manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Smoke Alarm
  8. •
  9. Honeywell Fire-Lite Alarms OSI-RI-FL User manual

Honeywell Fire-Lite Alarms OSI-RI-FL User manual

Quick Start Guide – OSI-RI-FL Smoke Detection System
Mounting the detector
Remove detachable front rim cover.
To detach the Imager part from the backbox, loosen the 3 holding screws.
To provide cable access to the Termination Card of the Imager remove the cut-outs from the back, bottom or top
of the main assembly by using a sharp blade to cut around the circular discs.
Secure the back box directly onto the mounting surface using any suitable number of the 5 pilot holes in the
backbox.
Use appropriate fasteners to secure the back box component to the mounting surface.
Wire the Termination Card on the Imager:
• Wire the initiating device circuit on the Imager Termination Card using the addressable loop.
• Wire external power to the unit via the POWER terminals.
• Wire the Remote Indicator and/or remote test or reset units if required.
• Securely connect the wires to the plug-in terminals and engage in the receptacles at the back of the Imager.
• Switch on the heater if the installation requires so.
• Set the detector address using the rotary switches
• Re-attach the Imager to the back box
• Remove the protective lm from the lens surface of the imager (TBD).
• Connect power to the Imager.
3
4
This guide provides information on how to install the OSI-RI-FL Smoke Detection System.
Extensive product and critical product security information can be found in the OSI-RI-FL Installation Guide (Document
No. E56-6584 [33807]) available at www.relite.com.
The OSI-RI-FL system consists of an Imager and a reector.
Determine the positions of the Imager and reector components.
Make sure that the intended mounting locations meet the following criteria:
• Detector spacing must comply with local codes and standards
• Reector must be located within the Field of View (FOV) of the Imager
• Clear path between the reector and Imager
• Mounted well above the head-height of people and obstructions
• Avoid direct sunlight onto the units
The Imager and reector should be placed within a recommended distance below the ceiling. This value will
vary according to regional specications, geometry, and specic requirements for the installation. The distance
for at ceilings and basic spacing requirements (S) is shown in the following table.
Standard Distance from Ceiling Maximum Spacing (S)
NFPA 72 300 mm (12 in.) minimum 18.3 m (60 ft)
AS1670.1 25 to 600 mm (1 to 23.6 in.) 14 m (45.9 ft)
BS5839.1 25 to 600 mm (1 to 23.6 in.) 15 m (49.2 ft)
GB50166 300 to 1000 mm (11.8 to 39.4 in.) 14 m (45.9 ft)
For full information on spacing requirements, please refer to your local codes and standards.
1
Mount the reector using the drill template
Available in an appendix in the Product Guide.
2
Ex. Distances according to NFPA 72
1/2 S maximum
ReflectorTx/Rx
S
Tx/Rx Reflector
16 ft. (5m) minimum
328 ft. (100m) maximum
1/4 S
maximu
m
12” minimum
(0.3m)
10’ (3.0m)
minimum
Typical
30’
(9.1m) maximum
To First
Detectors
1/2 S S
Wall
T1
RTS151/Key
Terminals
T3
T4
T5
T2
OSI-RI Terminals
External
Jumper
10k ohm
External
Resistor
Remote Alarm Output
Remote Trouble Output
Remote Test/Reset Input
AUX -
T2-1
T2-3
T2-2
T2-4
Alarm
Signal
Circuit
Trouble
Signal
Circuit
Yellow
Red
T2-1
T2-2
T2-4
Remote LED connections
T3
T2
T1
Not Used
Not Used
Heater Power In -
Heater Power In +
AUX (-)
Remote Test/Reset Input
Remote Trouble Output
Remote Alarm Output
SLC - OUT
SLC - IN
SLC + OUT
SLC + IN
USB
Connector
Cable knock-outs
bottom
Cable knock-outs
top
Holes for the fixing
of the detector
Large knock-out
for 4” J-Box
Mounting holes
I56-6584-001
Rotary switches for
setting the address
Heater Power In
-
Heater Power In +
Heater on/off switch
Communication Line
32 VDC max.
Twisted pair is
recommended
To next deviceFrom panel
or previous
device
+
-
-
+
Jumper
No shunts
No heater
Shunts in
Heater ON
shunts
heater
All manuals and user guides at all-guides.com
all-guides.com
Document: I56-6584-001 (33797_01)
One Fire-Lite Place, Northford, CT 06472-1601 USA
USA - Phone: (203) 484-7161
Canada - Phone: (905) 856-8733
www.relite.com
7
8
9
Operation after a Power Failure
After a power failure of any duration, when the supply is restored, the detector will check the possible new
situation versus it memorized data.
If the reector is found in the same position and all parameters are within acceptable limits, the detector will
