Top View
Mounting Height
Coverage (dia.)
8’
20’
10’
24’
12’
30’
Side View
20’ 13’ 6’ 0 6’ 13’ 20’
12’
10’
8’
HFD Range
360°
HFD Range
OVERVIEW
The OS-361DT is a ceiling mount low voltage dual technology
occupancy sensor designed for area lighting, or HVAC
control, for energy efficient building management. The sensor
combines a Passive Infrared (PIR) sensor, a High Frequency
Doppler (HFD) sensor and advanced signal processing
firmware to perform superior occupancy sensing capability.
An omni-directional quad element PIR sensor, a
state-of-the-art HFD sensor and advanced signal processing
firmware are employed to provide superior occupancy
sensing capability. The sensor will activate the relay output
and delay timer when both PIR and HFD sensors detect the
presence of occupant. The delay timer will be reset if either
PIR or HFD sensor detects motion before the delay time has
elapsed.
The OS-361DT is ideal for areas where motion may not be
easily detectable by a single technology occupancy sensor.
The sensor is operated by 24VDC low voltage power supplied
from an IR-TEC power pack, or building management system.
The sensor provides a form A relay dry contact for control of
lighting and/or HVAC systems.
Low Voltage Dual-Tech Occupancy Sensor
OS-361DT
INSTALLATION INSTRUCTIONS
APPLICATION NOTES
SPECIFICATIONS
Power supply
Current drain
Signal output
Infrared sensor
HFD sensor
HFD sensitivity
Detectable speed
Mounting height
Detection range
OFF delay setting
Op. humidity
Op. temperature
Dimensions
24±2 VDC
20 mA @24V, standby mode
Form A, 30VDC, 0.2A max.
Quad element pyroelectric infrared sensor
X-band DRO type with patch antenna
60/80/100/120% selectable
0.33 ~ 10 ft/sec. (0.1 ~ 3 m/sec.)
8 ~ 12 ft. (2.4 ~ 3.6 m)
2.5 X mounting height in diameter
0/1’/3’/5’/10’/15’/20’/30’ selectable
Max. 95% RH
-4°F ~ 122°F (-20°C ~ 50°C)
4.4” dia. x 1.7” depth (110 mm x 44mm)
PIR sensor is more sensitive to the movements
“crossing” the detection zones than “toward” or “away”
the sensor unit. Avoid placing the sensor in line with the
path of occupant, if possible.
PIR sensor cannot “see” the movements behind
obstacles, such as furniture, shelf, glass or partitions. As
a general rule, ensure to place the sensor at where the
occupant could have clear view of the sensor.
HFD sensor may penetrate through certain types
of non-metallic partition material (glass, plaster,
plywood…etc) and detects the movements outside of
partition. Adjusting the HFD sensitivity may be necessary
to achieve optimal detection.
Place the sensor at least at 5 ft. (1.5m) away from air
supply duct and fluorescent lighting to avoid false
activating.
For open office areas with partition which could block the
sensor view to occupant movements, it is recommended
to place the sensors over the intersection of multiple
workstations. For large areas of open office or space,
place multiple sensors so that there is overlap coverage
with each adjacent sensor.
The OS-361DT can be either surface mounted or recess
mounted in a hole with 3.4” diameter on the ceiling.
1.
2.
3.
4.
5.
6.
DIMENSIONS
1.73” 4.33”
4.33”
DETECTION PATTERN
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1)This device may not cause harmful interference,
(2)This device must accept any interference received,
Including interference that may cause undesired operation.
P/N: 058-36100-002 Printed in Taiwanwww.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
Turn power OFF at circuit breaker before connecting Power
Pack or Sensor.
Do NOT touch the window of infrared sensor on the PCB
assembly.
CAUTION
FCC ID: NRIOS-361DT
OS-361DT
DC
Hot Black
White
Red
RedRed
Black
Green
White
Red
Neut
Relay
Relay
DC24V
GND
COM
NO
Control
Load
Hot
120~277V
Neutral
Black
Blue
PPU-301
Hot Black
White
Red
Orange
Grey
Brown
Red
Neut
Relay
Relay
DC24V
GND
COM
NO
Control
Manual
Hold ON
Hold OFF
Load
Momentary Button
Hot
120~277V
Neutral
Red
Black
Green
White
Red
Black
Blue
DC
OS-361DT
PPU-300
The OS-361DT is an occupancy sensor which combines two
different sensing technologies, PIR and HFD, in one housing
for ceiling mount installation. The sensor is operated by 24
VDC low voltage power. Whenever the sensor detects the
presence of occupant, its dry contact relay output will be
engaged for the delay time programmed. The delay timer will
be reset if any motion is detected by either PIR or HFD sensor
before delay time elapses.
8 different delay times and 4 different HFD sensitivity levels
can be programmed via specific DIP switch combinations.
2 LED’s are available to indicate the operation of PIR and
HFD sensors respectively. The sensor operation LED can be
disabled by specific DIP switch, if necessary.
It is recommended to conduct a walk test to verify optimum
coverage after sensor installed. To test the sensor range,
restore the front cover, apply the low voltage power and wait
approximately 90 seconds for sensor to warm up. The LED
will blink during warm-up period. Walk into the projected area
in the path of occupant show up and observe if the sensor
can detect the presence. The LED will be lit whenever sensor
detects the motion. If the space has multiple entrances,
repeat the test in all available paths.
HFD sensor could possibly detect the movements outside of
certain type of dry wall or partition. If happened, sensitivity
can be adjusted by changing the ON-OFF combinations of
DIP switch #1 and #2 as the following table shows.
2 LED’s are available to indicate the status of PIR and HFD
sensor operation. The LED indication can be disabled by
setting the SW #3 to OFF position.
A 6-pole DIP switch is available for various sensor settings via
combinations of ON and OFF positions of specific switch.
Various control modes may be achieved by different wiring
connections. The following diagrams are typical control for
reference. For the availability of more complex control, please
contact [email protected] for technical assistance.
IR-TEC International Ltd. warranties this product to be free of
defects in materials or workmanship for a period of five years
from date of shipment. There are no obligations or liabilities
on the part of IR-TEC International Ltd. for consequential
damages arising out or in connection with the use or
performance of this product or other indirect damages with
respect to loss of property, revenue, or profit, or cost of
removal, installation or reinstallation.
WARRANTY
SENSOR OPERATION MOUNTING THE SENSOR
HFD SENSITIVITY – SW #1 & #2
LED ON/OFF – SW #3
Total 8 different delay times can be selected via the combinations
of SW #4, #5 and #6 as the following table shows.
OFF DELAY – SW #4, #5, & #6
RANGE TEST
SENSOR SETTINGS
SENSOR INTERNAL
WIRING DIAGRAM
Loosen the locking screw to the position where the front
cover can be removed. Leave the screw attached with
Connect the wire leads with IR-TEC power pack or BMS
as per wiring diagram of the desired control.
Mount the sensor base with screws provided. For surface
mount, use two knockout holes underneath both sides of
the PCBA. For recess mount, use two holes on the flange
of sensor base.
Replace the front cover and tighten the locking screw.
1.
2.
3.
4.
B. Manual-ON/Auto-OFF with PPU-300
A. Auto-ON/Auto-OFF with PPU-301
The supplied rubber pad can be used to cover the
locking screw for aesthetic purpose.
The respective LED will light on whenever PIR (blue)
or HFD (green) sensor detects the motion.
Note:
Stay out of sensor coverage during warm-up to avoid
extending the period.
Note:
Infrared sensor
HFD Sensor LED
HFD Sensor
PIR Sensor LED
DIP Switch (Don't touch!!)
Recess Mount Knockout
Recess Mount Knockout
Surface
Mount KnocKout
Surface Mount
Knockout
60% 80% 100% 120%
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
*
*
10 min. 15 min. 20 min. 30 min.
0 sec. 1 min. 3 min. 5 min.
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
* Factory Set

