● Make sure all wires and instrument testing port connection is firm.
Note (for improper operation may cause personal injury or equipment damage)
Squared before measurement, confirm the voltage selection in the appropriate value.
If long time not to use, the battery should be fully charge, and recharge in 3 months.
Squared do not in high temperature, damp, places and condensation may be placed
under direct sunlight for a long time.
Please use a damp cloth or cleaner to clean the equipment enclosure, do not use
abrasives or solvents.
Instrument wet, please dry storage first.
II.Feature
High-voltage insulation resistance tester, with 5 range: 500V, 1000V, 2500V, 5000V,
10000V, test up to 20TΩ,there is also a manual boost function.
● design in strict accordance with safety standards
● insulation resistance range: 20t Ω @ 10KV
● the short-circuit current can be adjusted up to 3mA.
● automatically display the test values of polarization index (PI), absorption ratio (DAR),
leakage current and capacitance, dielectric discharge test (DD) and step voltage test
(SV).
● excellent anti-interference performance. When the interference current reaches 2mA,
the instrument still ensures the test accuracy.
● AC and DC voltage test function of the tested line to automatically identify AC or DC.
● the capacitive test object discharges rapidly. During cable test, there is no need for
manual discharge, and the instrument discharges rapidly automatically.
● two power supply modes: Powered by lithium battery, the endurance time can reach 6
hours.
At the same time, it can be charged in use. In case of power failure, it can automatically
convert from AC power supply to battery power supply.
● the operation is simple and clear, and the insulation resistance analog column can be
displayed.