Honeywell SmartLine RMA801 Instruction Manual

SmartLine RMA801 HART/DE Remote Indicator Assembly
Quick Start Installation Guide
34-ST-25-63, Revision 2, March 2019
This document provides descriptions
and procedures for the Quick
Installation of Honeywell’s family of
SmartLine Remote Indicator.
The SmartLine Remote Indicator is a
configurable intelligent field device
which functions as an output and
status indicator for any HART and
DE devices.
For full details refer to the manuals
listed below for protocols, user
Interface (HMI) operation, Installation,
configuration, calibration,
maintenance, parts, and safety and
approvals etc. including options
Copyrights, Notices and
Trademarks.
Copyright 2019 by Honeywell
Revision 2, March 2019
Trademarks
SmartLine, RMA are U.S. registered
trademarks of Honeywell Inc.
HART® is Trademarks of
FieldComm Group™
Table of Contents
Installation and setup.................................................................................1
Site evaluation............................................................................................1
Installation precautions..............................................................................1
Explosion-Proof Conduit Seal....................................................................1
Mounting Remote indicator........................................................................2
Mounting Dimensions ................................................................................2
Bracket Mounting.......................................................................................2
Wiring a Remote Indicator .........................................................................2
Terminal Block ...........................................................................................2
Wiring Connections and Power Up............................................................3
Wiring procedure Options..........................................................................3
DEVICE CONFIGURATION ......................................................................3
Appendix A. PRODUCT CERTIFICATIONS .............................................3
Figure 1: Electronics Housing Components ..............................................1
Figure 2: Typical Pipe Mounted Installations.............................................2
Figure 3: Mounting Bracket Secured to a Remote indicator .....................2
Figure 4: Pipe Mounting Bracket Secured to a Horizontal or Vertical
Pipe............................................................................................................2
Figure 5: Remote Indicator Secured to a Wall Mounting Bracket.............2
Figure 6: DE/ANALOG Terminal Block......................................................2
Figure 7: RMA801 Terminal Block.............................................................2
Figure 8: Remote Indicator connected to the negative loop wire..............3
Figure 9: Remote Indicator connected to the negative loop wire..............3
Figure 10: Remote Indicator connected to the positive loop wire .............3
Documentation
To access complete documentation, including language variants, scan
the QR code below using your smart phone/device or QR code scanner.
Go to the APP store for your free Smartphone QR scanner
Or you can follow the URL to access the online SmartLine HUB page.
The HUB page will contain direct links to open SmartLine product
documentation.
URL QR Code
https://hwll.co/SmartLineHUB
Features and Options
The RMA801 Remote Indicator provides a means of remote-mounting a indicator (display)
that is associated with a Honeywell Smartline Transmitter or any transmitter operating in a
4-20 mA current loop.
The RMA801 is a DE/Analog Remote Indicator which can be connected anywhere along
the current loop.
For analog PV, the RMA801 measures the loop current and displays the equivalent PV
value on the display.
The RMA801 will autoconfigure when connected to Honeywell STT700/STT250 DE
transmitters when a database upload is performed.
This document provides the information for a quick setup. For detailed information, please refer
RMA801 user manual, 34-ST-25-62.
Figure 1: Electronics Housing Components
CAUTION
Temperature extremes can affect display quality. The display can go blank if the
temperature is below -20°C or above 70°C; however, this is only a temporary condition. The
display will again be readable when temperatures return to within operable limits.
The device shall be operated bya trained professional. It is the user/installer’s responsibility
to install the indicator in accordance with national and local code requirements. Conduit
entry plugs and adapters shall be suitable for the environment, shall be certified for the
hazardous location when required and acceptable to the authority having jurisdiction for the
plant
The RMA device is always connected in series with the transmitter. The current loop will
be broken if the RMA801 device is removed from the loop.
Installation and setup
Site evaluation
Evaluate the site selected for the Remote Indicator installation with respect to the
process system design specifications and Honeywell’s published performance
characteristics for your particular model. Some parameters that you may want to
include in your site evaluation can be found in the RMA801 user manual, 34-ST-25-
62
Installation precautions
Temperature extremes can affect display quality. The display can go blank if the
temperature is below -20°C or above +70°C; however, this is only a temporary
condition. The display will again be readable when temperatures return to within
operable limits.
Explosion-Proof Conduit Seal
WARNING
When installed as explosion proof in a Division 1 Hazardous Location, keep
covers tight while the Remote Indicator is energized. Disconnect power to the
Remote Indicator in the non-hazardous area prior to removing end caps for
service.
When installed as non-incendive equipment in a Division 2 hazardous location,
disconnect power to the Remote Indicator in the non-hazardous area, or
determine that the location is non-hazardous before disconnecting or
connecting the Remote Indicator wires.

