Huawei SmartLogger3000 User manual

SmartLogger3000
Export Limitation Conguration
Guide
Issue 04
Date 2022-10-24
HUAWEI TECHNOLOGIES CO., LTD.

Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specied in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every eort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: https://e.huawei.com
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. i

Preface
Purpose
This document applies to the SmartLogger3000 data collector series (SmartLogger
for short). Read this document before you use the SmartLogger. As a dedicated
platform for photovoltaic (PV) power system monitoring and management, the
SmartLogger implements the interface convergence, protocol conversion, data
collection, data storage, centralized monitoring, intelligent maintenance, and
remote networking functions for devices in a PV power system.
This manual describes the operation and maintenance instructions of the export
limitation function.
Intended Audience
This document is intended for :
● Technical support engineers.
● Maintenance engineers.
Symbol Conventions
The symbols that may be found in this document are dened as follows.
Symbol Description
Indicates a hazard with a high level of risk which,
if not avoided, will result in death or serious
injury.
Indicates a hazard with a medium level of risk
which, if not avoided, could result in death or
serious injury.
Indicates a hazard with a low level of risk which,
if not avoided, could result in minor or moderate
injury.
SmartLogger3000
Export Limitation Conguration Guide Preface
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. ii

Symbol Description
Indicates a potentially hazardous situation which,
if not avoided, could result in equipment damage,
data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Supplements the important information in the
main text.
NOTE is used to address information not related
to personal injury, equipment damage, and
environment deterioration.
Change History
Issue Date Description
04 2022-10-24 Change the default value of
communication disconnection detection
time to 3
03 2022-08-01 Added the empirical parameters of the
YDS60-80 meter.
02 2020-10-31 Update the description of "Start control"
paramter.
01 2020-07-29 This issue is the rst ocial release.
SmartLogger3000
Export Limitation Conguration Guide Preface
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. iii

Contents
Preface........................................................................................................................................... ii
1 System Network Diagrams....................................................................................................1
2 Connecting to the Inverter....................................................................................................3
3 Conguting Export Limitation Feature.............................................................................. 5
3.1 Wizard Conguration............................................................................................................................................................. 5
3.1.1 Step 1 Connecting to the Power Meter........................................................................................................................5
3.1.2 Step 2 Conguring Inverter Parameters...................................................................................................................... 6
3.1.3 Step 3 Conguring Export Limitation Parameters....................................................................................................8
3.2 General Conguration......................................................................................................................................................... 12
3.2.1 Step 1 Connecting to the Power Meter..................................................................................................................... 12
3.2.2 Step 2 Conguring Inverter Parameters.................................................................................................................... 13
3.2.3 Step 3 Conguring the Active Power Change Gradient....................................................................................... 14
3.2.4 Step 4 Conguring Export Limitation Parameters................................................................................................. 14
4 Circuit Breaker Control.........................................................................................................20
5 Q&A.......................................................................................................................................... 22
5.1 Why is there a failure to enable Export Limitation?.................................................................................................22
SmartLogger3000
Export Limitation Conguration Guide Contents
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. iv

1 System Network Diagrams
The Export Limitation feature is mainly used in the self-use scenario. The
SmartLogger detects the active power of the grid-tied point electric meter,
controls the active output of the inverter in a closed-loop manner, prevents the
inverter output power from being transmitted to the power grid, and maximizes
the inverter power generation for local load consumption.
Without the DO control circuit breaker
Figure 1-1
With the DO control circuit breaker
SmartLogger3000
Export Limitation Conguration Guide 1 System Network Diagrams
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 1

Figure 1-2
NO TICE
Pay attention to the power supply position of the SmartLogger. Avoid powering o
the SmartLogger after the DO control circuit breaker is switched o.
SmartLogger3000
Export Limitation Conguration Guide 1 System Network Diagrams
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 2

2 Connecting to the Inverter
Step 1 Log in as admin. Choose Maintenance > Connect Device to access the target
page, as shown in the following gure.
Step 2 Automatically search for inverters:
SmartLogger3000
Export Limitation Conguration Guide 2 Connecting to the Inverter
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 3

Step 3 Search result:
----End
SmartLogger3000
Export Limitation Conguration Guide 2 Connecting to the Inverter
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 4

3 Conguting Export Limitation Feature
3.1 Wizard Conguration
3.2 General Conguration
3.1 Wizard Conguration
3.1.1 Step 1 Connecting to the Power Meter
Log in as admin. Choose Settings > Power Adjustment > Export Limitation to
access the target page.Manually add a power meter after correctly setting
parameters. Then click the Next button.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 5

