Huawei FusionModule500 Technical specifications

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Issue
05
Date
2019-11-22
HUAWEI TECHNOLOGIES CO., LTD.

Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
i
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
https://e.huawei.com

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
About This Document
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
ii
About This Document
Purpose
This document describes the FusionModule500 Smart Mini Data Center (smart module for
short) in terms of the appearance, features, and specifications for you to understand the
product information.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
System engineers
Hardware installation engineers
Commissioning engineers
Data configuration engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
About This Document
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
iii
Symbol
Description
Supplements the important information in the main text.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.
Issue 05 (2019-11-22)
Updated the USB description.
Issue 04 (2019-03-10)
Updated the manual name and so on.
Issue 03 (2018-10-31)
The VCN500 is changed to the VCN540.
Updated rPDU configuration.
Issue 02 (2017-10-25)
Added the description of how to install a half-height rPDU vertically in the single-phase 220
V power system.
Issue 01 (2017-04-20)
This issue is the first official release.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Contents
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
iv
Contents
About This Document.................................................................................................................... ii
1 Overview.........................................................................................................................................1
1.1 Positioning....................................................................................................................................................................1
1.2 Features.........................................................................................................................................................................3
2 Typical Application Scenarios and Configurations...............................................................5
2.1 Typical Scenarios..........................................................................................................................................................5
2.2 Typical Configuration (Single-Phase 220 V Power System) ........................................................................................6
2.3 Typical Configuration (Dual-Live Wire 208 V Power System)..................................................................................13
3 System Architecture....................................................................................................................20
3.1 Structural System........................................................................................................................................................20
3.2 Power Supply and Distribution System ......................................................................................................................21
3.2.1 Single-Phase 220 V Power System..........................................................................................................................21
3.2.1.1 Overview ..............................................................................................................................................................21
3.2.1.2 3 kVA UPS............................................................................................................................................................23
3.2.1.3 6 kVA UPS............................................................................................................................................................24
3.2.1.4 10 kVAUPS..........................................................................................................................................................25
3.2.1.5 PDU5000 ..............................................................................................................................................................26
3.2.1.6 rPDU.....................................................................................................................................................................27
3.2.2 Dual–Live Wire 208 V Power System.....................................................................................................................28
3.2.2.1 Overview ..............................................................................................................................................................28
3.2.2.2 6 kVA UPS............................................................................................................................................................29
3.2.2.3 10 kVAUPS..........................................................................................................................................................30
3.2.2.4 PDU5000 ..............................................................................................................................................................31
3.2.2.5 rPDU.....................................................................................................................................................................32
3.2.2.6 Transformer...........................................................................................................................................................32
3.2.3 (Optional) Battery Pack ...........................................................................................................................................32
3.2.4 Battery Cabinet........................................................................................................................................................33
3.3 Cooling System...........................................................................................................................................................36
3.4 Management System...................................................................................................................................................36
3.4.1 Overview .................................................................................................................................................................36
3.4.2 ECC800e..................................................................................................................................................................37
3.4.3 (Optional) Independent Deployment AI/DI Unit .....................................................................................................40

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Contents
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
v
3.4.4 Smoke Detector .......................................................................................................................................................42
3.4.5 T/H Sensor...............................................................................................................................................................44
3.4.6 Door Status Switch ..................................................................................................................................................45
3.4.7 (Optional) Intelligent Battery Monitoring System...................................................................................................45
3.4.7.1 CIM.......................................................................................................................................................................46
3.4.7.2 BIM.......................................................................................................................................................................56
3.4.8 Water Sensor............................................................................................................................................................57
3.4.9 (Optional) Pad..........................................................................................................................................................58
3.4.10 (Optional) WiFi Converter.....................................................................................................................................59
3.4.11 (Optional) VCN540 ...............................................................................................................................................60
3.4.12 (Optional) IP Camera.............................................................................................................................................61
3.4.13 (Optional) GSM Modem........................................................................................................................................62
3.4.14 (Optional) Infrared Remote Control Module.........................................................................................................63
3.5 Cable Management.....................................................................................................................................................64
A Technical Specifications (Single-Phase 220 V Power System)..........................................67
B Technical Specifications (Dual–Live Wire 208 V Power System).....................................68
C Derating Coefficients ................................................................................................................69
D Acronyms and Abbreviations..................................................................................................70

