Ink Bird ITC-106 User manual

PID Temperature Controller
ITC-106
User Manual
Version 1.0
Inkbird Tech. Co., Ltd.
Copyright
Copyright©2016 Inkbird Tech. Co., Ltd. All rights reserved. No part of this document may be reproduced
without prior written permission.
Disclaimer
Inkbird has made every effort to ensure that the information contained in this document is accurate and
complete; however, the contents of this document are subject to revision without notice. Please contact
Inkbird to ensure you have the latest version of this document.
http://waterheatertimer.org/Add-another-thermostat-to-gas-or-electric-water-heater.html#PID

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
2
Contents
1. Safety Precautions ................................................................................................3
2. Specification ........................................................................................................4
3. Dimension and Installing .......................................................................................5
4. Wiring Diagram ....................................................................................................5
5. Panel Instruction ..................................................................................................6
6. Setting Parameters ...............................................................................................7
6.1 Sensor Type and Measuring Range......................................................................................7
6.2 Operation Guide ...............................................................................................................7
6.21 Boot screen display....................................................................................................7
6.22 Enter the settings menu ............................................................................................7
6.23 Sensor Input Type Setting:.........................................................................................8
6.24 Output Parameters Setting: ........................................................................................8
6.25 PID Parameters Setting:.............................................................................................8
6.26 Setup Flow Chart:......................................................................................................8
7. Technical Assistance and Warranty ....................................................................... 10
7.1 Technical Assistance ........................................................................................................ 10
7.2 Warranty.........................................................................................................................10

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
3
1. Safety Precautions
Ensure the product using within the specification.
Do not touch the terminals at least while power is being supplied. Doing so may
occasionally result in injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shaving or filings from
installation to enter the product. Doing so may occasionally result in electric shock,
fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise,
injury from explosion may occasionally occur.
Never disassemble, modify or repair the product or touch any of the internal parts.
Electric Shock, fire, or malfunction may occasionally occur.
If the output relays are used past their life expectancy, contact fusing or burning may
occasionally occur. Always consider the application conditions and use the output
relays within their rated load and electrical life expectancy. The life expectancy of
output relays varies considerably with the output load and switch conditions.

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
4
2. Specification
Supply Voltage
AC 100~240V 50/60Hz (model:ITC-106RH, ITC-106VH)
AC/DC 12~24V 50/60Hz (model:ITC-106RL, ITC-106VL)
DC 12~24V (model:ITC-106RL, ITC-106VL)
Operating Voltage
Range
85~110% of the rated voltage
Power Consumption
5VA(100~240VAC)
4VA(12~24VAC)
3W(12~24VDC)
Display Code
PV: displays in red high luminance LED with 9.9mm height of 4
digits
SV: displays in green high luminance LED with 8.00mm height
of 4 digits
Display Accuracy
±0.2%FS 0.1ºC/ ºF(<1000ºC/ ºF);1ºC/ ºF(≥1000ºC/ ºF)
Sampling Period
0.5 second
Temperature
Compensation
0~50 ºC /32~122ºF
Control Output
Relay Output: AC 250V 3A (resistive load)
Voltage Output (for driving SSR): 12VDC, 30mA DC
Maximum load: 600Ω
Electrical Life of Relay:100,000 times
Alarm Output
Relay Output: AC 250V 3A (resistive load)
Weight
About 140g
Working Temperature
-10~ 55 ºC / 14~ 131 ºF(No freeze or condensation)
Working Humidity
RH 35-85%
Storage Temperature
-25~65ºC / -13~ 149 ºF (No freeze or condensation)
Models and Specification
Model
Control Output
Supply Voltage
ITC-106RL
Relay Output
AC/DC 12~24V
ITC-106VL
SSR Output
AC/DC 12~24V
ITC-106RH
Relay Output
AC 100~240V
ITC-106VH
SSR Output
AC 100~240V

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
5
3. Dimension and Installing
Size Diagram (Unit: mm)
Shell Size Install Adapter Panel Cutout
Insert the temperature controller into the hole in the panel, put the adapter from the
back and push it to button and make it clasp for temporarily fastening. Be sure there
is no gap among the controller, panel and the adapter and then fasten the two screws
on the adapter with the torque of 0.29N to 0.39N.
Be sure the ambient temperature is within the stated working range in the manual,
especially when there are two or more temperature controllers installed.
4. Wiring Diagram
2 wires sensor 3 wires sensor Thermocouple Output Relay Output Voltage
Power Connection: #9 and #10 terminals are for power connecting, which its supply
voltage should be match the item model.
Platinum Resistance Sensor Connection:
Three wires sensor: connected the #3 terminal with the red wire, the other two bule
wires should be separately connected to the #4 and #5 terminals.
And the sensor with two wires (e.g. PT100) should be separately connected to
the #3 and #5 terminals, the #4 and #5 terminals must be connected with the wire.
Thermocouple Connection(e.g. K sensor): #3 terminal is connected to the
positive pole(Red) and the #4 terminal is connected to the negative pole(Blue).