Mounting Remote indicator
Summary Remote Indicator models can be attached to a two-inch (50.8 millimeter)
vertical or horizontal pipe using Honeywell’s optional pipe mounting bracket. Honeywell’s
optional wall mounting bracket is also shown in figures below.
Mounting Dimensions
Refer to Honeywell drawing number 51455045*for detailed electronic housing
dimensions. Refer to Honeywell drawing numbers 32306827*for detailed pipe mounting
dimensions, 50124813*for Detailed Pipe Angle mounting dimensions and 32306828*for
detailed wall mounting dimensions.
THE TRANSMITTER ENCLOSURE CAN BE ROTATED A TOTAL OF 90° FROM THE
STANDARD MOUNTING POSITION
* Honeywell drawings can be supplied on request.
Bracket Mounting
If you are using an optional bracket, start with Step 1.
1. Pipe Mount Option -Refer to Figure 2. Align the two mounting holes at the
bottom of the Remote Indicator with the two slots in the mounting bracket
and assemble the (2) M8 hex cap screws, (2) lock washers and (2) flat
washers provided.
2. Rotate the Remote Indicator assembly to the desired position and torque the
M8 hex cap screws to 27,0 Nm/20,0 Lb-ft maximum
3. Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and
install a “U” bolt around the pipe and through the holes in the bracket.
Secure the bracket with (2) M10 hex nuts, (2) flat washers and (2) lock
washers provided. Refer to Figure 4.
Figure 2: Typical Pipe Mounted Installations
Figure 3: Mounting Bracket Secured to a Remote indicator
Figure 4: Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe
4. Wall Mount Option –Refer Figure 5 Position the bracket on the mounting
surface at the desired location and secure the bracket to the mounting
surface using the appropriate hardware (Wall mounting hardware
requirements to be determined and supplied by the end user).
Figure 5: Remote Indicator Secured to a Wall Mounting Bracket
Wiring a Remote Indicator
Overview
The Remote Indicator is designed to operate in normal 4-20mA analog mode with HART
enabled transmitters across SmartLine Devices. In DE mode, only STT250 and STT700
Honeywell SmartLine transmitters.
For improved noise performance, it is recommended to provide earth ground for both
transmitter and RMA housing.
Figure 6: DE/ANALOG Terminal Block
Figure 7: RMA801 Terminal Block
Terminal Block
The RMA801 has 3 terminals. Following table provides the connection details-
Three screw terminals suitable for wirings up to (16AWG)
Shielded, twisted-pair cable such as Belden 9318 or equivalent must be used for
all signal/power wiring.
The cable shield must be connected at only one end of the cable. Connect it to
the power supply side and leave the shield insulated at the transmitter side
and RMA side.
Loop Terminals 5 & 6 shall be connected in series with the 4-20 ma loop for both analog
and DE modes. Additionally, third wire (Terminal 9) is required for DE communication in
DE mode only.
Loop wiring for analog and DE mode is shown in figure below.
NOTE:
After wiring the Transmitter as outline in the next sections, torque the screws to
1.1 Nm (10 lb-in)
Terminal No.
Description
5
Loop +ve
6
Loop -ve
9
DE COMM

