Model LD — 11.2 K-factor
Large Drop Upright Sprinkler, Standard Response
Control Mode Specific Application
Page 1 of 4 AUGUST 2018 TFP335
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Specific
Application is a glass bulb type auto-
matic sprinkler. It is intended for use
with the National Fire Protection Asso-
ciation large drop sprinkler installation
criteria for the protection of high piled
storage. The LD Sprinkler can provide a
higher level of protection than standard
spray sprinklers and, in some cases,
can provide an economic advantage by
eliminating in-rack sprinklers.
NOTICE
The TYCO Model LD 11.2 K-factor,
Large Drop Upright Sprinkler described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number
Refer to Table A for sprinkler identifica-
tion number.
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 289-04-E
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb ......................Glass (5mm dia.)
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Additional Technical Data
Refer to Table A for additional techni-
cal data.
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Specific
Application is only for use with National
Fire Protection Association “large drop
sprinkler” installation criteria.
TFP335
Page 2 of 4
Installation
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Specific
Application must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontal, a small air bubble
should be present. The diameter of
the air bubble is approximately 1/16
in. (1,6 mm) for the 155°F (68°C) rating
and 3/32 in. (2,4 mm) for the 286°F
(141°C) rating.
A leak tight 3/4 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 20
lb-ft (13,4 to 26,8 N∙m). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand
tighten the Model LD Sprinkler into the
sprinkler fitting.
Step 2. Using the W-Type 3 (End
B) Sprinkler Wrench (Ref. Figure 2)
applied to the sprinkler Wrench Flats
(Ref. Figure 1), tighten the Model LD
Sprinkler into the sprinkler fitting.
Care and
Maintenance
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Spe-
cific Application must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For additional infor-
mation, refer to the Installation section.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation, such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Item Description
Sprinkler Identication Number (SIN) TY5153
TY5153 is a redesignation of C5153
K-factor, (gpm/psi) (lpm/bar) 11.2 gpm/psi½(161,3 lpm/bar½)
Temperature Rating ºF (ºC)
155°F (68°C)
200°F (93°C)
286°F (141°C)
Thread Size 3/4 in. NPT or ISO 7-R 3/4
Sprinkler Orientation Upright
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
*
**
*
*
**
CROSS
SECTION
UPRIGHT
4
5
WRENCH
FLAT
1/2" (12,7 mm)
NOMINAL MAKE-IN
2-3/8"
(60,3 mm)
3/4"
NPT
2
1
3 6
Temperature rating
is indicated on
Deector.
Compression
Screw
-Bulb
2
-
3
Frame
-
1
4
5 Button
-
Sealing
Assembly
Deector
-
-
6
Pipe thread connections
per ISO 7-1 can be
provided on special
request.
APPLY
WRENCH AS
SHOWN
WRENCH
RECESS
(END "B")
FIGURE 1
MODEL LD LARGE DROP
UPRIGHT SPRINKLER
FIGURE 2
W-T Y PE 3
SPRINKLER WRENCH
TABLE A
MODEL LD LARGE DROP UPRIGHT SPRINKLER
TECHNICAL DATA
TFP335
Page 3 of 4
TABLE B
MODEL LD LARGE DROP UPRIGHT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Model LD (TY5153), K = 11.2,
Upright Large Drop Sprinkler, (specify)
temperature rating, (specify) finish,
P/N (specify):
155°F ( 68°C) ..................50-400-2-155
200°F (93°C) .................50-400-2-200
286°F (141°C) .................50-400-2-286
Sprinkler Wrench
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Storage Type NFPA
Sprinkler Type CMSA
Response Type SR
System Type Wet
Temperature Rating ºF (ºC)
155°F (68°C)
200°F (93°C)
286°F (141°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13
Idle Pallet Storage Refer to NFPA 13
Rubber Tire Storage Refer to NFPA 13
Roll Paper Storage
(Refer to the Standard) Refer to NFPA 13
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) Refer to NFPA 13
TFP335
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

This manual suits for next models

1

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY2334 User manual

Johnson Controls

Johnson Controls tyco TY2334 User manual

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls tyco EC-8C Series User manual

Johnson Controls

Johnson Controls tyco EC-8C Series User manual

Johnson Controls tyco ESFR-34 User manual

Johnson Controls

Johnson Controls tyco ESFR-34 User manual

Johnson Controls SABROE SVER User manual

Johnson Controls

Johnson Controls SABROE SVER User manual

Johnson Controls tyco TY2234 User manual

Johnson Controls

Johnson Controls tyco TY2234 User manual

Johnson Controls tyco CHEC User manual

Johnson Controls

Johnson Controls tyco CHEC User manual

Johnson Controls tyco ILLUSION User manual

Johnson Controls

Johnson Controls tyco ILLUSION User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls TY5811 User manual

Johnson Controls

Johnson Controls TY5811 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY2335 User manual

Johnson Controls

Johnson Controls tyco TY2335 User manual

Johnson Controls tyco CC1 User manual

Johnson Controls

Johnson Controls tyco CC1 User manual

Johnson Controls tyco TY720 User manual

Johnson Controls

Johnson Controls tyco TY720 User manual

Johnson Controls tyco TY-L Series User manual

Johnson Controls

Johnson Controls tyco TY-L Series User manual

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM34 User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Popular Irrigation System manuals by other brands

Rain SuperPro S075 S Setting instructions

Rain

Rain SuperPro S075 S Setting instructions

Viking MICROMATIC VK106 Technical data

Viking

Viking MICROMATIC VK106 Technical data

Viking VK530 Technical data

Viking

Viking VK530 Technical data

Reliable F3-80 Series manual

Reliable

Reliable F3-80 Series manual

Viking M Installation

Viking

Viking M Installation

Autopot 80Pot system Set-up guidelines

Autopot

Autopot 80Pot system Set-up guidelines

Micro Rain MR 32 INSTRUCTION MANUAL FOR OPERATION AND MAINTENANCE

Micro Rain

Micro Rain MR 32 INSTRUCTION MANUAL FOR OPERATION AND MAINTENANCE

Reliable DDX PrePaK Instructions for installation, operation care and maintenance

Reliable

Reliable DDX PrePaK Instructions for installation, operation care and maintenance

Victaulic VicFlex V32 Assembly instructions

Victaulic

Victaulic VicFlex V32 Assembly instructions

Autopot 80 Pot System Set-up guidelines

Autopot

Autopot 80 Pot System Set-up guidelines

K-Rain RPS Select Setting instructions

K-Rain

K-Rain RPS Select Setting instructions

K-Rain RPS 75i Setting instructions

K-Rain

K-Rain RPS 75i Setting instructions

RainMaster RME HAWK user manual

RainMaster

RainMaster RME HAWK user manual

K-Rain RPS 46 instruction manual

K-Rain

K-Rain RPS 46 instruction manual

Aqua Control C4067 manual

Aqua Control

Aqua Control C4067 manual

Pierce CP600 Assembly manual

Pierce

Pierce CP600 Assembly manual

Toro TS120 operating manual

Toro

Toro TS120 operating manual

Toro TWRS user guide

Toro

Toro TWRS user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.