
maintenance of Fire alarm detectors refer to
www.esser-systems.de.
E
Importante!
Estas instrucciones deben ser tenidas en cuenta cuidadosamente
antes de proceder a la puesta en marcha del Módulo de Alarma
Técnica. Devoluciones bajo garantía serán invalidadas en caso de
avería causada por no seguir estas instrucciones. No se aceptará
responsabilidad por ningún tipo de pérdidas derivadas.
Instrucciones de Seguridad
•No conecte el módulo TAL a alimentación de 220 Vca.
•El módulo TAL solo puede usarse dentro de los límites de
temperatura de trabajo.
•Solo técnicos cualificados que estén familiarizados con los
riesgos específicos y las normativas correspondientes deben
llevar a cabo las operaciones de reparación y mantenimiento
del TAL.
•El módulo TAL solo puede conectarse a centrales 8000 /
IQ8Control.
•El módulo TAL solo puede conectarse en interiores.
•No realice modificaciones sobre el módulo.
Conexionado Fig. 1
El módulo de Alarma Técnica (TAL) se conecta al lazo analógico
de sistemas 8000 / IQ8Control para reconocimiento, transmisión e
indicación individual de alarmas técnicas.
Compruebe la dirección del cableado:
X1, terminal -UL(IN) (entrada) ⇒-UL(OUT) (salida).
Use cable tipo IY (St) Y n x 2 x 0,8 mm con la
especificación adecuada para sistemas de detección de
incendio!. La pantalla evitará posibles interferencias.
Tipos de TAL
Entrada Salida/Tipo Caja Ref.
Optoacoplada Aislador Plástico ABS 804863
Optoacoplada Aislador Makrolon 805863
Optoacoplada Relé Plástico ABS 804864
Optoacoplada Relé Makrolon 805864
TAL con aislador (Ref. 80x863)
Los aisladores de lazo permiten el funcionamiento en caso de
cortocircuito en el cableado de lazo.
Los aisladores más próximos al cortocircuito abren (aíslan) el
tramo de lazo, permitiendo la comunicación en el resto del lazo.
Un único cortocircuito entre aisladores no afectará al
funcionamiento del resto del lazo.
TAL con salida de Relé (Ref. 80x864) Fig. 2
La conexión del relé NC/C (normalmente cerrado) y C/NO
(normalmente abierto), puede usarse para realizar maniobras
externas. El contacto puede activarse cuando el TAL esté
activado. El relé se configura por activación de zonas como
cualquier salida.
Revise el límite máximo del contacto 30V DC / 1A!
Indicador Remoto. Fig. 3
Es posible conectar un LED indicador remoto de alarma. El
cableado para el indicador remoto no debe exceder el 100m!. Es
posible conectar los siguientes indicadores remotos. Ref: 781804,
781814 y 801824.
Entrada optoacoplada Fig. 4
Es posible conectar un contacto externo al módulo de Alarma
Técnica (TAL) mediante activación por tensión. Esta entrada no
es supervisada. En caso de no usar la entrada normal de alarma,
ésta deberá cerrarse con resistencia de 10KOhm.
Conexión de Pulsadores de Alarma Fig. 5 / 6
El módulo TAL permite conectar pulsadores de alarma
convencionales con resistencia de alarma de 1K a la entrada D-
Line. En caso de alarma de cualquier pulsador conectado al TAL,
se indicará como alarma del Tal según su configuración de
dirección y zona La longitud máxima del cableado de la línea no
excederá de 500m!. El último equipo deberá disponer de
resistencia final de línea de 10 KOhm.
Si no se usa la entrada de alarma Técnica, deberá colocarse una
resistencia final de línea de 10 KOhms ( véase Fig. 5) entre los
terminales de D-Line (Configuración de fábrica desde equipos con
índice D).
Rearme
La activación de alarma del Tal es enclavada.
Para rearmar el TAL, rearme el panel o conecte la zona
correspondiente.
Datos Técnicos
Alimentación: 8 V cc bis 42 V cc
Relés
-Límite Contacto: 30 V cc / 1 A
-Tipo de contacto: Contacto seco
Entrada Optoacoplada: 2,4 V cc a 24 V cc /
0,4 a 15 mA
Consumo Reposo (19 V) 45 μA aprox.
Consumo Alarma: typ. 9 mA, pulsante
Indicador de alarma: LED, Rojo
Terminales: 1,5 mm² max.
Temperatura ambiental: -20 °C a +70 °C
Temp. almacenamiento: -30 °C a +75 °C
Grado Protección: IP 42 IP 54
Caja: Plástico ABS Makrolon
Color: Grís blanco Blanco
Peso: 200 g apróx. 300 g aprox.
Dimensiones (a x h x f) 124 x 124 x 38
(mm)
122 x 120 x 55
(mm)
GB
Warning!
These installation instructions must be studied carefully before
commissioning the Technical Alarm Module. Claims under
warranty will be invalidated in the event of damage caused by non-
compliance with the installation instructions. No liability is accepted
for any resulting consequential loss.
Safety instructions
•It is not allowed to connect the TAM to the mains supply.
•The TAM can only be used in the appropriate temperature
range.
