Kentec Electronics Sigma CP K Series User manual


Man-1078_Sigma_CP_22
Page 2 of 24
Index Page
0B1. Introduction .........................................................................................................................3
1B2. Safety and mounting.............................................................................................................3
2B3. Technical specification...........................................................................................................4
3B4. Using intrinsically safe barriers...............................................................................................8
4B5. Control panel fascia...............................................................................................................9
5B6. Connecting to the circuit board ............................................................................................ 10
6B7. Software revision number.................................................................................................... 10
7B8. Detection zone wiring.......................................................................................................... 11
8B9. Sounder circuit wiring.......................................................................................................... 12
9B10. Connection to remote control terminals .............................................................................. 12
10B11. Aux 24V DC supply............................................................................................................ 13
11B12. Connection to relay contacts .............................................................................................. 13
12B13. Connection to Repeater panels........................................................................................... 13
13B14. Connection to Ancillary boards ........................................................................................... 14
14B15. Connection to 8 way Sounder boards ................................................................................. 14
15B16. Panel operation................................................................................................................. 15
16B17. Configuration options ........................................................................................................ 16
17B18. Watchdog reset switch ...................................................................................................... 19
1819. Processor reset switch ....................................................................................................... 19
19B20. Internal indications –troubleshooting................................................................................. 19
39B20.1 Mains fail ................................................................................................................................19
40B20.2 Batt fail...................................................................................................................................19
41B20.3 CPU fault ................................................................................................................................ 19
42B20.4 Aux 24V fault ..........................................................................................................................19
43B20.5 Batt low..................................................................................................................................19
44B20.6 Earth fault...............................................................................................................................19
45B20.7 Sys fuse fault ..........................................................................................................................20
46B20.8 S1 fault and S2 fault ................................................................................................................ 20
47B20.9 Comms fault............................................................................................................................20
21. Power supply .................................................................................................................... 21
22. Maintenance ..................................................................................................................... 22
22B23. Zone designation label....................................................................................................... 22
23B24. Record of Configuration..................................................................................................... 23

Man-1078_Sigma_CP_22
Page 3 of 24
0B1. Introduction
The SIGMA CP range consists of a series of conventional fire alarm control panels designed in accordance
with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating
Equipment.
The range consists of 2, 4 and 8 zone control panels. All control panels are available in two versions:
Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder
circuits are provided).
Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. This is
what is commonly referred to as a two-wire system.
Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also offers
the ability to provide zoned or two stage sounder operation.
All control panels have an integral, mains powered battery charger and power supply designed in
accordance with the requirements of EN54-4.
In addition to the requirements of EN54-2 the control panel has the following facilities:
………….
Test condition
to allow the automatic resetting of zones in alarm for testing purposes. EN54-2
Section 10 option with requirements.
………….
Delay of the actioning
of fire alarm devices (sounders) so that an alarm may be verified before a
premises is evacuated. EN54-2 Section 7.11 option with requirements.
………….
Fire alarm devices
to enable an audible warning to be sounded throughout a premises upon the
detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with
requirements.
In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and
local fire which operate upon fire condition. These are to be used for local control and signalling.
1B2. Safety and mounting
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’
relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance
with the following:
(i) IEE regulations for electrical equipment in buildings
(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
ensure that you make any appropriate information about this product available to anyone concerned with its
use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As
such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a
readily accessible double pole disconnect device meeting the requirements of EN60950/IEC950 which
disconnects live and neutral simultaneously shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -50C (+/- 3) and +400C (+/-
2) and with a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.

