6. Wiring Diagram
DALI master
Detection Pattern7.
Tangential movement 10m
Radial movement 8m
3m 3m
Tangential movement 5m
Radial movement 4m
1
50% blind A
Tangential movement 10m
4m
3m
7
corridor blind B
1. Technical Specifications
Product type Tri-level control PIR DALI sensor
Operating voltage 9.5 ~ 22.5VDC ( suitable DALI power supply)
Input current < 8mA
Power consumption < 0.5W
Detection angle 360
o
Detection area (Max.)*
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2Lux / 10Lux / 50Lux / Disable
Warmming-up time 30s
Operating temperature -20
o
C ~ +50
o
C
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
Rotary switch preset (Please
see the location in 2. Installation)
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%
5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s
10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%
Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
5. Functions
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
This DALI sensor is designed for incoporated in the DALI system, taking command from the DALI master, accepting and carrying out the grouping work with up to 64 lumanaires. It can switch on/off, or dim the
assigned group members and feed back the status to the DALI master.
By connecting the DALI terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HMW23 in the group will turn on the lights when surrounding natural light is below the daylight
threshold. The sensor antenna is shared and the detection area could be widely enlarged in this way.
5.1 Tri-level Control (Corridor Function)
5.2 Synchronization Function
DALI group selection (Please
see the location in 2. Installation)
4. DALI group selection
DALI group configuration can be done on PC or on the rotary switch:
1. There are 16 channels available on the rotary switch. “0” is
for DALI broadcast, the rest 15 channels is for end user to
define the application unit.
2. PC grouping can overwrite rotary switch grouping, the last
setting controls.
3. The rotary switch channel is corresponding to the groups
listed below:
Switch channel DALI group Switch channel DALI group
0
1
2
3
4
5
6
7
broadcast
group 0
group 1
group 2
group 3
group 4
group 5
group 6
8
9
A
B
C
D
E
F
group 7
group 8
group 9
group 10
group 11
group 12
group 13
group 14
2. Installation
Warnings:
1. Installation of the sensor involves connecting it to the mains supply. This work must be
carried out by a specialist in accordance with electrotechnical regulations.
2. Disconnect supply before installing.
3
4
2
(1) Sensor inset
(2) Lens pluggable
(3) Protection cover (covers the
high-voltage terminals, and leaves
the DALI terminals exposed).
(4) Ceiling (drill hole O 70mm).
70mm
HIR23-20230717-A1
Infrared receiver
Photocell
LED indicator
Rotary switch preset
DALI group selection
1
PIR
Blind
A
B
Blind
Note1: the blinds are optional, they may be inserted
behind the lens for focussing the detection range.
Note2:We recommend the mounting distance between sensor to sensor
should be more than 2m to prevent sensors from false-triggering.
Installation Height : 5m
Detection Range (Ø) :10m
HIR23-20230717-A1
Installation and Instruction Manual
HIR23
FLUSH MOUNT PIR DALI SENSOR
L
N
DALI power
supply
DALI
driver
DALI
driver
Bus-mastering
DALI
DALI
DALI 1 DALI 2
HIR23
DALI 1 DALI 2
HIR23
8. Description of the Button Functions (remote control HRC-11)
Press button “ON/OFF” to select permanent ON or permanent OFF mode.
* Press button “AUTO”/“RESET” to exit this mode.
HRC-11
Press button “Shift”, the LED on the top left corner is on to indicate mode selection. All
values / settings in RED are valid for 20 seconds.
For example, to set detection range 100%, daylight threshold Disable, hold-time 5min,
stand-by time +∞, stand-by dimming level 30%, the steps should be:
Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”,
“Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all settings are passed
on the sensor(s).