NO TE
● If the connected power meter model is UMG604, PD510, PZ96L, UPM209, or COUNTIS
E43, select the corresponding model in the Intelligent Power Meter Type drop-down
list box.
● When the UPM209 or COUNTIS E43 power meter is connected to the SmartLogger, a
120-ohm resistor needs to be connected to the RS485 bus of the meter. For details, see
the user manual of the power meter.
● COUNTIS E43:Not applicable to Load Imbalance.
● The meter which used for Export Limitation, set the "Meter usage" to "Export +
import meter". Each array allows only one export+import meter to be connected.
3.1.2 Step 2 Conguring Inverter Parameters
If Figure 3-2 does not have Communication disconnection fail-safe and
Communication disconnection detection time and Fail-safe power
threshold.Please refer to Figure 3-3.After the inverter parameters are correctly
congured,then click the Next button.
Figure 3-1
The following table lists the recommended parameter settings.
Table 3-1
Parameter Recommended Value Description
Active power change
gradient
125%/s,If the maximum
value range is 50%/s, set
this parameter to 50%/s.
Soft start time 20
Soft start time after grid
failure
20
Communication
disconnection fail-safe
Enable
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 6

Parameter Recommended Value Description
Communication
disconnection detection
time
3 Under the Spanish
RD1699 grid standard, it
is recommended to set it
to 1S.
Fail-safe power threshold 0
Plant active power
gradient
0
Figure 3-2
Table 3-2
Parameter Recommended Value
Active power change gradient 125%/s,If the maximum value range is
50%/s, set this parameter to 50%/s.
Soft start time 20
Soft start time after grid failure 20
Communication interrupt shutdown Enable
Communication resumed startup Enable
Communication interruption duration 1
Plant active power gradient 0
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 7

3.1.3 Step 3 Conguring Export Limitation Parameters
If the DO switch-on/o operations are not involved, ignore the switch-on/o
congurations.
Figure 3-3
●Parameter Conguration
Parameter Value Range Default Value Description
Start control Yes/No No Enable/Disable
Export Limitation
feature. Set this
parameter to Yes.
Otherwise, the
export limitation
feature does not
take eect.
Electric meter
power direction
Positive/Reverse Reverse Set this
parameter to
Positive if the
active power
reading of the
power meter is
positive when
the inverter has
no power output.
Otherwise, set
this parameter to
Reverse.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 8

Parameter Value Range Default Value Description
Limitation mode Total power/
Single-phase
power
Total power Total power:
Backow
prevention for
the total power
of the grid-tied
point.
Single-phase
power: Backow
prevention for
each phase of
the grid-tied
point.
(COUNTIS
E43:Not
applicable to
Load Imbalance.)
Maximum grid
feed-in power
(0.000,
1000.000)kW
0.000kW Maximum output
power of the
inverter to the
power grid
Suggestion: Set
this parameter
according to the
threshold
allowed by the
local power
company.
Power lowering
adjustment
period
(0.2,300.0)s 0.5s Inverter output
power lowering
period. Refer to
Empirical
Parameters.
(If it is consistent
with Maximum
protection time,
the power can be
lowered for
100% in a single
step.)
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 9

Parameter Value Range Default Value Description
Maximum
protection time
(3.0,300.0)s 3.0s The maximum
duration of the
inverter output
power to the
power grid
exceeding the
preset threshold
detected by the
SmartLogger. If
Switch-o with
0% power limit
is enabled, DO
switch-o is
triggered. This
parameter is
used with Power
lowering
adjustment
period. Refer to
Empirical
Parameters.
Suggestion: Set
this parameter
according to the
maximum
duration allowed
by the local
power company.
Power raising
threshold
(0.001,
50.000)kW
5.000kW Inverter output
power raising
threshold.The
recommended
setting is
1%~2%Pn.
Fail-safe power
threshold
(0.0, 100.0)% 100.0% Inverter output
power
percentage
controlled by the
SmartLogger
when
communication
between the
SmartLogger and
the power meter
is abnormal.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 10