Man-1078_Sigma_CP_22
Page 4 of 24
Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level
position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting
positions.
It should be positioned in an accessible position as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not
liable to move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable
entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared
before power is applied to the panel.
2B3. Technical specification
Table 1 - Electrical specifications
Mains supply
230V AC +10% - 15% (100 Watts maximum)
Mains supply fuse
1.6Amp (F1.6A L250V)
Replace only with similar type
Power supply rating
3 Amps total including battery charge 28V +/ 2V
Maximum ripple current
1.5 Volts
Output voltage
18.5 to 29V DC +/- 2%
Imax a
400 milliamps
Imax b
2.3 Amps
Imin
0.065A
Battery type (Yuasa NP)
Two 12 Volt sealed lead acid (7Ah maximum)
Flame retardant UL94:V-0
See table 2 for capacities
Battery charge voltage
27.6VDC nominal (temperature compensated)
See table 3
Battery charge current
0.7A maximum
Battery lead fuse
20mm, 3.15A glass
Replace only with the same type
Battery high impedance warning
(Rimax)
1.35 ohms max
Low battery voltage indication
21V +/- 2%
Low battery shut off voltage
18.5V +/- 2%
Maximum current draw from batteries
3 Amps
With main power source disconnected
R0V output
Fused at with electronic fuse
Dedicated sounder outputs
24V Fused at 500mA with electronic fuse
1.6 Amp total load over
U
all
U
circuits
Zonal sounder outputs
24V Fused at 500mA with electronic fuse
1.6 Amp total load over
U
all
U
circuits
Fault relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Fire relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Local fire relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Zone quiescent current
1.6mA maximum
See table 4 for detector types
Terminal capacity
0.5mm2to 2.5mm2 solid or stranded wire
Number of detectors per zone
> 20
Dependent on type
Number of sounders per circuit
Dependent on type and current consumption
See table 6 for sounder types
Detection circuit end of line
6K8 5% ½ Watt resistor
Supplied in terminals
Sounder circuit end of line
10K 5% ¼ Watt resistor
Supplied in terminals
No. of detection circuits
(see table 2 for number of zones for each model)
Dependent on model
No. of sounder outputs
2 (plus one per zone on T models)
SIL, AL, FLT, RST inputs
Switched -ve, max resistance 100 Ohms
Zone normal threshold
8K ohm TO 1K ohm
Detector alarm threshold
999 ohms to 400 ohms
Call point alarm threshold
399 ohms to 100 ohms
Short circuit threshold
99 ohms to 0 ohms
Head removal condition
15.5 to 17.5 volts
Zener clamp detector base to be used
Cabling
FP200 or equivalent (maximum capacitance 1uF
maximum inductance 1 millihenry)
Metal cable glands must be used
Table 2 - Standby battery capacity required for fully loaded system
Panel model
24 hours
standby
48 hours standby
72 hours
standby
Standby current
Max panel alarm
current
K11020 (2 Zones)
3Ah
4.6Ah
6.2Ah
0.065
0.10A
K11040 (4 Zones)
3.3Ah
5.1Ah
6.9Ah
0.075
0.21A
K11080 (8 Zones)
3.75Ah
5.95Ah
8.2Ah
0.093A
0.55A
T11020 (2 Zones)
3Ah
4.6Ah
6.2Ah
0.065
0.15A
T11040 (4 Zones)
3.3Ah
5.1Ah
6.9Ah
0.075
0.30A
T11080 (8 Zones)
3.75Ah
5.95Ah
8.2Ah
0.093A
0.63A

