HYBRYD ALU SGN LED Manual

ALU SGN LED
Centrally supplied emergency exit sign luminaire
1/6IMM - ALU SGN LED - CB_CBAM_LVAM - EN V05
IP40
INSTALLATION AND MAINTENANCE MANUAL
MOUNTING TYPE
C2 –directly to the ceiling (for suspended mounting -
separate accessory C202)
W1 – back to the wall
W2 – side to the wall (semaphore)
SYSTEM VARIANT
CB –luminaire supplied from HVCBS (230V AC / 108VDC
/ 216V DC), without address module
CBAM –
luminaire supplied from the HVCBS (230V AC/216V
DC), with built-in address module and operating
mode selection
LVAM –
luminaire supplied with 24V DC from the LVDBS
system, with built-in address module and
operating mode selection
LIGHTING TYPE
NM – NON-MAINTAINED – luminaire operates in emergency mode after power supply failure
M– MAINTAINED – lighting provided all the time, in case of power supply failure switches automatically into emergency mode
SIZE OF EXIT SIGN
30x15 – ISO 7010 compliant exit sign with the dimensions of 30x15 cm and a viewing distance of 30 meters
40x20 – ISO 7010 compliant exit sign with the dimensions of 40x20 cm and a viewing distance of 40 meters
60x30 – ISO 7010 compliant exit sign with the dimensions of 60x30 cm and a viewing distance of 60 meters
TECHNICAL DATA
Supply voltage
CB 230V AC 50/60Hz, 80-275V DC
CBAM 230V AC 50/60Hz, 170-275V DC
LVAM 10-32V DC
Current
consumption
30x15, 40x20 60x30
@216V DC
CB 24mA 26mA
CBAM 28mA 30mA
@24V DC LVAM 115mA 160mA
Power factor 0.4
Protection class
CB/CBAM I
LVAM III
Ingress protection IP40
Light source type LED strips 1)
Light source temperature 5000K
Colour rendering index 70
Light source supply power
30x15 2)
2W
40x20
60x30 3W
Light source lifespan > 50 000h
Supply cable cross-section area 0.5 – 2.5mm2
Ambient temperature
CB/CBAM -10 – +550C
LVAM -25 – +600C
Suitable for through wiring YES
¹)Non-exchangeable but serviceable light source; 2) Sign dimensions
SAFETY
• During the installation and usage of emergency luminaires, follow the national safety rules as well as generally accepted technical rules.
• During usage of emergency luminaires keep a register of inspection reports.
• Luminaire installation or maintenance has to be preceded by turning o the power supply.
• Ensure that all foreign bodies are removed before the luminaire power is switched on.
• The luminaire is to be used undamaged and in accordance with specications.
• The luminaire designed for use inside the building.
The above-mentioned luminaire is a re protection equipment andtherefore falls within relevant standards and regulations.
EN

2/6 www.hybryd.eu
NOT OBEYING THE SAFETY INSTRUCTIONS AND RECOMMENDATIONS CAN CAUSE LIFE THREAT OR EVEN DEATH
NOT OBEYING THIS INSTRUCTION MANUAL CAN RESULT IN LUMINAIRE DAMAGE AND LOSS OF WARRANTY
LUMINAIRE CONSTRUCTION
30x15 / 40x20
CB/CBAM
LED strips
Power supply connector
Adress and operating
mode switch (only CBAM)
Emergency
module
40×20/30×15
LVAM
LED strips
Power supply connector
Adress and operating
mode switch (only LVAM)
Emergency
module
60x30
60×30
CB/CBAM
LED strips
Cable tie holder
Power supply
connector
Emergency
module
Cable gland
LVAM
LUMINAIRE AND SIGN DIMENSIONS (in mm)
30x15 40x20 60x30
Wymiary zaokraglone
100
320 (W2: 320+60)
170
100
640 (W2: 640+120)
320
100
420 (W2: 420+60)
220
Wymiary zaokraglone
100
320 (W2: 320+60)
170
100
640 (W2: 640+120)
320
100
420 (W2: 420+60)
220
Wymiary zaokraglone
100
320 (W2: 320+60)
170
100
640 (W2: 640+120)
320
100
420 (W2: 420+60)
220

3/6IMM - ALU SGN LED - CB_CBAM_LVAM - EN V05
MOUNTING DIMENSIONS (in mm)
30x15 40x20 60x30
L
321
170
260
90
58,5 20 58,5
23
100
87
45
85
420
220
134
332
73,5 20 73,5
21
100
45
110
L
87
L
21 0
324
34,5
30,5
50,5
530
640
45
220
100
C2 – 30x15 C2 – 40x20 C2 – 60x30
100
220
55
30
77
100
320
55
30
85
640
100
40
400
42
60
16
W2 - 30x15 W2 – 40x20 W2 - 60x30
L
321
170
260
90
58,5 20 58,5
23
100
87
45
85
420
220
134
332
73,5 20 73,5
21
100
45
110
L
87
L
21 0
324
34,5
30,5
50,5
530
640
45
220
100
WIRING DIAGRAM
CB / CBAM
LVAM

