Package contents
A complete shipment contains the following items:
Poseidon2 3468
Printed manual + datasheet
Safety information
The device complies with regulations and industrial standards in force in the Czech Republic and the
European Union. The device has been tested and is supplied in working order. To keep the device in
this condition, it is necessary to adhere to the following safety and maintenance instructions.
Never remove the device cover if the relay terminals are connected to the electrical network!
Using the device in a manner other than prescribed by the manufacturer may cause its
safeguards to fail!
The power supply outlet or disconnection point must be freely accessible.
The device must not be used in particular under any of the following conditions:
The device is noticeably damaged
The device does not function properly
Unfastened parts can move inside the device
The device has been exposed to moisture or rain
The device has been serviced by unauthorized personnel
The power adapter or power supply cable are noticeably damaged
If the device is used in a manner other than designed for, the protection provided by the device
may fail.
The local electrical system must include a power switch or a circuit breaker and overcurrent
protection.
The manufacturer warrants the device only if it is powered by the supplied power adapter or an
approved power supply.
If you have any problems with installing or operating the device, please contact technical support:
HW group s.r.o.
http://www.hw-group.com
Email: support@HWg.cz
U Pily 3
143 00 Praha 4
Czech Republic
Tel. +420 222 511 918
When contacting technical support, please keep at hand the exact type of your device (at the type
plate) and, if possible, the firmware version (see later in this manual).

Poseidon2 3468 –Manual
HW group
www.HW-group.com
4

Poseidon2 3468 –Manual
HW group
www.HW-group.com
5
First steps
1) Connecting the cables
Turn the unit upside down and write down its MAC address
that is printed on the label.
Set the switches: DIP1=Off, DIP2=Off.
Connect the unit to the Ethernet (with a patch cable to a
switch, cross-over cable to a PC), RJ-45 port.
Plug the power adapter into a mains outlet and connect it to
the Poseidon2 power jack.
The green POWER LED lights up.
If the Ethernet connection works properly, the LINK LED lights up after a short while, and then
flashes whenever data are transferred (activity indication).
2) Configuring the IP address –UDP Config
UDP Config utility –root directory of the supplied CD (Windows and Linux versions).
Available for download at www.HW-group.com Software > UDP Config.
Click the icon to launch UDP Config. The program automatically looks for connected devices.
Automatic device discovery works only in the local network.
Individual Poseidon2 units are identified by their MAC addresses (on the label at the bottom).
Double-click a MAC address to open a basic device configuration dialog.
Poseidon2 3468
Double click for
details

Poseidon2 3468 –Manual
HW group
www.HW-group.com
6
First steps
Configure the network parameters
IP address / HTTP port (80 by default)
Network mask
Gateway IP address for your network
Device name (optional)
Click the Apply Changes button to save the
settings.
Alternatively, you may use the following utilities to configure the IP address:
UDP Config for Linux
Important:
To reset the device to factory defaults, toggle DIP1 several times within 5 seconds after
applying power to the device.
No configuration changes can be stored while DIP2=On.
To change the IP address, set DIP2=Off.

Poseidon2 3468 –Manual
HW group
www.HW-group.com
7
First steps
4) WWW interface of the device
To open the WWW interface of the device:
oEnter the IP address into a web browser
oClick the IP address in UDP Config
oClick the underlined IP address in the
UDP SETUP utility
The WWW page displays current states of devices and sensors.
Web interface of the device
General:Overview of current readings
General Setup: IP address, DNS, security (username/password)
SNMP: SNMP / SNMP Trap configuration (ports and alarm recipients)
E-mail: Configuration and test
GSM & RFID:Configuration and test in order to use a remote SMS-GW
Log & Time: Time configuration, NTP server
Sensors: Device name, sensor names, status overview
Inputs: Control of inputs and alert parameters
Outputs: Control and mode configuration of outputs
System: Firmware upgrade, save/restore configuration, etc.
User-defined names for
sensors and digital
inputs
Action when value
out of range
Alarm thresholds

