Subject to change without notice. Edition: 11 Aug. 2023 Ver. A0 Page 2/6
Functions and Features
Intelligent Photocell (daylight detection prior to motion detection)
2
The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for
more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is required that the xture stays at
dimmed level during absence.
With insufcient natural light, the sensor
switches on the light automatically when
presence is detected.
With sufcient natural light, the light
does not switch on when presence is
detected.
The sensor switches off the light when
natural light is sufcient, even with
presence.
Manual Override
3
* Short Push (<1s): on/off function;
On →Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this
period, the sensor goes back to normal sensor mode.
Off →On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.
* Long Push (>1s): adjust the hold-time brightness level between10% and 100%.
Note: if end-user do not want this manual override function, just leave the “push” terminal unconnected to any wire.
With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the
brightness by push-switch, which makes the product more user-friendly and offers more options to t some extra-ordinary demands:
Semi-auto Mode (Absence Detection)
4
It is easy to forget to switch off the light, in ofce, corridor, even at home. And in many other cases, people do not want to have a
sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no need to have the light on. The
solution is to apply this “absence detector”: motion sensor is employed, but only activated on the manual press of the push-switch, the
light keeps being ON in the presence, and dims down in the absence, then switches off in the long absence.
Note: end-user can choose either function or function for application. Default function is manual override.
3 4
Tri-level Control (Corridor Function)
1
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice
before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufcient) -->off; and 2 periods of
selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
Note: if the stand-by time is preset at "+∞", the xture never switches off but stays at preset dimming level even when natural light is sufcient.
zero-cross point
Alternating current
Zero-cross Relay Operation
Designed in the software, sensor switches on/off the
load right at the zero-cross point, to ensure that the
in-rush current is minimised, enabling the maximum
lifetime of the relay.
5
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time.
Loop-in and Loop-out Terminal
6