resume its operation and go out of fault condition.
If any signicant parameters have changed, it will remain in a fault condition and a re-initialization will be required.
Imager reset
The fault LED is non-latching but the alarm LED can be set to latching by the FACP. The Imager alarm can be
reset from the FACP.
6Testing the installation
After the commissioning, the detector must be tested for correct alarming by using the OSP-004 test lter at the
reector or using the remote test station. When using the RTS151KEY for testing the detector, the remote fault
LED will blink the set sensitivity of the detector. The number of blinks, similar to section 5, will represent the set
sensitivity and the sequence is repeated every 3 seconds till the detector is reset.
5Initialization and commissioning
Ensure that neither you nor any other objects are in the line of sight between the detector and the reector and
start to manually align the Imager to the reector.
The OSP-002 Laser Alignment Tool can be used for the rough alignment if the system is to be installed at longer
distances or in heavy lit environments.
Follow these steps to adjust the optical sphere of the detector component to align the system:
• Make sure the lever is the 3 o’clock position.
• The 4 arrows will intuitively guide the user to optimal eyeball alignment.
Likely the alignment process will start with all arrows red.
• Gently move the eyeball until all arrows and the middle green LED blink green for the eyeball to be optimal
aligned.
• When all arrows are green, gently lock the eyeball by moving the lever down till the eyeball is solidly locked.
The lever is now in the 5 o’clock position and you feel the resistance of the locked position.
By locking the eyeball an internal switch is activated and the detector will now start its initiation or commissioning
process. A normal commissioning process takes roughly 10 seconds. During the commissioning process, the
beam path must remain clear from object intrusions.In this process cycle, the detector will measure the size of the
reector in the FOV and set the sensitivity automatically to the optimum sensitivity for the specic distance.
Before going in operational mode, the detector will show its set sensitivity. This is shown by blinking the 4 arrows
to the color yellow, reecting the % of selected obscuration/sensitivity. The key is; 1 blink = 25%, 2 blinks = 30%,
3 blinks = 40% and 4 blinks = 50%. After 5 seconds, the scenario will be repeated a second time and the arrows
LEDs go out and the front OK LED blinks green. The detector is now in operation and working correctly.
The paintable rim can now be snapped over the front to secure the locking lever and to hide the alignment LEDS
and locking mechanism.
Applying the cover also secures the locking lever in position.
Operation Modes and Troubleshooting Guide OSI-RI-FL
Modes Red and
Remote Alarm
output
Yellow and Remote
Trouble Output
Green Initiating means Comments &
Troubleshooting Tips
Power on Off Blink Off Apply Power from
discharged state
• All wiring correctly done.
• Address switches set.
Alignment Off Blink Off Lever in 3:00 position
and commissioning is
active
• Ready to perform
alignment.
• Follow guidance from the
4 arrows to correctly align.
Initializing/
Commissioning
Off Blink Off Lock lever in 6:00
position to start
commissioning
• Commissioning and
setting sensitivity.
• Do not interrupt beam.
Normal Off Off Blink Successful completion
of initialization or
detector reset
• Initializing nished.
• Detector operates normal
in quiescent condition.
• Detector successfully
reset.
Alarm On Off Off Smoke, Test Filter
or RTS151KEY Test
Station
• Blinks till reset from FACP.
Trouble-Drift
Compensation
Off 3 Quick Blinks Blink Long Term Drift
Reference Out of 20%
Range
• Reduced IR Signal
• Clean detector and
reector.
Trouble-Beam
Blockage
Off 4 Quick Blinks Blink Beam blockage
or detector out of
alignment
• Remove blockage or re-
align detector
• Faulty unit.
Trouble-Imager
saturation
Off 5 Quick Blinks Blink Imager saturated • Sunlight or very strong
light into detector or
reector.
• Re-position detector or
reector.
• Remove light source.
Test activated-Pass
Result
On Blinks the set
sensitivity by
number of blinks (1-
4). Repeats every 3
seconds till reset.
Off FACP or RTS151KEY • Remains in alarm until
reset by FACP.
• Number of lit arrows
indicates sensitivity
level that was selected
automatically.
Level down
OSP-002 Laser
Alignment Tool
Reflector
All manuals and user guides at all-guides.com