Lux off
Exp 1
Exp 2
Press button “AUTO” to initiate automatic mode. The sensor starts working and all settings
remain as before the light is switched ON/OFF;
1. Press button “Start” to program.
2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by
time”, “Stand-by dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).
"Exp" refer to Expansion, these two buttons are reserved functions and pending future
development.
CCT+
CCT-
Sensor off Twilight
Shift
AUTO
100% 75% 50% 10%
2 Lux
100 Lux
10 Lux
300 Lux
50 Lux
500 Lux
Disable
Ambient
Memory Apply
Test
2 s
30 s
1 min 10 min
5 min 15 min 30 min
0s
10 s 1h
10% 20% 30% 50%
Dual tech & RF mode
SEMI-AUTO
Hold-time
Stand-by time
Stand-by dimming level & Auto-config.
Daylight threshold
Sensitivity & More functions
RX STBY%
PIR
RX 100%
HF HF+PIR HF/PIR
Shift Send
5 min 30 min
20 min
Power
100%
Power
80%
1 min 10 min +
Start
RESET
ON
OFF
24h 30s
12h 4h
Learn
Erase Transmit
Brightness
CCT-
CCT+
Tri-level Harvest Master ×
Exp 1 Exp 2 Lux off
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
Press button “RESET”, perform DIP Switch/Rotary Switch settings.
*The default settings are: Detection range 100%; Hold-time 5min; Stand-by time +∞;
Stand-by dimming level 30%; Daylight threshold disable;
This key is not appliable on this product.
HRC-11
Sensor off Twilight
Shift
AUTO
100% 75% 50% 10%
2 Lux
100 Lux
10 Lux
300 Lux
50 Lux
500 Lux
Disable
Ambient
Memory Apply
Test
2 s
30 s
1 min 10 min
5 min 15 min 30 min
0s
10 s 1h
10% 20% 30% 50%
Dual tech & RF mode
SEMI-AUTO
Hold-time
Stand-by time
Stand-by dimming level & Auto-config.
Daylight threshold
Sensitivity & More functions
RX STBY%
PIR
RX 100%
HF HF+PIR HF/PIR
Shift Send
5 min 30 min
20 min
Power
100%
Power
80%
1 min 10 min +
Start
RESET
ON
OFF
24h 30s
12h 4h
Learn
Erase Transmit
Brightness
CCT-
CCT+
Tri-level Harvest Master ×
Exp 1 Exp 2 Lux off
In AUTO /SEMI-AUTO modes, press buttons in zone “hold-time” to set the hold-time at 2s
/ 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Dual tech & RF mode
Press buttons in zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min
/ 10min / 30min / 1h / +∞.
Note: 1. To set stand-by-time at 10s/ 5min / 30min / 1h, press “Shift” button rst.
2. “0s” means on/off control;
3. “+∞” means bi-level control, the xture is 100% on when there is motion detected, and remains at the
stand-by dimming level when no presence after motion hold-time. Only when the stand-by time is set in "+∞" and
the ambient lux level is below the target lux level, the lux will auto-on.
Press the button in zone “stand-by dimming level” to set the stand-by dimming level at 10%
/ 20% / 30% / 50%.
Press buttons in zone “Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux
/ 100Lux / 300Lux/500Lux / Disable.
1. Press button “Shift”, the red LED on.
2. Press button “Ambient”, the surrounding lux level is sampled and set as daylight threshold
/ target Lux level.
In AUTO /SEMI-AUTO modes, press buttons in zone “Detection range” to set
detection range at 100%/75%/50%/10%.
1.Press button “Shift”, the red LED on.
2. Press buttons “Tri-level” or “Daylight harvest” to shift between Tri-level control
mode and Daylight harvest mode.
Note: To set daylight sensor at 100Lux / 300Lux/500Lux , press “Shift” button rst.
Master
100% 75%
50% 10%
Tri-level
Harvest
2 Lux 100 Lux
10 Lux 300 Lux
50 Lux 500 Lux
Disable
Ambient
Test
2 s
30 s
1 min
10 min
5 min
15 min
30 min
20 min
0s 10 s
1h
5 min
30 min
1 min
10 min
+
10% 20%
30% 50%
24h
30s
12h
4h
PIR
HF
HF+PIR
HF/ PIR
Learn
Erase
Transmit
Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button rst.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button “RESET” or any button in “Hold-time”.
Stand-by time mode
Hold-time mode
Daylight threshold
Sensitivity & More functions
Stand-by dimming level & Auto-cong.
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
This key is not appliable on this product.
HIR23-20230717-A1 HIR23-20230717-A1