Wiring Connections and Power Up
Make sure that the following power supply constraint is met.
1000/22*3.2 ,, loopMinTxerMinS RVVV
Where
ohmsinresistanceloopis
lsat terminatagesupply volMinimumrTransmitteis
tagesupply volminimumis
,
,
loop
MinTxer
MinS
R
V
V
Wiring Options
There are 3 wiring options for connecting Remote Indicator to the loop.
See Figure 9, Figure 9 and Figure 8 for the wiring connections.
DE Devices
In this mode, the Remote Indicator shall be connected as shown in Figure 8.
Figure 8: Remote Indicator connected to the negative loop wire
Once the wiring is complete, power on the loop. The RMA device will take 6s (approx.) to
turn on the display.
Note –The resistor “R” indicates (shown for representation only) the loop resistor which is
needed for HART and DE communication and is typically provided by the user or control
system.
Analog (4-20mA) Devices:
Refer Figure 8 and 9 for the Remote Indicator Connection on the Negative and positive
side of the loop.
Figure 9: Remote Indicator connected to the negative loop wire
1. Remote Indicator installed as explosion proof in Class I, Division 1, Group A
Hazardous (classified) locations in accordance with ANSI/NFPA 70, the US
National Electrical Code, with 1/2 inch conduit do not require an explosion-proof
seal for installation. If 3/4 inch conduit is used, a LISTED explosion proof seal must
be installed in the conduit, within 18 inches (457.2 mm) of the Remote Indicator.
Figure 10: Remote Indicator connected to the positive loop wire
ATTENTION
For all wiring options, ensure that RMA chassis ground terminal is
connected to earth ground.
Connect the Loop Power shield to earth ground at the power supply
end and not at RMA end. The shield shall be continuous from
transmitter through RMA till the power supply
:
DEVICE CONFIGURATION
Once the loop is powered, the RMA will be turned ON with a scrolling message “SmartLine”
appearing on the display.
For DE devices, the RMA is autoconfigured. For any DE configuration change in the
transmitter, database upload shall be performed to reflect the changes in RMA.
To configure the device, open the front cover of the device.
Use the ‘Menu’ and ‘Enter’ key buttons on display to configure the device. See table below
for configuration parameters.
Use the ‘Menu’ button to navigate the configuration parameters. Use the ‘Enter’ button to
select and set a parameter value.
1. Temperature: °C, °F, °R, K, mV, Ohm
Pressure Engineering Units: inH2O@39ºF, mH2O@4ºC, cmH2O@4ºC, Torr,
mmH2O@68ºF, ftH2O@68ºF, inH2O@68ºF, inH2O@60ºF, atm, Pa, kPa, MPa, gf/cm2,
kgf/cm2, psi, mbar, bar, inHg@0ºC, mmHg@0ºC, mmH2O@4ºC.
SNO
MENU
Parameters
Description
1
SEL PV
Select Process Variable (temperature,
pressure, loop out, % out)
2
UNIT
Select Engineering Unit
Units are visible as per PV selection
3
ENTLRV
Enter Lower Range Value
(Numeric Value)
4
ENTURV
Enter Upper Range Value
(Numeric Value)
5
CAL Lo
Input Calibration Low Point. See manual for
details of calibration
(Applicable in Analog Mode only)
6
CAL Hi
Input Calibration High Point. See manual for
details of calibration.
(Applicable in Analog Mode only)
7
B UNIT
Select Engineering Base Unit of Transmitter
Base Units visible as per PV selection
(Applicable in Analog Mode only)
8
CNTRST
Set LCD Contrast
9
RMA DG
RMA Diagnostic Messages. See manual for
details of diagnostic messages
10
FW VER
Firmware Version
EXIT
EXIT Menu
Appendix A. PRODUCT CERTIFICATIONS
A1 European Directive Information (CE Mark)