Poseidon2 3468 –Manual
HW group
www.HW-group.com
8
E-mail
Periodic Status Settings
Periodical Status
When on, sends an e-mail with device status at the specified intervals. For example
every 24 hours (1440 minutes).
Alarm reminder
When active, sends periodic reminders
that the device is in the Alarm state. For
example every 15 minutes.
NOTE: Configuration changesmust be confirmed by clicking the Apply Changes button.
Sends a test e-mail and
shows the connection log
1) Correct Gateway IP address
2) DNS server in network settings
3) SMTP server and port
4) Authentication turned on, correct
username and password
5) Spam filter for your mailbox is
disabled
To send e-mail, check:
Inserts the specified text
at the beginning of the
e-mail subject line

Poseidon2 3468 –Manual
HW group
www.HW-group.com
9
GSM
Log & Time
IP address of „HWg-SMS-GW“
to use for sending
text messages (SMS)
Press to synchronize the
time with the specified
server
Recipients' phone no’s

Poseidon2 3468 –Manual
HW group
www.HW-group.com
10
Sensors
After connecting sensors or changing RJ11 connections, sensors need to be detected again.
NOTE: Configuration changes must be confirmed by clicking the Apply Changes button.
Sensor name will be shown
in e-mails, text messages,
and SNMP traps
Sends a SNMP trap if the “Safe
Range” for this sensor is exceeded
Scans connected sensors and
displays detected sensors
Sends an E-mail if the “Safe
Range” for this sensor is
exceeded
To avoid numerousfalse alerts
(by e-mail or SMS) whenever the reading
fluctuates around the threshold,
you can use:
1) Hysteresis Idle Range
Tolerance band around the
“Safe Range”. Prevents
multiple alarm alerts.
2) Delay [s]
Delays the information about
alarm beginning and alarm
end by a specified time. Can be used for dry contacts, too.
Tip: For details, see the complete “Poseidon family” manual.
Sends a text message (SMS) if
the “Safe Range” for this sensor is
exceeded

Poseidon2 3468 –Manual
HW group
www.HW-group.com
11
Poseidon2 informs about alarm
activation and alarm deactivation
for each contact and/or sensor.
E-mail format cannot be changed;
sensors may have custom names.
Yellow background in a line with a
sensor or an input means that the
safe range is exceeded but alarm
notification is off.
FAQ
Connecting the inputs
Inputs
NOTE: Configuration changes must be confirmed by clicking the Apply Changes button.
•Poseidon family manual
For a detailed description of all settings and tabs, see the “Poseidon family”
manual.Available on the web or the installation CD.
TIP
Enter sensor name –will be
shown in e-mails, text
messages or SNMP traps
0 (Off)
1 (On)
ALARM CONTACT STATUS:
Active if On
Alarm when the contact
closes (1 = On)
Active if Off
Alarm when the contact
opens (0 = Off)
Disabled
No Alarm
Reaction to digital inputs:
Disabled
Send a SNMP Trap
Send an E-mail
Send a SMS

Poseidon2 3468 –Manual
HW group
www.HW-group.com
12
Outputs
Output mode:
A) Manual
Output can be controlled using the Web interface or externally using M2M protocols.
The output cannot be used in “thermostat” mode –local condition.
B) Local Condition
The output cannot be controlled using the Web interface, it is controlled by the local
condition. The output is read-only for all M2M protocols. Hysteresis configured in the sensor
settings applies.
The output cannot be controlled remotely.
oOn if any alarm
The output is active if at least one input or sensor is in alarm.
oOn if value equal to Trigger
The output is active if the selected sensor reading is equal to the “Target Value”.
oOn if value higher than Trigger
The output is active if the selected sensor reading is greater than the “Target Value”.
oOn if value lower than Trigger
The output is active if the selected sensor reading is less than the “Target Value”.
oDependent On –sensor / input to which the condition applies.
Choose the output mode
Manual mode:
Output controlled over the WEB
or M2M protocols
Local Condition mode:
Controls the output according to
the specified sensor