Man-1078_Sigma_CP_22
Page 5 of 24
Table 3 - Battery charge voltage versus temperature
Temperature
0C
Battery charge voltage
0
29.2
10
28.56
20
27.99
30
27.55
40
27.13
Table 4 - Compatible detectors
Model
Type
Manufacturer
Maximum Number per zone
SLR-E
OPTICAL
Hochiki
32
SLR-E3N
OPTICAL
Hochiki
32
SIJ-E
IONISATION
Hochiki
32
DCD-1E
HEAT
Hochiki
32
DCD-2E
HEAT
Hochiki
32
DCD-1RE
HEAT
Hochiki
32
DFG-60E
HEAT
Hochiki
32
DFJ-60E
HEAT
Hochiki
32
DFJ90-E
HEAT
Hochiki
32
DCD-AE3
COMBINED HEAT
Hochiki
32
DCD-CE3
COMBINED HEAT
Hochiki
32
DFL-AE3
FIXED HEAT
Hochiki
32
DFJ-CE3
FIXED HEAT
Hochiki
32
SPC-ET
BEAM
Hochiki
6
SPB-ET
BEAM
Hochiki
8
SRA-ET
BEAM
Hochiki
5
55000-200/210 - SERIES 60
IONISATION
Apollo
32
55000-300 - SERIES 60
OPTICAL
Apollo
32
55000-100 - SERIES 60
HEAT
Apollo
32
55000-101 - SERIES 60
HEAT
Apollo
32
55000-102 - SERIES 60
HEAT
Apollo
32
55000-103 - SERIES 60
HEAT
Apollo
32
55000-104 - SERIES 60
HEAT
Apollo
32
55000-215 –
SERIES 65
IONISATION
Apollo
32
55000-216 -
SERIES 65
IONISATION
Apollo
32
55000-217 -
SERIES 65
IONISATION
Apollo
32
55000-218 -
SERIES 65
IONISATION
Apollo
32
55000-219 -
SERIES 65
IONISATION
Apollo
32
55000-220 -
SERIES 65
IONISATION
Apollo
32
55000-315 -
SERIES 65
OPTICAL
Apollo
32
55000-316 -
SERIES 65
OPTICAL
Apollo
32
55000-317 -
SERIES 65
OPTICAL
Apollo
32
55000-120 -
SERIES 65
HEAT
Apollo
32
55000-121 -
SERIES 65
HEAT
Apollo
32
55000-122 -
SERIES 65
HEAT
Apollo
32
53541-151 –SERIES 30
IONISATION
Apollo
32
53541-152 –SERIES 30
IONISATION
Apollo
32
53551-101 –SERIES 30
OPTICAL
Apollo
32
53531-221 –SERIES 30
HEAT
Apollo
28
53531-211 - SERIES 30
HEAT
Apollo
28
53531-212 - SERIES 30
HEAT
Apollo
28
53531-213 - SERIES 30
HEAT
Apollo
28
53531-214 - SERIES 30
HEAT
Apollo
28
AS100
OPT
Argus Vega
22
AS200
OPT/HEAT
Argus Vega
22
AS300
HIGH TEMP HEAT
Argus Vega
26
AS400
RATE OF RISE HEAT
Argus Vega
26
NID-58
IONISATION
Nittan
32
2KC/2KD
OPTICAL
Nittan
32
2SA-LS/2SA-70T-LS
HEAT
Nittan
32
TCA-70-LS
HEAT
Nittan
32
NFD-18-2/NFD-18-5
FLAME
Nittan
3
NID-48F
IONISATION
Nittan
32
NS-12-7
HEAT
Nittan
32
NC-9C-70T
HEAT
Nittan
32
ECO1002
HEAT/PHOTO
System Sensor
21
ECO1003
PHOTO
System Sensor
26
ECO1005
HEAT
System Sensor
22
ECO1005T
HEAT
System Sensor
22

Man-1078_Sigma_CP_22
Page 6 of 24
Although the current consumption of many detection devices would allow more than 32 to be connected to a
zone, this number should be limited to 32 to ensure that a short or open circuit on the wiring does not
prevent the indication of a fire alarm from more than 32 fire detectors and/or call points as required by
European standard EN54-2.
No more than 32 detectors and call points should be fitted to any one zone.