A2. Hazardous Locations Certifications
C
ATEX
Flame-proof and Dust:
II 2 G Ex db IIC
T6..T4 Gb
II 2 D Ex tb IIIC T 95oC Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to
85ºC
Intrinsically Safe:
II 1 G Ex ia IIC T4 Ga
Note 2
-50oC to 70oC
Non-Incendive
II 3 G Ex ec IIC T4
Gc
Note 1
-50oC to 85oC
Enclosure: Type IP66/ IP67
ALL
ALL
STANDARDS: EN 60079-0: 2012+A11: 2013;
EN 60079-1: 2014; EN 60079-11: 2012; EN 60079-31: 2014;
EN 60079-7: 2015;
D
IECEx
Flame-proof:
Ex db IIC T6..T4 Gb
Ex tb IIIC T 95oC Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to
85ºC
Intrinsically Safe:
Ex ia IIC T4 Ga
Note 2
-50oC to 70oC
Non-Incendive
Ex ec IIC T4 Gc
Note 1
-50oC to 70oC
Enclosure: IP66/ IP67
ALL
ALL
STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014;
IEC 60079-11: 2011; IEC 60079-7: 2015; IEC 60079-31: 2014

K
cCSAus
Explosion proof:
Class I, Division 1, Groups A, B, C,
D;T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups E,
F, G; T4
Class I Zone 1 Ex db IIC T4 Gb
Ex db IIC T4 Gb
Zone 21 Ex tb IIIC T 95oC Db
Ex tb IIIC T 95oC Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
Intrinsically Safe:
CSA 14.2689056
Class I, II, III, Division 1, Groups
A, B, C, D, E, F, G; T4
Ex ia IIC T4 Ga
Note 2
-50oC to 70oC
Non-Incendive
Class I, Division 2, Groups A, B, C,
D; T4
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Note 1
-50oC to 85oC
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
Standards: CSA C22.2 No. 0: 2015; CSA C22.2 No. 30: 2016; CSA C22.2
No. 94-M91; CSA C22.2 No. 25: 2017; CSA C22.2 No. 61010-1: 2017;
CSA-C22.2No.157: 2016; C22.2 No. 213: 2017; C22.2 No. CSA 60079-
0:2015; C22.2 No. 60079-1: 2016; C22.2 No. 60079-11: 2014; C22.2 No.
60079-15: 2016; C22.2 No. 60079-31: 2015;
ANSI/ ISA12.12.01-2017; ANSI/ ISA 61010-1: 2016; ANSI/ UL 60079-0:
2013; ANSI/ UL 60079-1: 2015; ANSI/ UL 60079-11: 2014; ANSI/ UL
60079-15: 2013; ANSI/ UL 60079-31: 2015 ; FM 3600: 2011; FM 3615:
2006; FM Class 3616: 2011; ANSI/ UL 913: 2015; UL 916: 2015; ANSI/
UL 12.27.01: 2017; ANSI/UL 50E: 2015
Notes
1. Operating Parameters:
Voltage= 12 to 42 V Current= 25 mA
2. Intrinsically Safe Entity Parameters
For details see Control Drawing, 50089981.
A4. Marking ATEX Directive
a. General
The following information is provided as part of the labeling of the Remote
Indicator:
•Name and Address of the manufacturer
•The serial number of the Remote Indicator is located on the Meter Body
data-plate. The first two digits of the serial number identify the year (02)
and the second two digits identify the week of the year (23); for example,
0223xxxxxxxx indicates that the product was manufactured in 2002, in
the 23rd week.
b. Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the
equipment. The user shall then check the box [ ] adjacent to the type of
protection used on the equipment certification nameplate. Once a type of
protection has been checked on the nameplate, the equipment shall not then be
reinstalled using any of the other certification types.
c. WARNINGS and Cautions
Non-Incendive / Non-Sparking (Division 2 and Zone 2 Environments):
WARNING –EXPLOSION HAZARD –SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
Intrinsically Safe (Divisions 1, Zone 1 and Zone 2 Environments):
WARNING –EXPLOSION HAZARD –SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
WARNING –DO NOT OPEN WHEN AN EXPLOSIVE GAS
ATMOSPHERE IS PRESENT.
Explosion-Proof (Division 1 and Zone 1 Environments):
WARNING –DO NOT OPEN WHEN AN EXPLOSIVE GAS
ATMOSPHERE IS PRESENT.
WARNING –DO NOT OPEN WHEN ENERGIZED
“OPEN CIRCUIT BEFORE REMOVING COVER”
Flameproof (Division 1 and Zone 1 Environments):
WARNING –DO NOT OPEN WHEN ENERGIZED
General Requirements / Increased Safety (Zone 1):
WARNING –DO NOT OPEN WHEN ENERGIZED
WARNING –OPEN CIRCUIT BEFORE REMOVING COVER
All Protective Measures:
WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60oC USE
WIRE RATED 105oC
A.3 Conditions of Use” for Ex Equipment”, Hazardous Location
Equipment or “Schedule of Limitations”:
a. Consult the manufacturer for dimensional information on the flameproof
joints for repair.
b. Painted surface of the RMA 800 series may store electrostatic charge and
become a source of ignition in applications with a low relative humidity less
than approximately30% relative humidity where the painted surface is
relatively free of surface contamination such as dirt, dust or oil. Cleaning of
the painted surface should only be done with a damp cloth.
c. The ambient temperature range, maximum process temperature and
applicable temperature class of the equipment is as follows:
RMA801: T4 for -50˚C < Ta < 85˚C
RMA803: T4 for -20˚C < Ta < 70˚C
d. The RMA800 series enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction. Care must be
considered during installation and use to prevent impact or friction to avoid
impact.
e. If a charge-generating mechanism is present, the exposed metallic part on
the enclosure is capable of storing a level of electrostatic charge that could
become incendive for IIC gases. Therefore, the user/installer shall
implement precautions to prevent the buildup of electrostatic charge, e.g.
earthing the metallic part. This is particularly important if the equipment is
installed in a zone 0 location.
f. On installation, the RMA800 series shall be provided with supply transient
protection external to the apparatus such that the voltage at the supply
terminals of the RMA800 series does not exceed 140% of the voltage rating
of the equipment.
A.4 Control Drawing