Poseidon2 3468 –Manual
HW group
www.HW-group.com
13
Software Applications
HWg-PDMS
Windows application that logs
data from all HW group devices
into its internal database.
The application runs in the
background (NTservice). Data are
received from the device over http
or e-mail.
Data can be exported over XML
or automatically stored to MS
Excel.
License: Free HWg-PDMS version for 3 sensors
Paid versions for 8 / 20 / 200 / unlimited sensors
HWg-Trigger
Windows application for detecting and reacting
to events.
Detects, for instance, disconnected devices,
failed sensors, values out of range, or
incoming SNMP Trap alerts.
Possible responses include sending an
e-mail, activating a relay over the
network, or sending a text message
(SMS) using HWg-SMS-GW.
Other responses include displaying a
warning message in Windows,
starting an application, or
shutting down the computer.
License: 30-day trial version free of charge

Poseidon2 3468 –Manual
HW group
www.HW-group.com
14
PosDamIO
Poseidon Damocles I/O is a command-line utility for Windows and Linux that lets
you control Poseidon and Damocles units over the XML interface. It can display the
states of sensors, inputs and outputs, as well as set an output high or low.
SensDesk.com
Online portal for collecting data from LAN and GSM sensors.
Poseidon2 can connect to the SensDesk internet service. All devices can be managed from a single
WWW interface. Watch sensor states, display your devices in a map, compare trends in time and
analyze alarm messages.
SensDesk is a way to implement fully functional monitoring of customer technology in a matter of
minutes, with fixed costs of the system. No need for installing a complex system or adding another
server at the customer side.
Overview of all sensors at a single place
Centralized alarm configuration for individual sensors
Mobile application for monitoring
Remote configuration of GSM devices. www.SensDesk.com

Poseidon2 3468 –Manual
HW group
www.HW-group.com
15
Mechanical dimensions
Power output
Poseidon2 3468 features the PWR OUT terminals for
powering connected sensors and detectors.
Powered by 9–30V: PWR OUT = 9–30V
Powered by 48V: PWR OUT = 12V

Poseidon2 3468 –Manual
HW group
www.HW-group.com
16
Specifications
ETHERNET
Interface
RJ45 (100BASE-Tx) –10/100 Mbps network compatible
Supported protocols
IP: ARP, TCP/IP (HTTP, NTP, SMTP, netGSM, HWg-PUSH), UDP/IP (SNMP)
SNMP compatibility
Ver.1.00 compatible, partial ver.2.0 implementation
Logger
Internal memory
250,000 records in flash memory
Logged items
Sensors, DI, DO
SENSORS
Type
HWg original accessories: 1-Wire & 1-Wire UNI
Connector
2xRJ11 (1-Wire UNI)
Sensors
Up to 8 sensors in total (temperature + humidity combo sensors count as 2 sensors)
Sensor distance
Up to 60m
DI –DRY CONTACT INPUTS
Port
I1, I2, I3, I4
Type
Digital Input (supports NO/NC Dry contact)
Sensitivity
1 (On) = 0–500 Ω
Max. distance
Up to 50m
OUTPUTS
Port / type
OUT1, OUT2 / Relay contacts (NC-COM-NO)
Max. load
max. 24V / 16A DC; max. 250V / 16A AC
State
Power up state (no state restart memory)
POWER input
Type
You can power the device from power input 1 or 2.
Power input 1
POWER 9-30V DC –2,5W
Jack 9–30V DC (barrel, inner 2.5 mm outer 6.3 mm) + Terminal Block
Power input 2
Terminal Block 48V DC
POWER output
Voltage
Power input 1 (9-30V): Power Out = Power IN (9-30V)
Power input 2 (48V): Power Out = 12V
Current / Connector
Max. 150mA / Terminal Block
LED status indicators
POWER (RJ45 + top)
Green –power OK (top), Ethernet enabled (RJ45)
LINK & Activity (RJ45)
Yellow - Ethernet connectivity
Setup / Alarm
Red
Inputs
Green
Outputs
Yellow
DIP SWITCH
DIP1: Setup
OFF = Normal state
Load defaults: Set ON, power-up device, toggle 3 times during first 5 seconds
DIP2: Security
ON = Secure mode (online demo) –remote configuration disabled
OFF = Non-secure mode –remote configuration enabled
Physical parameters
Temperature range
Operating: -30 to +75 °C (-22 to 167 °F) / Storage: -35 to +85 °C (-31 to +185 °F)
Dimensions / Mass
145 x 90 x 45 [mm] / 225 g
EMC
FCC Part 15, Class B, CE - EN 55022, EN 55024, EN 61000

