1 Safety instructions
• In order to guarantee the correct condition of the unit for the operating time it
is necessary to use the unit only for media to which the wetted materials are
sufficientlyresistant(→Technicaldata).
• Theresponsibilitywhethertheunitissuitablefortherespectiveapplicationlies
withtheoperator.Themanufacturerassumesnoliabilityforconsequencesof
misusebytheoperator.Improperinstallationanduseoftheunitresultinaloss
ofthewarrantyclaims.
• TheunitcomplieswiththestandardEN61000-6-4.Indomesticareas
(EN61000-6-3)theunitmustbeinstalledinclosedmetaltanks/pipes.
2 Functions and features
Theunitmonitorsthelevelofliquid,aqueousmediaintanksandpipes.Itisin
particularintendedforthedetectionofcoolants(e.g.R134a,R22orR717)and
oils.Itcanbeusedforpointleveldetectionandrun-dryprotection.
• Theunitcanbeoperatedatmediumtemperaturesof-20...85°C.
• Tankpressure:-1…40bar.
3 Installation
ThedeviceiseitherinstalledandsealeddirectlyviatheG1/2internalthreadorvia
asuitablemountingadapter.
For direct installation via the internal thread:
► Usesuitablesealingmaterialorasuitable(forrefrigerationsystems)seal-
ingmethod. Thesensorhousingmustbeinelectricalcontactwiththemetal
processconnection.
For installation via mounting adapter:
A correct fit and function of the unit and ingress resistance of the
connectionareonlyensuredusingifmadapters.
Availableaccessories:www.ifm.com→Datasheetsearch→Accessories
► Observetheinstallationinstructionsoftheadapterused.
► Weldorinstalltheadapterintothetank/pipe.
► Slightlygreasethethreadofthesensorusingalubricatingpastewhichis
suitableandapprovedfortheapplication.