•Maintenance and Service of the TAM must be qualified
personnel which is familiar with the regulations and the related
dangers.
•The TAM can only be connected to Fire Alarm System 8000 /
IQ8Control.
•It is only allowed to install the TAM indoors.
•It is not allowed to modify the TAM.
Wiring Fig. 1
The Technical Alarm Module (TAM) is connected to the analog
loop of the series 8000 / IQ8Control fire alarm system for
recognition, transmission and individual display of technical
alarms.
Observe the direction of the wiring:
X1, terminal -UL(IN) (input) ⇒-UL(OUT) (output).
Use cable IY (St) Y n x 2 x 0,8 mm with special
specification or fire detection cable!
The shielding is used to prevent EMI.
Versions of TAM
Input Type/Output Housing Part No.
Optocoupler Isolator ABS plastic 804863
Optocoupler Isolator Makrolon 805863
Optocoupler Relay ABS plastic 804864
Optocoupler Relay Makrolon 805864
TAM with isolator (Part No. 80x863)
Loop isolators provide the operation in case of a short circuit on
the loop.
The isolators next to the short circuit opens and disables the
section between the two isolators on the loop.
A single wire break does not take affect to the proper operation
of the loop.
TAM with relay output (Part No. 80x864) Fig. 2
The connectors of the 2nd micro switch NC/C (normally closed)
and NO/C (normally open) may be used to control external
devices. The contact will be closed when the TAL has been
released. The relay output may be triggered by a programmed
control zone in the customer data of the FACP.
Observe max. contact rating 30V DC / 1A!
Remote indicator Fig. 3
A remote LED indicator is used for an optical indication of alarm
condition. The maximum length of wire for the remote LED
indicator can not be more than 100 m! The following Remote LED
Indicators may be connected: Part No. 781804, 781814 and
801824.
Optocoupler input Fig. 4
It is possible to connect an external alarm contact (e.g. switch) to
the intelligent Technical Alarm Module. The input is not monitored.
The unused input of the external D-Line must be terminated with
an End-of-line 10KOhm resistor.
Connection of an external detector zone Fig. 5 / 6
One TAM provides the connection of an external detector zone
(D-Line) with up to 10 conventional Manual call points and an
internal alarm 1KOhm resistor per MCP (not according to VdS). If
activated the address and the programmed additional text of the
TAM, where the external zone is connected to, will be displayed.
The maximum length of the cable for the external D-Line must not
exceed 500 meters! The last detector of the external zone must be
terminated with a 10KOhm End-of-line resistor.
If no external D-Line is connected the 10KOhm terminating
resistor (factory default from Hardware index D) must be
connected directly to the terminals (refer to Fig. 5).
Reset
The TAM activation is latching.
To reset the TAM reset FACP or corresponding zone.
Technical Data
Operating voltage: 8 V DC to 42 V DC
Relay
-Contact rating: 30 V DC / 1 A
-Change over contact: floating contact
Optocoupler: 2,4 V DC to 24 V DC /
0,4 to 15 mA
Quiescent current @ 19 V DC: ca. 45 μA
Alarm current: typ. 9 mA, pulsed
Alarm indicator: LED, red
Terminals: max. 1,5 mm²
Ambient temperature: -20 °C to +70 °C
Storage temperature: -30 °C to +75 °C
Protection rating: IP 42 IP 54
Housing: ABS plastic Makrolon
Colour: grey white white
Weight: approx. 200 g approx. 300 g
Dimensions (w x h x d): 124 x 124 x 38
(mm)
122 x 120 x 55
(mm)
Conexiones Wiring
+
-
+
-
A B
X1
SCHIRM -UL -UL
out in +UL
X1
SCHIRM -UL -UL
out in +UL
X1
SCHIRM -UL -UL
out in +UL
Fig. 1 : Ejemplo, conexionado lazo analógico sistema 8000 / IQ8Control
Fig. 1 : Example, analog loop wiring, fire alarm system 8000 / IQ8Control
NONC C X2
-+
LED
X1
Art.-Nr./Part No.
781804, 781814, 801824
Input
OPTO
2,4 V DC - 24 V D
C
X1
Fig. 2 : Contacto seco ( Solo Ref.. 80x864)
Fig. 2 : Change over contact, floating (only Part No. 80x864) Fig. 3 : Indicador remoto LED
Fig. 3 : Remote LED indicator Abb. 4 : Entrada optoacoplada
Fig. 4 : Optocoupler input
X1
-ext +ext
D-Linie
R=10 kΩ
X1
-ext +ext
D-Linie
R=10 kΩ
n
1
Handmelder ohne LED
MCP without LED
2
X1
1
-ext +ext
D-Linie
2
externer Schaltkontakt
external contact
1K
1K
R=10 kΩ
Fig. 5 : Final de línea entrada
Fig. 5 : End of line resistor Fig. 6 : Ejemplo de conexión de pulsadores a la entrada (D-Line)
Fig. 6 : Example, connecting ext. detector zone (D-Line)
Pulsadores Convencionales (1KΩ) sin LED
MCP without LED
Contacto externo (1KΩ)
External contact (1KΩ)