Other Honeywell Smoke Alarm manuals

Honeywell SiXSMOKE-CN User manual

Honeywell

Honeywell SiXSMOKE-CN User manual

Honeywell DF8M User manual

Honeywell

Honeywell DF8M User manual

Honeywell XLS-278 User manual

Honeywell

Honeywell XLS-278 User manual

Honeywell FireLite BEAM355 User manual

Honeywell

Honeywell FireLite BEAM355 User manual

Honeywell 5806W3 Assembly instructions

Honeywell

Honeywell 5806W3 Assembly instructions

Honeywell GENT Venturi-Air Duct Kit User manual

Honeywell

Honeywell GENT Venturi-Air Duct Kit User manual

Honeywell C8600A User manual

Honeywell

Honeywell C8600A User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell FCI 1151 User manual

Honeywell

Honeywell FCI 1151 User manual

Honeywell Fire-Lite Alarms SD365R User manual

Honeywell

Honeywell Fire-Lite Alarms SD365R User manual

Honeywell Photoelectronic Smoke/Temperature Detector... Assembly instructions

Honeywell

Honeywell Photoelectronic Smoke/Temperature Detector... Assembly instructions

Honeywell 5800COMBO-CN User manual

Honeywell

Honeywell 5800COMBO-CN User manual

Honeywell FIre LIte ALarms D350PL User manual

Honeywell

Honeywell FIre LIte ALarms D350PL User manual

Honeywell SS4-A2 User manual

Honeywell

Honeywell SS4-A2 User manual

Honeywell Notifier VESDA-E VEA Series User manual

Honeywell

Honeywell Notifier VESDA-E VEA Series User manual

Honeywell Xtralis FAAST FLEX FLX-010 User manual

Honeywell

Honeywell Xtralis FAAST FLEX FLX-010 User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell TC842B1007AE User manual

Honeywell

Honeywell TC842B1007AE User manual

Honeywell JTYJ-GD-01BW User manual

Honeywell

Honeywell JTYJ-GD-01BW User manual

Honeywell FCI 1400 User manual

Honeywell

Honeywell FCI 1400 User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Honeywell MS-5UD Series User manual

Honeywell

Honeywell MS-5UD Series User manual

Honeywell FMST FXV(E) Series User manual

Honeywell

Honeywell FMST FXV(E) Series User manual

Honeywell DFS8MS User manual

Honeywell

Honeywell DFS8MS User manual

Popular Smoke Alarm manuals by other brands

AJAX FireProtect 2 operating instructions

AJAX

AJAX FireProtect 2 operating instructions

System Sensor Innovair 200 Series quick start guide

System Sensor

System Sensor Innovair 200 Series quick start guide

Fike OSI-RI-FIK quick start guide

Fike

Fike OSI-RI-FIK quick start guide

Greenheck Smoke Dampers SMD-203 Specifications

Greenheck

Greenheck Smoke Dampers SMD-203 Specifications

Fire-Lite Alarms OSI-RI-FL quick start guide

Fire-Lite Alarms

Fire-Lite Alarms OSI-RI-FL quick start guide

Avidsen HomeSmoke user guide

Avidsen

Avidsen HomeSmoke user guide

Eldes EWF1 manual

Eldes

Eldes EWF1 manual

DELTA DORE DFR TYXAL+ manual

DELTA DORE

DELTA DORE DFR TYXAL+ manual

BAT BT 166 User handbook

BAT

BAT BT 166 User handbook

Universal Security Instruments Sensing Plus AMIC3511S instructions

Universal Security Instruments

Universal Security Instruments Sensing Plus AMIC3511S instructions

Chacon 34234 user manual

Chacon

Chacon 34234 user manual

Notifier HPX-751 Installation and maintenance instructions

Notifier

Notifier HPX-751 Installation and maintenance instructions

System Sensor 2100S Installation and maintenance instructions

System Sensor

System Sensor 2100S Installation and maintenance instructions

Hekatron LRS 01 installation instructions

Hekatron

Hekatron LRS 01 installation instructions

U-Line H-9468 Installation

U-Line

U-Line H-9468 Installation

Rielta IPD-E Series installation guide

Rielta

Rielta IPD-E Series installation guide

Bellman & Symfon BE1289 manual

Bellman & Symfon

Bellman & Symfon BE1289 manual

First Alert ONELINK CO511 user manual

First Alert

First Alert ONELINK CO511 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.