Other IR-Tec Accessories manuals

IR-Tec WallSenzr LBS-701 Series User manual

IR-Tec

IR-Tec WallSenzr LBS-701 Series User manual

IR-Tec TRANS LMD-509 Series User manual

IR-Tec

IR-Tec TRANS LMD-509 Series User manual

IR-Tec OS-551DT User manual

IR-Tec

IR-Tec OS-551DT User manual

IR-Tec OS-NET ON-LRD-209S User manual

IR-Tec

IR-Tec OS-NET ON-LRD-209S User manual

IR-Tec WallSenzr LDD-700 Series User manual

IR-Tec

IR-Tec WallSenzr LDD-700 Series User manual

IR-Tec OS-551 User manual

IR-Tec

IR-Tec OS-551 User manual

IR-Tec trans LMD-109 User manual

IR-Tec

IR-Tec trans LMD-109 User manual

IR-Tec wallSenzr LDT-700 Series User manual

IR-Tec

IR-Tec wallSenzr LDT-700 Series User manual

Popular Accessories manuals by other brands

Rechner Sensors SMART Paddle instruction manual

Rechner Sensors

Rechner Sensors SMART Paddle instruction manual

Banner K30 Pro instruction manual

Banner

Banner K30 Pro instruction manual

Rolfit CS-160P user manual

Rolfit

Rolfit CS-160P user manual

Panasonic MA4X713 (MA713) Specification sheet

Panasonic

Panasonic MA4X713 (MA713) Specification sheet

Bernard Jump Liners SPEC JL-1.3 Specification sheet

Bernard

Bernard Jump Liners SPEC JL-1.3 Specification sheet

SmartSun MEDIDA user manual

SmartSun

SmartSun MEDIDA user manual

Bogen RIO1S Specifications

Bogen

Bogen RIO1S Specifications

Crivit CEK 29 A1 Operating instructions and safety instructions

Crivit

Crivit CEK 29 A1 Operating instructions and safety instructions

Klarstein 10032181 manual

Klarstein

Klarstein 10032181 manual

D3FY SPORTS VERT3X owner's manual

D3FY SPORTS

D3FY SPORTS VERT3X owner's manual

OxyGo CPAP Sanitizer+ instructions

OxyGo

OxyGo CPAP Sanitizer+ instructions

EWK I Maintenance manual

EWK

EWK I Maintenance manual

Lion Precision LRD6300 user guide

Lion Precision

Lion Precision LRD6300 user guide

Leuze electronic IPS 248i Original operating instructions

Leuze electronic

Leuze electronic IPS 248i Original operating instructions

Simrad PI SEINESOUNDER - REV D instruction manual

Simrad

Simrad PI SEINESOUNDER - REV D instruction manual

Elsner KNX AQS/TH-B-UP Series Installation and adjustment

Elsner

Elsner KNX AQS/TH-B-UP Series Installation and adjustment

steute RF 96 SDS SW868-NET Mounting and wiring instructions

steute

steute RF 96 SDS SW868-NET Mounting and wiring instructions

BASETech BT-1761037 operating instructions

BASETech

BASETech BT-1761037 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.