Poseidon2 3468 –Manual
HW group
www.HW-group.com
17
NO
+
-
COM
POWER OUT
12V
Relay outputs
NO and NC labels apply to Off (0) state, or device turned off
When the output is On (1), a “Normally Open” (NO) relay contact is closed
LEDs: Contact state (closed / open) is indicated by a LED
Isolation: The double-throw contact is electrically isolated from the rest of the device
ID range: Outputs use ID addresses from 151 to 180
Digital (dry contact) inputs
Digital input terminals may be connected to voltage-free contacts or the GND pin. The inputs are
electrically connected to the 12V power supply. Never connect the inputs to the 48V supply voltage!
Unconnected inputs read as “0 (Off)”
Active inputs read as “1 (On)”
Supported sensors: Any contact without external voltage (dry contact)
Polling period: 800 ms
Range of sensor IDs: Inputs use IDs from 1 to 24
NO NC

Poseidon2 3468 –Manual
HW group
www.HW-group.com
18
M2M interface
The product is ready to be connected with third-party SW applications.
For a description of the interfaces (XML format, detailed SNMP description, mapping of Modbus/TCP
variables), see the detailed “Poseidon family” manual.
XML (over HTTP)
SNMP , SNMP traps
Modbus/TCP
SMTP (E-mail)
SDK (Software Development Kit)
Programmers can take advantage of the HWg SDK (Software Development Kit) with an ActiveX
interface and ready-made examples.
VB - Visual Basic (6.0) - (3xx examples)
Borland C++ (1xx examples)
Microsoft Visual C++ (2xx examples)
C# / .NET (5xx examples)
Borland Delphi (4xx examples)
JAVA
PHP / ASP
other examples that do not directly use
SDK functions (all 9xx examples)
Note: The latest version of HWg-SDK is available for download at the HWg website.
You just need to register your e-mail.
•For a detailed description of the M2M communication interface and more
details, see the detailed Poseidon family manual.
TIP

Poseidon2 3468 –Manual
HW group
www.HW-group.com
19
Updating the firmware over the WEB
Upload the .hwg firmware file over http to http://x.x.x.x/upload/.
Connection problems etc. must be avoided during file transfer. If the update fails, upload the firmware
over RS-232.
Firmware in the .HWg format is available at our website, or on the supplied CD.
Restoring factory defaults
To restore the factory default configuration (including deleting all passwords):
1) Turn the device off by disconnecting power.
2) Set DIP1 to ON.
3) Turn the device on.
4) Toggle DIP1 several times during the first 5 seconds after powering up.
•For a detailed product description, see the detailed Poseidon family manual.
TIP
Table of contents
Other HW Group Measuring Instrument manuals

HW Group
HW Group HWg-STE User manual

HW Group
HW Group IP WatchDog2 Lite User manual

HW Group
HW Group STE 2 User manual

HW Group
HW Group Poseidon 3265 How to use

HW Group
HW Group Poseidon 1250 Tset Specification sheet

HW Group
HW Group Poseidon 3268 How to use

HW Group
HW Group Ares LTE Series User manual

HW Group
HW Group Poseidon2 3266 User manual

HW Group
HW Group NB Series User manual

HW Group
HW Group Poseidon 2250 How to use