4/6 www.hybryd.eu
BEFORE ANY INSTALLATION OR MAINTENANCE OPERATION IS PERFORMED
ON THE LUMINAIRE THE POWER SUPPLY SHOULD BE DISCONNECTED
All installation and maintenance procedures can be performed only by qualied,
properly trained and if appropriate, certied sta
INSTALLATION
1. Unpack the luminaire after transport and verify its condition.
2. Drill holes in ceiling or wall according to luminaire mounting
hole spacing, so that power cables can be pushed freely
into the luminaire through the cable glands. Use dowels or
screws, appropriate for the material luminaire is being mo-
unted to.
3. Unscrew the two M4 screws xing the bottom part of lu-
minaire and remove it, at the same time, remove the plates
with safety sign. Attention! The plates can be supplied se-
parately.
4. Push the power supply cable through the cable gland in lu-
minaire. Screw the luminaire to the wall or ceiling using pre-
viously drilled mounting holes. For W2 mounting type route
the communication and power cables through the hole in
the W2 and screw it to the wall. Then screw the housing
body and the W2.
5. Connect the power supply cables from the HVCBS/LVDBS
system according to the appropriate wiring diagrams, strip
7–8mm of wire copper insulation. Pay special attention to
the luminaire supply voltage!
30x15 / 40x20
60x30

5/6IMM - ALU SGN LED - CB_CBAM_LVAM - EN V05
6. In case of luminaires with built-in address module:
a. set luminaire address using the rotary switch SW1 and
second slider of SW2 switch (SW2-2).
Setting the SW2-2 position to „1” means adding 10 to the
address, according to the table below.
SW2-2
SW1
Address
SW2-2
SW1
Address
0 1 1 1 1 11
0 2 2 1 2 12
0 3 3 1 3 13
0 4 4 1 4 14
0 5 5 1 5 15
0 6 6 1 6 16
0 7 7 1 7 17
0 8 8 1 8 18
0 9 9 1 9 19
0 A 10 1 A 20
SW2 SW1
SW2
SW1
„1“
„0“
SW2-1 SW2-2
b. using the rst slider of SW2 switch (SW2-1) select the
operating mode. Position „1”–maintained(M), position „0” –
non-maintained (NM).
7. Mark the operating mode on the luminaire label. Mark 0
for maintained mode
(M)
and 1for non-maintained mode
(NM)
.
M NM
8. Depending on mounting:
• for W1/W2 insert the plate with safety sign,
• for doblesided C2 insert the plates with safety sign,
• for single sided C2 insert the front plate with safety
sign and light blocking back plate.
Check for exit sign direction during plate installation.
9. Put the bottom part of luminaire and using two M4
screws screw the two luminaire parts together. For the
60x30 luminaire version, before mounting the bottom
part, connect the LED strip power cable plug to the LED
socket on the bottom part.
30x15 / 40x20
30×15 / 40×20
60x30
60×30

6/6 www.hybryd.eu
MAINTENANCE
Luminaire should be cleaned with a damp cloth according to building maintenance plan.
Do not use abrasive cleaners, solvents, substances and cleaning agents containing alcohol to clean the lampshade.
The light source used in this luminaire may only be replaced by the manufacturer, his service agent or a similar qualied person.
STORAGE
The luminaire should be stored no longer than 12 months from the date of purchase, in a dry place with an ambient temperature range of
-10 – + 30˚C.
COMMISSIONING
After all installation procedures are nished, luminaire operation needs to be veried. Follow the instructions below:
1. Switch the luminaire power supply on the HVCBS (CB, CBAM) or LVDBS (LVAM) system.
2. For luminaires without built-in address module:
a. Leave luminaire operating and verify light source operation – should be operating,
b. Turn o luminaire power supply.
3. For luminaires with built-in address module:
a. Congure the HVCBS/LVDBS syste,
b. Run the functional test on HVCBS/LVDBS system,
c. Verify luminaire operation. The light source should operate properly,
d. Verify if the HVCBS/LVDBS system reports proper luminaire operation.
WARRANTY
Warranty is valid and enforceable only when manufacturer's recommendations are preserved, and the installation and usage are proper.
Warranty is granted for a period of 12 months from the date of sale, unless the luminaire has been sold under dierent contract conditions.
The warranty is excluded in case of misuse, unsuitable use, wrong connection or mechanical defects of the luminaire caused by the client.
Table of contents
Other HYBRYD Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Lightolier
Lightolier IS_EG2 Assembly and installation

American DJ
American DJ Mega Bar RGBA User instructions

Vision & Control
Vision & Control LDLF60x180-IR850/24V Instructions for use

Philips
Philips SL ePAR 180 LED Luminaire user manual

SGM
SGM Giotto spot 1200 user manual

STEFLY
STEFLY Canopy Flasher Installation manual and operating instructions