Man-1078_Sigma_CP_22
Page 7 of 24
Table 5 - Compatible detector bases and call points
Model
Type
Manufacturer
Comments
YBN-R/4
STANDARD
Hochiki
YBO-R/5
STANDARD WITH REMOTE LED
Hochiki
YBM-R/6
STANDARD BASE
Hochiki
YBN-R/4SK
DIODE BASE
Hochiki
Must be used with LCMU*
YBO-R/5SK
DIODE BASE WITH REMOTE LED
Hochiki
Must be used with LCMU*
YBO-R/6SK
DIODE BASE
Hochiki
YBO-R/5PA
SAVWIRE
Hochiki
Only with T series panels
YBO-R/6PA
SAVWIRE
Hochiki
Only with T series panels
ECO1000R
STANDARD
System Sensor
ECO1000BRSD
DIODE BASE
System Sensor
Must be used with LCMU*
45681-200
STANDARD BASE
Apollo
45681-201
DIODE BASE
Apollo
Must be used with LCMU*
45681-206
SAVWIRE BASE
Apollo
Only with T Series Panels
AUBDR100-470
470R RESISTOR + DIODE
Argus Vega
Must be used with LCMU*
AUBSR100-470
470R RESISTOR
Argus Vega
MCP1BR
470R RESISTOR + DIODE
KAC
For 2-wire systems
WR2012
470 + 680 OHM CALL POINT
KAC
Use with both resistors intact for
call point discrimination
MCP1AR
470R
KC
For standard, 4-wire systems
CX
470 OHM CALL POINT
Fulleon
NCP-T
CALL POINT
Nittan
ELECTRONICS FREE BASES
ALL
Note: LCMU (Line Continuity Monitoring Device) part number K1406 allows call points mounted
downline of detectors that have been removed from diode bases to continue to operate.
*LCMU units are not compatible with 2 wire “T” series Sigma CP Panels.
Table 6 - Compatible sounders
Model
Type
Manufacturer
Comments
BANSHEE
ELECTRONIC
VIMPEX
WAFER
ELECTRONIC
VIMPEX
FIRECRYER RANGE
ELECTRONIC VOICE
VIMPEX
KOBELL
MOTORISED
VIMPEX
ASKARI
ELECTRONIC
FULLEON
Standard polarised type only
ROSHNI
ELECTRONIC
FULLEON
Standard polarised type only
SQUASHNI
ELECTRONIC
FULLEON
Standard polarised type only
SYMPHONI
ELECTRONIC
FULLEON
Standard polarised type only
ELECTRONIC BELL
ELECTRONIC
FULLEON
Standard polarised type only
CFB BELLS
MOTORISED
FULLEON
Standard polarised type only
B6 AND B8 BELLS
SOLENOID
FULLEON
Standard polarised type only
Table 7 - Compatible I.S. barriers
Model
Type
Manufac
turer
MTL5561
DETECTION ZONE GALVANIC ISOLATOR
MTL
MTL7778ac
SOUNDER CIRCUITS SI AND S2 ONLY
MTL
Note: Use galvanic isolator with Hochiki or Apollo detectors only.

Man-1078_Sigma_CP_22
Page 8 of 24
3B4. Using intrinsically safe barriers
SIGMA CP control panels support the use of I.S. barriers for connecting to equipment in hazardous areas.
Only certified detectors, call points and sounders may be used in hazardous areas and these
must be connected to the control panel via a compatible I.S. barrier as listed in table 7.
Connection of the I.S. barrier changes the characteristics of the detection circuit so zones that have I.S.
barriers connected must be adjusted to work with them.
Programmable options C61 to C68 allow each zone to operate with I.S. barriers.
The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval
system diagram which should be supplied by the detector manufacturer. The power rating of the end of line
resistor will be dependent upon the Zone classification rating (Gas class) this will be specified on the system
diagram.
Figure 1. Detection zone wiring through an MTL5561 I.S .barrier
+
-
SOUNDER
OUTPUT
I.S.
POLARISED
SOUNDER
10K END OF LINE RESISTOR
MTL7778ac
MAXIMUM OF TWO SOUNDERS PER SOUNDER CIRCUIT
I.S.
EARTH
POWER WILL DEPEND UPON
I.S. ZONE CLASSIFICATION
HAZARDOUS AREASAFE AREA
+
IN +
OUT
-
IN -
OUT
I.S.
POLARISED
SOUNDER
+
IN +
OUT
-
IN -
OUT
Figure 2. Sounder circuit wiring through an MTL7778ac I.S. barrier
+
-
ZONE
+
IN +
OUT
-
IN -
OUT
I.S. DETECTOR
I.S.CALL POINT
MTL5561 6K8 END OF
LINE RESISTOR
+
-
+
-
SAFE AREA HAZARDOUS AREA
POWER RATING WILL
DEPEND UPON I.S. ZONE
CLASSIFICATION
NOTE: Active End of
Line Devices (LCMU)
must not be used in
the Hazardous Area
MAXIMUM NUMBER OF DEVICES ON ZONE
SPECIFIED IN SYSTEM DIAGRAM