Parameter Value Range Default Value Description
Switch-o with
0% power limit
Enable/Disable Disable Enables or
disables DO
switch-o. The
default value is
Disable. When
enabled and the
power is limited
to 0%, the DO
performs the
corresponding
action (the hold
time is 5
seconds) if the
current reverse
ow does not
disappear after 5
seconds.
Switch-o
control port
No/DO1/DO2/D
O3
No Set the Switch-
o control port
based on actual
cable connection.
Switch-on
control port
No/DO1/DO2/D
O3
No Set the Switch-
on control port
based on actual
cable connection.
Switch-o state
feedback port
No/DI1/DI2/DI3/
DI4
No Set the Switch-
o state
feedback port
based on actual
cable connection.
Switch-on state
feedback port
No/DI1/DI2/DI3/
DI4
No Set the Switch-
on state
feedback port
based on actual
cable connection.
●Empirical Parameters
Meter
Model
Power
Lowering
Adjustment
Period
Maximum
Protection Time
Description
UMG 0.5s 3s
COUNTIS
E43
0.5s 3s
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 11

Meter
Model
Power
Lowering
Adjustment
Period
Maximum
Protection Time
Description
UMP209 0.5s 3s
CHNT
DTSU666-H
0.5s 3s Under the Spanish
RD1699 grid standard,
please set Power
Lowering Adjustment
Period 0.8s, Maximum
Protection Time 2s
YDS60-80 0.8s 2s The maximum
protection time must
be adjusted based on
local policies.
The preceding parameters are tested in a lab environment and can be
preferentially used for conguration and commissioning onsite. They may need to
be adjusted based on the actual situation.
3.2 General Conguration
3.2.1 Step 1 Connecting to the Power Meter
Log in as admin. Choose Deployment Wizard > Power Meter to access the
target page.Manually add a power meter after correctly setting parameters.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 12

NO TE
● If the connected power meter model is UMG604, PD510, PZ96L, UPM209, or COUNTIS
E43, select the corresponding model in the Intelligent Power Meter Type drop-down
list box.
● When the UPM209 or COUNTIS E43 power meter is connected to the SmartLogger, a
120-ohm resistor needs to be connected to the RS485 bus of the meter. For details, see
the user manual of the power meter.
● COUNTIS E43:Not applicable to Load Imbalance.
● The meter which used for Export Limitation, set the "Meter usage" to "Export +
import meter". Each array allows only one export+import meter to be connected.
3.2.2 Step 2 Conguring Inverter Parameters
Log in as admin. Choose Monitoring > SUN2000 > Running Param. > Feature
Parameters to access the target page.
Figure 3-4
The following table lists the recommended parameter settings. For multiple
inverters, use Batch congurations.
Table 3-3
Parameter Recommended Value
Communication interrupt shutdown Enable
Communication resumed startup Enable
Communication interruption duration 1
Soft start time 20
Soft start time after grid failure 20
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 13

3.2.3 Step 3 Conguring the Active Power Change Gradient
Log in as admin. Choose Monitoring > SUN2000 > Running Param. > Power
Adjustment to access the target page.
Figure 3-5
The following table lists the recommended parameter settings. For multiple
inverters, use Batch congurations.
Table 3-4
Parameter Recommended Value
Plant active power gradient 0
Active power change gradient 125%/s,If the maximum value range is
50%/s, set this parameter to 50%/s.
3.2.4 Step 4 Conguring Export Limitation Parameters
Log in as admin. Choose Settings > Power Adjustment > Active Power Control
to access the setting page. If the DO switch-on/o operations are not involved,
ignore the switch-on/o congurations.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 14

Figure 3-6
●Parameter Conguration
Parameter Value Range Default Value Description
Start control Yes/No No Enable/Disable
Export Limitation
feature. Set this
parameter to Yes.
Otherwise, the
export limitation
feature does not
take eect.
Electric meter
power direction
Positive/Reverse Reverse Set this parameter
to Positive if the
active power
reading of the
power meter is
positive when the
inverter has no
power output.
Otherwise, set this
parameter to
Reverse.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 15
Other manuals for SmartLogger3000
3
Table of contents
Other Huawei Data Logger manuals

Huawei
Huawei Atlas 500 Quick reference guide

Huawei
Huawei SmartLogger3000 User manual

Huawei
Huawei SmartLogger1000 User manual

Huawei
Huawei SmartLogger2000 series User manual

Huawei
Huawei FusionDC1000A User manual

Huawei
Huawei FusionDC1000A User manual

Huawei
Huawei SmartLogger2000-10-B-JP User manual

Huawei
Huawei FusionModule2000 V500R003C10 Operating manual

Huawei
Huawei FusionModule1000A20 Operating manual

Huawei
Huawei FusionModule500 Technical specifications