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
1 Overview
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
1
1 Overview
1.1 Positioning
To meet the requirements for customers' growing services, Huawei launches the
FusionModule500 that can be rapidly deployed and flexibly expanded. The FusionModule500
is positioned as a smart module solution and occupies about 10 m2. It is mainly used in the
equipment rooms of county-level governments, bank business outlets, and small and
medium-sized enterprises.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
1 Overview
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
2
Figure 1-1 Position of the FusionModule500 in the financial industry
(1) FusionModule5000
(2) FusionModule2000
(3) FusionModule800
(4) FusionModule500

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
1 Overview
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
3
Figure 1-2 Position of the FusionModule500 for governments
(1) FusionModule5000
(2) FusionModule2000
(3) FusionModule800
(4) FusionModule500
1.2 Features
Integration
The smart module integrates the cabinets, power supply and distribution system, and
monitoring system to provide a comprehensive solution.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
1 Overview
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
4
Safety and Reliability
The Converged Cabinet incorporates the UPS, monitoring system, and power
distribution system that are designed in modular manner and feature high security and
reliability.
The powerful monitoring system allows you to master the infrastructure status anytime
and improves the protection capability of cabinets.
High Scalability
The modular design allows the smart module to be flexibly configured so that fast
capacity expansion can be achieved.
The smart module provides redundant power ports and communications ports for future
expansion.
Powerful Monitoring
Provides various sensors to monitor the functional modules.
Provides a pad to easily manage the functional modules locally.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
5
2 Typical Application Scenarios and
Configurations
2.1 Typical Scenarios
The smart module is mainly used in the equipment rooms of bank business outlets, small and
medium-sized enterprises, and governments.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
6
2.2 Typical Configuration (Single-Phase 220 V Power
System)
Single-Cabinet Solution
Figure 2-1 24 U Converged Cabinet
Table 2-1 Typical configuration 1
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 850 mm x 1200 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, battery pack
(optional)/external battery (optional),
PDU5000, and rPDU
Monitoring
ECC800e, temperature and humidity sensor
(T/H sensor), door status sensor, smoke
detector, water sensor, infrared remote
control module (optional), GSM modem
(optional), and LAN switch (optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
7
Figure 2-2 42 U Converged Cabinet
Table 2-2 Typical configuration 2
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, battery pack
(optional)/external battery (optional),
PDU5000, and rPDU
Monitoring
ECC800e, T/H sensor, camera (optional),
VCN (optional), door status sensor, smoke
detector, water sensor, pad (optional), WiFi
converter (optional), infrared remote control
module (optional), GSM modem (optional),
NetEco (optional), and LAN switch
(optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
8
Two-Cabinet Solution
Figure 2-3 Converged Cabinet + battery cabinet
Table 2-3 Typical configuration 3
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, PDU5000, rPDU, and battery
NOTE
If batteries are configured, battery packs are not required.
Monitoring
ECC800e, T/H sensor, camera (optional), VCN
(optional), door status sensor (Converged Cabinet),
door status sensor (battery cabinet, optional),
smoke detector, water sensor, pad (optional), WiFi
converter (optional), infrared remote control
module (optional), GSM modem (optional),
intelligent battery monitoring system (optional),
NetEco (optional), independent deployment AI/DI
unit (optional), and LAN switch (optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
9
Figure 2-4 Converged cabinet+ network cabinet
Table 2-4 Typical configuration 4
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
NOTE
Network cabinet dimensions (W x D x H):
600 mm x 1100 mm x 2000 mm or 800 mm x 1100 mm x
2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, PDU5000, rPDU, and battery pack
(optional)/external battery (optional)
Monitoring
ECC800e, T/H sensor (Converged Cabinet), T/H
sensor (network cabinet, optional), camera
(optional), VCN (optional), door status sensor
(Converged Cabinet), door status sensor (network
cabinet, optional), smoke detector, water sensor, pad
(optional), WiFi converter (optional), infrared
remote control module (optional), GSM modem
(optional), NetEco (optional), independent
deployment AI/DI unit (optional), and LAN switch
(optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
10
Three-Cabinet Solution
Figure 2-5 Network cabinet + converged cabinet + batterycabinet
Table 2-5 Typical configuration 5
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
NOTE
Network cabinet dimensions (W x D x H):
600 mm x 1100 mm x 2000 mm or 800 mm x 1100 mm x
2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, PDU5000, rPDU, and battery
NOTE
If batteries are configured, battery packs are not required.