Man-1078_Sigma_CP_22
Page 9 of 24
4B5. Control panel fascia
In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment,
LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes
to configure the control panel to suit the requirements of the installation.
Removing the fascia
Before the fascia can be removed it will be necessary to unplug the three way terminal block on the left
hand side of the PCB.
The fascia of the control panel is held in place by countersunk screws. Undo the two screws and lift the
fascia gently away from the box towards you.
With the fascia removed there is much more room inside the panel for making off and dressing cables.
When cabling work is complete the fascia can be re-fitted with the two countersunk screws and the red,
green/yellow and black wires re-connected to the three way terminal block.
It is most important that the polarity of the red and black wires is observed as wrong
connection of these will damage the control panel.

Man-1078_Sigma_CP_22
Page 10 of 24
5B6. Connecting to the circuit board
All connections for field wiring are to a single row of terminals along the top of the circuit board.
The connections for the power cables are to a pluggable terminal block which may be pulled off of the board
to remove the plate/PCB assembly. Remove this pluggable terminal only with mains power off.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the
panel.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded
securely to the enclosure via a metal gland.
Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily
to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.
Terminals are capable of accepting wires of up to 2.5mm2.
AUX
24V R0V SIL AL FLT RST
RS485 S1 ZONE
1LOCAL
FIRE
+ - FAULT
RLY FIRE
RLY
+-S2
+-+-ZONE
2
+-ZONE
3
+-ZONE
4
+-ZONE
5
+-ZONE
6
+-ZONE
7
+-ZONE
8
+-NC CNO NC CNO NC CNO
REMOTE CONTROL
Terminal designations
Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.
If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and
well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne
in mind when considering cable entries.
6B7. Software revision number
New features may be added to Sigma CP fire control panels from
time to time and when this is done the operating software of the
unit is updated. The software revision can be located on the main
processor by removing the plate holding the PCB from the
enclosure and turning it over. The software version will have a
number such as “Sig27.hex” and it is this number which will
determine which features the panel has installed and its
compatibility with Sigma CP ancillary board, sounders boards,
repeaters etc.
CORRECT
INCORRECT INCORRECT
SW1
SW2
SW4SERIAL NUMBER
++++
+
+
+
+
+
D1008 ISSUE06
C1
R1
R2
R3
R5R6
R7
R8
R9
C30
C31
R11
R12
R13
R14
R15
R17R18
R19
R21
R51
R52R53
R54
R55
R56
R57
R58
R60
R61
R62
R63
R64
R65
R66
R67R69
R71
R72
R73
R74
R78
R80
R81
R85
R86
R87
R88
R90
R98R99
R102
R103
R104
R109
R110
R111
R112
C2C3C4C5C7
C19
C20C21C22C23
C27
C37
C38
C39C40
C43
C44
C55
C60 C61
R113
R114
R116
R117
C96
C33
R128
C73C74
C75
C76
C34
C35 C36
R130
R131
R132
R133
R134
R135
R137
R129
C42
C41
R89
R107
C81
R126
C83
C94
C95
R118
R4A
R4B
R4C
R4D
R4E
R4F
R10A
R10B
R10C
R10D
R10E
R10F
R16A
R16B
R16C
R16D
R16E
R16F
R22A
C92
C93C97
C98
C99
C100
C101
C102
C103
R155
R156
R157
C104
C105
R158
C106 C107
C108
C109
D1D2D3
D4
D9
D10
D11
D12
D13
D14
D15
D16
D22
D23
Z11
Z14
D30
F1
F2
F4
F9
F10
F11
TR1
TR2
TR3
TR9
TR26
TR19
TR24
TR28TR25
IC4
IC5
IC10
IC1
IC2
D32D33D34
D35
IC6
REG1
J1
C24
C25
C65C66C67C68
C56
C82
D41
D20
F12
C51
RL2
RL3 RL1 RL9
RL10
XTL1
LED3LED4LED5 LED6 LED7LED17 LED35
VR1
TH1
TR23
L1
T3
REG3
FB5
FB6
FB7
FB8
FB1
FB2
FB3
FB4
FB9
FB10
R70
R75
R76
X2X1
C45
VDR4VDR3
VDR2
VDR1FB20FB21
C128C127
LED8LED11LED15LED12LED10
LED16
LED34
LED9
LED13
LED14
C6
F3
R168
TR47
R167
R166
Sig27.hex
Jason
SOFTWARE VERSION LABEL

Man-1078_Sigma_CP_22
Page 11 of 24
+
-
ZONE
+
IN +
OUT
-
IN -
OUT
DETECTOR
CALL POINT
6K8 END OF
LINE RESISTOR
+
-
ZONE
+
IN +
OUT
-
IN -
OUT
DETECTOR
CALL POINT
6K8 END OF
LINE RESISTOR
POLARISED
SOUNDER
IN OUT
+
IN +
OUT
_ _
NOTE: SOUNDER WIRED IN
REVERSE POLARITY
USE ONLY SA-WIRE BASES
ON “T” SERIES PANELS
Figure 4.–K Series detection zone wiring
Figure 5.- T series detection zone wiring
7B8. Detection zone wiring
The detection zones provide a nominal 24V DC to power conventional detectors and call points as listed in
the compatibility tables on pages 6 and 7.
The wiring is monitored for open and short circuit fault conditions by removing the 6K8 end of line
monitoring resistors that are supplied fitted to the control panels’ terminals and placing them across the last
device that is wired to the zone circuit.
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
On T series panels, polarised sounders must also be wired across the detection zone but in reverse polarity
to that shown by the zone terminals (see figure 5 below). At least one sounder should be fitted to each
detection zone. Each zone can be configured individually as a 2-wire type zone or a non 2-wire type zone
using configuration options C1 to C8.
For non 2-wire systems that are required to comply with BS5839 Part 1: 2002 detector removal
requirements, detector bases fitted with a Schottky diode should be used and the end of line resistor
replaced with an LCMU active end of line monitoring device.

Man-1078_Sigma_CP_22
Page 12 of 24
8B9. Sounder circuit wiring
Whether using standard or T series control panels, all sounders must be of the polarised type. If non-
polarised sounders are used the control panel will permanently show a fault condition. See table 6 on page 7
for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring
resistor across the last device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41 Amps on any one
circuit.
9B10. Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. Operation of
these inputs must be restricted by an access level 2 control as defined in EN54-2 These are
abbreviated at the terminals block as follows:
a) Remote 0 V supply - ROV
b) Silence Alarm –SIL
c) Sound Alarm –AL
d) Fault –FLT
e) Reset –RST
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open
switch or contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
ROV SIL AL FLT RST
TOTAL RESISTANCE LESS THAN100 OHMS
SILENCE ALARM SWITCH
SOUND ALARM SWITCH
Figure7- Example connections to remote control inputs
+-
S1
Figure6.- Sounder circuit wiring
10K end of line
resistor
POLARISED
SOUNDER
IN OUT
+
IN
+
OUT
_ _
POLARISED
SOUNDER
IN OUT
+
IN
+
OUT
_ _