For more information
To learn more about SmartLine Devices, visit www.honeywellprocess.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road
Shanghai, China 20061
www.honeywellprocess.com
34-ST-25-63, Rev.2
March 2019
2019 Honeywell International Inc.
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest
Authorized Distributor, contact one of the offices below.
Australia Honeywell Limited, Phone: +(61) 7-3846 1255, FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36, Toll Free Fax: 1300-36-04-70
China –PRC –Shanghai, Honeywell China Inc. Phone: (86-21) 5257-4568,
Fax: (86-21) 6237-2826
Singapore, Honeywell Pte Ltd. Phone: +(65) 6580 3278. Fax: +(65) 6445-3033
South Korea, Honeywell Korea Co Ltd. Phone:+(822)799 6114. Fax:+(822) 792
9015
EMEA, Phone: + 80012026455 or +44 (0)1202645583. FAX: +44 (0) 1344 655554
Email: (Sales) sc-cp-apps-salespa62@honeywell.com
AMERICAS, Honeywell Process Solutions, Phone: 1-800-423-9883,
Knowledge Base search engine http://bit.ly/2N5Vldi
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials and
faulty workmanship. Contact your local sales office for warranty information.
If warranted goods are returned to Honeywell during the period of coverage, Honeywell
will repair or replace without charge those items it finds defective. The foregoing is
Buyer's sole remedy and is in lieu of all other warranties, expressed or implied,
including those of merchantability and fitness for a particular purpose.
Specifications may change without notice. The information we supply is believed to be
accurate and reliable as of this printing. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and the
Honeywell web site, it is up to the customer to determine the suitability of the product
in the application.
Other manuals for SmartLine RMA801
2
Table of contents
Other Honeywell Touch Panel manuals

Honeywell
Honeywell CENTRA LINE WEB-HMI Series User manual

Honeywell
Honeywell QXe Recorder User manual

Honeywell
Honeywell 012577 Instruction manual

Honeywell
Honeywell SmartLine RMA801 Instruction Manual

Honeywell
Honeywell ADEMCO 6271CV User manual

Honeywell
Honeywell Gent Vigilon A3 Mimic Instruction manual

Honeywell
Honeywell OmniAssure User manual

Honeywell
Honeywell S7999B Operation manual

Honeywell
Honeywell UDC 2300 User manual

Honeywell
Honeywell Tuxedo Touch Series Assembly instructions