GB 6
GB
Theconnectionsontheterminalstripandencoder
inputs are safely isolated in accordance with
VDE 0100. The person who installs the system /
machine must make sure that the existing or
newlywiredcircuitmeetstheVDErequirements.
- Only connect control lines to switching elements and setting
devices (relay, switch, potentiometer), that are suitable for extra-
low voltages.
- Useshielded/twistedcontrollines.Connecttheshieldonlysingle-
sided to PE of the frequency inverter.
- Use shielded motor cables. Connect shield to the PE and
extensively connect to motor housing.
- Earth frequency inverter very well: star-shaped earthing, avoid
earth loops, shortest connection to main earthing terminal.
1. Operating Specifications
1.5 Operating Instructions
- Installanisolatingswitchbetweenthevoltagesupplyandinverter,
so that KEB COMBIVERT can shut off independently.
- Frequent switching between mains and inverter is not permitted!
- Switchingbetweenmotorandinverterduringoperationisprohibited!
- TheKEBCOMBIVERT istobeoperatedundersuitableconditions
(see Ambient Conditions in Part 2).
- Whenchangingtheprogrammingofafrequencyinverter(deviation
from factory setting) check it once more before start up.
!Wrong
setting can lead to unintended behaviour of the drive!
- Shoulda malfunction oradefect occuronthe KEB COMBIVERT,
in spite of keeping to the connection and operating instructions, it
can lead to undefined operating conditions. Consequently the
actuation of software-type proctective measures like e.g. limit
switch,the correct performanceofa brake orthecorrectreaction
to setpoint value settings is not guaranteed.
- Theprotectionofaplantonlythroughsoftwareprotectivefunctions
is not sufficient, it is absolutety necessary to install external
protective measures that are independent from the KEB
COMBIVERT.
To avoid damages to the inverter as well as
material damages and injuries to persons,
oberserve the following instructions: