ALU SGN LED
Centrally supplied emergency exit sign luminaire
1/6IMM - ALU SGN LED - CB_CBAM_LVAM - EN V05
IP40
INSTALLATION AND MAINTENANCE MANUAL
MOUNTING TYPE
C2 –directly to the ceiling (for suspended mounting -
separate accessory C202)
W1 – back to the wall
W2 – side to the wall (semaphore)
SYSTEM VARIANT
CB –luminaire supplied from HVCBS (230V AC / 108VDC
/ 216V DC), without address module
CBAM –
luminaire supplied from the HVCBS (230V AC/216V
DC), with built-in address module and operating
mode selection
LVAM –
luminaire supplied with 24V DC from the LVDBS
system, with built-in address module and
operating mode selection
LIGHTING TYPE
NM – NON-MAINTAINED – luminaire operates in emergency mode after power supply failure
M– MAINTAINED – lighting provided all the time, in case of power supply failure switches automatically into emergency mode
SIZE OF EXIT SIGN
30x15 – ISO 7010 compliant exit sign with the dimensions of 30x15 cm and a viewing distance of 30 meters
40x20 – ISO 7010 compliant exit sign with the dimensions of 40x20 cm and a viewing distance of 40 meters
60x30 – ISO 7010 compliant exit sign with the dimensions of 60x30 cm and a viewing distance of 60 meters
TECHNICAL DATA
Supply voltage
CB 230V AC 50/60Hz, 80-275V DC
CBAM 230V AC 50/60Hz, 170-275V DC
LVAM 10-32V DC
Current
consumption
30x15, 40x20 60x30
@216V DC
CB 24mA 26mA
CBAM 28mA 30mA
@24V DC LVAM 115mA 160mA
Power factor 0.4
Protection class
CB/CBAM I
LVAM III
Ingress protection IP40
Light source type LED strips 1)
Light source temperature 5000K
Colour rendering index 70
Light source supply power
30x15 2)
2W
40x20
60x30 3W
Light source lifespan > 50 000h
Supply cable cross-section area 0.5 – 2.5mm2
Ambient temperature
CB/CBAM -10 – +550C
LVAM -25 – +600C
Suitable for through wiring YES
¹)Non-exchangeable but serviceable light source; 2) Sign dimensions
SAFETY
• During the installation and usage of emergency luminaires, follow the national safety rules as well as generally accepted technical rules.
• During usage of emergency luminaires keep a register of inspection reports.
• Luminaire installation or maintenance has to be preceded by turning o the power supply.
• Ensure that all foreign bodies are removed before the luminaire power is switched on.
• The luminaire is to be used undamaged and in accordance with specications.
• The luminaire designed for use inside the building.
The above-mentioned luminaire is a re protection equipment andtherefore falls within relevant standards and regulations.