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
11
Item
Specifications
Monitoring
ECC800e, T/H sensor (Converged Cabinet), T/H
sensor (network cabinet, optional), camera
(optional), VCN (optional), door status sensor
(Converged Cabinet), door status sensor (network
cabinet, optional), door status sensor (battery
cabinet, optional), smoke detector, water sensor, pad
(optional), WiFi converter (optional), infrared
remote control module (optional), GSM modem
(optional), intelligent battery monitoring system
(optional), NetEco (optional), independent
deployment AI/DI unit (optional), and LAN switch
(optional)
Four-Cabinet Solution
Figure 2-6 Network cabinet + Converged Cabinet + battery cabinet + battery cabinet

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
12
Table 2-6 Typical configuration 6
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
NOTE
Network cabinet dimensions (W x D x H):
600 mm x 1100 mm x 2000 mm or 800 mm x
1100 mm x 2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, PDU5000, rPDU, and battery
NOTE
If batteries are configured, battery packs are not
required.
Monitoring
ECC800e, T/H sensor (Converged Cabinet),
T/H sensor (network cabinet, optional),
camera (optional), VCN (optional), door
status sensor (Converged Cabinet), door
status sensor (network cabinet, optional),
door status sensor (battery cabinet,
optional), smoke detector, water sensor, pad
(optional), WiFi converter (optional),
infrared remote control module (optional),
GSM modem (optional), intelligent battery
monitoring system (optional), independent
deployment AI/DI unit (optional), NetEco
(optional), and LAN switch (optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
13
2.3 Typical Configuration (Dual-Live Wire 208 V Power
System)
Single-Cabinet Solution
Figure 2-7 42 U Converged Cabinet
Table 2-7 Typical configuration 1
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, battery pack (optional)/external battery
(optional), PDU5000, rPDU, and transformer
Monitoring
ECC800e, T/H sensor, camera (optional), VCN
(optional), door status sensor, smoke detector, water
sensor, pad (optional), WiFi converter (optional),
infrared remote control module (optional), GSM
modem (optional), NetEco (optional), and LAN
switch (optional)

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
2 Typical Application Scenarios and Configurations
Issue 05 (2019-11-22)
Copyright © Huawei Technologies Co., Ltd.
14
Two-Cabinet Solution
Figure 2-8 Converged Cabinet + battery cabinet
Table 2-8 Typical configuration 2
Item
Specifications
Cabinet dimensions (W x D x H)
600 mm x 1100 mm x 2000 mm
Power backup time
15–240 minutes
Power distribution
UPS2000-G, PDU5000, rPDU, battery, and
transformer
NOTE
If batteries are configured, battery packs are not
required.
Other manuals for FusionModule500
7
Table of contents
Other Huawei Data Logger manuals

Huawei
Huawei FusionModule 1000A20 User manual

Huawei
Huawei SmartLogger3000 User manual

Huawei
Huawei SmartLogger3000 User manual

Huawei
Huawei Atlas 500 Quick reference guide

Huawei
Huawei SmartLogger3000 User manual

Huawei
Huawei FusionModule 1000B Operating manual

Huawei
Huawei FusionModule1000A20 Operating manual

Huawei
Huawei SmartLogger3000 User manual

Huawei
Huawei FusionModule2000 V500R003C10 Operating manual

Huawei
Huawei SmartLogger1000 User manual