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
6
5. Panel Instruction
①PV Displaying Screen: Displaying the measuring value or the setting parameters.
②SV Displaying Screen: Displaying the setting value or the set parameters readout.
③Working Indicator Light
OUT: Control Output Indicating
ALM: Alarm Output Indicating
RUN: Manual Operation Indicating
④UP Button: when setting the value, pressing the up button can be increase the value
that would be added rapidly by keeping press this button.
⑤DOWN Button: when setting the value, pressing the down button can be decrease the
value that would be reduced rapidly by keeping press this button.
⑥SHIFT Button: when setting the value or parameters,
A, pressing this button to switch to the required value position.
B, Pressing this button can be shift to the submenu from the main menu.
C, Pressing this button can be freely switch to another mode from manual or the
automatic operation.
⑦SET Button: Pressing this button can read the value of control output and the set
temperature. Hold and press this SET button for 3s or more can be enter into the
parameters settings mode.

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
7
6. Setting Parameters
6.1 Sensor Type and Measuring Range
Sensor Type
Input
Code
Measuring Range
Platinum
Resistor
Pt100
-200~600 (ºC )
-300~1100(ºF )
Cu50
-50~150 (ºC )
-100~300(ºF )
Thermocouple
K
-50~1300 (ºC )
-100~2300(ºF )
S
-50~1700 (ºC )
-100~3000(ºF )
Wre
0~2300 (ºC )
0~4000(ºF )
T
-200~400 (ºC )
-300~750(ºF )
E
0~1000 (ºC )
0~1800(ºF )
J
0~1000 (ºC )
0~1800(ºF )
B
0~1800 (ºC )
0~3200(ºF )
N
0~1000 (ºC )
0~1800(ºF )
Remarks:
The faulty input sensor is the "K" type.
If select the wrong input sensor, the measuring temperature will be incorrect and may
exceed the measuring range with displaying "orAL", control output off.
6.2 Operation Guide
6.21 Boot screen display
6.22 Enter the settings menu
Under measuring and controlling condition, press ▲/▼to set the temperature value, press
and hold the "SET" button for 2 seconds to enter into the parameters settings mode.

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
8
6.23 Sensor Input Type Setting:
Set the sensor input type as required(the faulty is the "K" type), the temperature need to
calibrated for there will be deviation due to the sensor and the operating environment.
6.24 Output Parameters Setting:
The recommended control mode for the first use is the PID control(default settings of PID
control), please select the self-tuning mode when the controlling temperature cannot reach
the desired value after it worked over time with the stable controlled temperature.
Under the self-tuning mode, the temperature will exceed the set value and activate the
alarm. The exceeding temperature value is related to the heating system but it will return
to normal after finished the self-tuning. If the temperature control requirement is
undemanding, please select the ON/OFF control mode which its range of temperature
controlling is depended on the dF(hysteresis). As below is the setting and the calculation:
The low temperature point=SV setting value-dF
The high temperature point=SV setting value+dF.
※dF(hysteresis) can be worked both on alarm setting and ON/OFF control mode.
6.25 PID Parameters Setting:
SSR control output: the control period(CtrL) can be set within 4 seconds(default 2
seconds);
Relay control output: The control period (CtrL) should be set to longer time(the normal is
18s) that would prolong the work life of the relay.
6.26 Setup Flow Chart:
(Please check next page)

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
9

ITC-106 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
10
7. Technical Assistance and Warranty
7.1 Technical Assistance
If you have any problems installing or using this thermostat, please carefully and
thoroughly review the instruction manual. If you require assistance, please write us to
cs@ink-bird.com. We will reply your emails in 24 hours from Monday through Saturday.
You can also visit our web site www.ink-bird.com to find the answers of the common
technical questions.
7.2 Warranty
INKBIRD TECH. C.L. warrants this thermostat for one years from the date of purchase
when operated under normal condition by the original purchaser (not transferable), against
defects caused by INKBIRD’s workmanship or materials. This warranty is limited to the
repair or replacement, at INKBIRD’s discretion, of all or part of the thermostat. The
original receipt is required for warranty purposes.
INKBIRD is not responsible for injury property damage or other consequential damages or
damages of third parties arising directly from an actual or alleged in mater of workmanship
of the product.
There are no representations, warranties, or conditions, express or implied, statutory or
otherwise, other than herein contained in the sale of goods act or any other statue.
Contact Us
Technical Support: cs@ink-bird.com
Business Hours: 09:00-18:00(GMT+8) from Monday to Friday
URL: www.ink-bird.com
Table of contents
Other Ink Bird Temperature Controllers manuals

Ink Bird
Ink Bird ITC-1000 User manual

Ink Bird
Ink Bird ITC-306T User manual

Ink Bird
Ink Bird ITC-308 User manual

Ink Bird
Ink Bird ITC-608T User manual

Ink Bird
Ink Bird ITC-1000 User manual

Ink Bird
Ink Bird ITC-308 User manual

Ink Bird
Ink Bird ISC-007BW User manual

Ink Bird
Ink Bird ITC-100 User manual

Ink Bird
Ink Bird ITC-306A User manual

Ink Bird
Ink Bird ITC-308 User manual