Other Hytronik Security Sensor manuals

Hytronik HMW28/PRO User manual

Hytronik

Hytronik HMW28/PRO User manual

Hytronik HCD438 User manual

Hytronik

Hytronik HCD438 User manual

Hytronik HIR22 Quick guide

Hytronik

Hytronik HIR22 Quick guide

Hytronik HIR32 User manual

Hytronik

Hytronik HIR32 User manual

Hytronik HIR20 User manual

Hytronik

Hytronik HIR20 User manual

Hytronik HIM84 Quick guide

Hytronik

Hytronik HIM84 Quick guide

Hytronik HC403VRC-KD Quick guide

Hytronik

Hytronik HC403VRC-KD Quick guide

Hytronik HMW25 User manual

Hytronik

Hytronik HMW25 User manual

Hytronik HC034RF Quick guide

Hytronik

Hytronik HC034RF Quick guide

Hytronik DUAL sense HIM17 Quick guide

Hytronik

Hytronik DUAL sense HIM17 Quick guide

Hytronik HIR22 User manual

Hytronik

Hytronik HIR22 User manual

Hytronik HIM32 User manual

Hytronik

Hytronik HIM32 User manual

Hytronik HIM54 User manual

Hytronik

Hytronik HIM54 User manual

Hytronik HIM31 User manual

Hytronik

Hytronik HIM31 User manual

Hytronik HIR24 Quick guide

Hytronik

Hytronik HIR24 Quick guide

Hytronik HIR27 User manual

Hytronik

Hytronik HIR27 User manual

Hytronik HIR21 User manual

Hytronik

Hytronik HIR21 User manual

Hytronik HIM38/RF Quick guide

Hytronik

Hytronik HIM38/RF Quick guide

Hytronik Dual Sense HIM16 User manual

Hytronik

Hytronik Dual Sense HIM16 User manual

Hytronik HMW22 User manual

Hytronik

Hytronik HMW22 User manual

Hytronik HIR28 Quick guide

Hytronik

Hytronik HIR28 Quick guide

Hytronik HCD405/BT Quick guide

Hytronik

Hytronik HCD405/BT Quick guide

Hytronik HMW15 Quick guide

Hytronik

Hytronik HMW15 Quick guide

Hytronik HMW39/RF User manual

Hytronik

Hytronik HMW39/RF User manual

Popular Security Sensor manuals by other brands

Apogee Instruments SE-100 owner's manual

Apogee Instruments

Apogee Instruments SE-100 owner's manual

Pfeiffer Vacuum ASM 390 Additional Installation, Operation and Maintenance Instructions

Pfeiffer Vacuum

Pfeiffer Vacuum ASM 390 Additional Installation, Operation and Maintenance Instructions

Balluff BTL7-A/C/E/G501-M P-S32/S115/KA Series user guide

Balluff

Balluff BTL7-A/C/E/G501-M P-S32/S115/KA Series user guide

Newlec EMERGENCY TWINSPOT instructions

Newlec

Newlec EMERGENCY TWINSPOT instructions

Tyco Visonic TOWER-20 PG2 installation instructions

Tyco

Tyco Visonic TOWER-20 PG2 installation instructions

Toshiba TCB-LDS Series installation manual

Toshiba

Toshiba TCB-LDS Series installation manual

Yale ENA-DC SmartHome Alarm series user manual

Yale

Yale ENA-DC SmartHome Alarm series user manual

Iget HOME XP4B installation manual

Iget

Iget HOME XP4B installation manual

CARLO GAVAZZI SMS user manual

CARLO GAVAZZI

CARLO GAVAZZI SMS user manual

LINKIND LL20004 user manual

LINKIND

LINKIND LL20004 user manual

EINHELL TC-MD 50 operating instructions

EINHELL

EINHELL TC-MD 50 operating instructions

Tyco SD-304C PG2 installation instructions

Tyco

Tyco SD-304C PG2 installation instructions

Greenlee GT-11 instruction manual

Greenlee

Greenlee GT-11 instruction manual

mySmart MWS3A-PRM-LV Product guide

mySmart

mySmart MWS3A-PRM-LV Product guide

Visonic CLIP SMA installation instructions

Visonic

Visonic CLIP SMA installation instructions

Hitachi UST-568 instruction manual

Hitachi

Hitachi UST-568 instruction manual

Satel TESTER INDIGO manual

Satel

Satel TESTER INDIGO manual

Orno VIRONE DV-1 manual

Orno

Orno VIRONE DV-1 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.