This manual suits for next models

4

Other Honeywell Security System manuals

Honeywell CommerCialPro 7000 Operation manual

Honeywell

Honeywell CommerCialPro 7000 Operation manual

Honeywell Accenta Series Quick start guide

Honeywell

Honeywell Accenta Series Quick start guide

Honeywell LYNX Touch SIA User manual

Honeywell

Honeywell LYNX Touch SIA User manual

Honeywell HS-6270 User manual

Honeywell

Honeywell HS-6270 User manual

Honeywell SILENT KNIGHT RA-2000 User manual

Honeywell

Honeywell SILENT KNIGHT RA-2000 User manual

Honeywell ADEMCO VISTA-10P Assembly instructions

Honeywell

Honeywell ADEMCO VISTA-10P Assembly instructions

Honeywell Friedland FGGA07 Series User manual

Honeywell

Honeywell Friedland FGGA07 Series User manual

Honeywell Domonial User manual

Honeywell

Honeywell Domonial User manual

Honeywell Home SI800MS User manual

Honeywell

Honeywell Home SI800MS User manual

Honeywell SEF8M User manual

Honeywell

Honeywell SEF8M User manual

Honeywell VISTA-20PSeries User manual

Honeywell

Honeywell VISTA-20PSeries User manual

Honeywell DTPI8M User manual

Honeywell

Honeywell DTPI8M User manual

Honeywell ADEMCO 745 3 Series Assembly instructions

Honeywell

Honeywell ADEMCO 745 3 Series Assembly instructions

Honeywell RAPID EYE K9696V2 User manual

Honeywell

Honeywell RAPID EYE K9696V2 User manual

Honeywell Lyric Operator's manual

Honeywell

Honeywell Lyric Operator's manual

Honeywell LYNXR User manual

Honeywell

Honeywell LYNXR User manual

Honeywell Fire-Lite Alarms MS-9200UDLSC User manual

Honeywell

Honeywell Fire-Lite Alarms MS-9200UDLSC User manual

Honeywell VISTA-32FBPT User manual

Honeywell

Honeywell VISTA-32FBPT User manual

Honeywell NOTIFIER PAN1-PLUS User manual

Honeywell

Honeywell NOTIFIER PAN1-PLUS User manual

Honeywell LYNX User manual

Honeywell

Honeywell LYNX User manual

Honeywell Lynx Plus Series Assembly instructions

Honeywell

Honeywell Lynx Plus Series Assembly instructions

Honeywell LYNX Touch Security System User manual

Honeywell

Honeywell LYNX Touch Security System User manual

Honeywell ESSER IQ8MCP User manual

Honeywell

Honeywell ESSER IQ8MCP User manual

Honeywell AlarmNet 360 Reference guide

Honeywell

Honeywell AlarmNet 360 Reference guide

Popular Security System manuals by other brands

ADEMCO Security System VISTA-10SE installation instructions

ADEMCO

ADEMCO Security System VISTA-10SE installation instructions

Risco WisDom user manual

Risco

Risco WisDom user manual

STI Exit Stopper STI-6400 Series quick start guide

STI

STI Exit Stopper STI-6400 Series quick start guide

Visonic SR-730 PG2 - installation instructions

Visonic

Visonic SR-730 PG2 - installation instructions

Kidde KN-COP-DP-10YB user guide

Kidde

Kidde KN-COP-DP-10YB user guide

Zicom Z.HA.HO.GSM.ATOUCH.KIT user manual

Zicom

Zicom Z.HA.HO.GSM.ATOUCH.KIT user manual

Eaton FHF DSLB 20 LED Technical manual

Eaton

Eaton FHF DSLB 20 LED Technical manual

COMPRO CO BL 50 AL 230 2F manual

COMPRO

COMPRO CO BL 50 AL 230 2F manual

SmartPool PoolEye PE23 user guide

SmartPool

SmartPool PoolEye PE23 user guide

ROBENS DUNKERY instruction manual

ROBENS

ROBENS DUNKERY instruction manual

Eaton EVT-300 Driver Instructions

Eaton

Eaton EVT-300 Driver Instructions

MWf MF Security HD-30 user manual

MWf

MWf MF Security HD-30 user manual

Raidon InTANK IR8624-S3 user manual

Raidon

Raidon InTANK IR8624-S3 user manual

Lorex VANTAGE LH110 ECO SERIES Product information

Lorex

Lorex VANTAGE LH110 ECO SERIES Product information

Cocoon CS03A Setup guide

Cocoon

Cocoon CS03A Setup guide

ZKTeco SF1008+ quick start guide

ZKTeco

ZKTeco SF1008+ quick start guide

Electronics Line EL-2626AC installation guide

Electronics Line

Electronics Line EL-2626AC installation guide

Climax Mobile Lite Installer's guide

Climax

Climax Mobile Lite Installer's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.