Man-1078_Sigma_CP_22
Page 13 of 24
10B11. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door
release controllers.
The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative
terminal and is the same terminal that should be used to switch the remote control terminals.
It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt
free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another
system for example to give an alert. See programming code 24.
The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the
event of a wiring fault.
Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times
as standby time will be significantly affected by even modest standing loads. It is recommended that the
Aux24V output is not used to power standing loads and not used to supply loads of greater than 300
milliamps
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is
imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the
generation of high voltage transients back to the control panels power supply.
The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply
should be used for these.
11B12. Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts
are rated for switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should
not be exceeded under any circumstances.
Fault relay
The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.
Local fire relay
The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the
sound alarm button on the front panel. The relay will remain activated until the alarm is silenced or the
panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is
triggered on a zone that is in test mode.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain
activated until the control panel is reset. This relay will
NOT
operate upon activation of the remote AL input.
Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.
12B13. Connection to Repeater panels
Repeater panels connect via a 2 core cable to the terminals marked RS485 + and –on the Sigma CP main
control panel PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming
cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to
the cable must have the jumper links J2 removed.
Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.
Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set
the Write Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a
few seconds and the main panel will show the addresses of the repeaters that were found on the display for
instance r1 indicates that a repeater at address 1 has been found.
Turn the write enable switch of, then on again and then press the ENTER button to accept each repeater
that has been found. When all repeaters have been added, set the main panel Write Enable switch to off.
Press the Watchdog reset switch on the main panel.
All repeaters are now configured and the main control panel will report a fault if any repeaters that have
been accepted become faulty or go off line.
For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and
maintenance manual.
Please note that repeaters can only be fitted to panels containing boards labeled
S4XXA or above. They will not work with panels containing boards without an alpha
suffix.

Man-1078_Sigma_CP_22
Page 14 of 24
For panels with software version Sigma242.hex or below, the Enable controls keyswitch and Write Enable
switch must both be set to off.
13B14. Connection to Ancillary boards
Ancillary boards connect via a 2 core cable to the terminals marked RS485 + and –on the Sigma CP main
control panel PCB. Up to 7 Ancillary boards may be connected and each board has terminals for the
incoming cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel
connected to the cable must have the jumper links J2 removed.
Set the ancillary board address using the DIP switch (SW2); ensure no two ancillary boards share the same
address.
Apply power to main panel and all ancillary boards then turn on the enable keyswitch and set the write
enable slide switch to on, briefly press the PROCESSOR RESET button on the main panel, wait for a few
seconds and the main panel will show the addresses of the ancillary boards that were found on the display
for instance o1 indicates that an ancillary board at address 1 has been found.
Press the ENTER button to accept each ancillary board that has been found.
The control panel will report a fault if any ancillary boards that have been accepted
become faulty or go off line.
For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation
and maintenance manual.
Please note that Ancillary boards can only be fitted to panels containing boards
labelled S4XXA or above. They will not work with panels containing boards without
an alpha suffix.
14B15. Connection to 8 way Sounder boards
Sounder boards connect via a 2 core cable to the terminals marked RS485 + and –on the Sigma CP main
control panel PCB. Up to 7 Sounder boards may be connected and each board has terminals for the
incoming cables and outgoing cables. All except the last Ancillary board, Sounder board or Repeater
connected to the cable must have the jumper links J2 removed. Sounder boards must be powered from a
separate power supply which is suitably rated to supply the full sounder load that is connected. This can be
up to 4 Amps if all circuits are fully loaded.
Set the Sounder board address using the DIP switch (SW2); ensure no two Sounder boards share the same
address.
Apply power to main panel and all Sounder boards then turn on the enable keyswitch and set the write
enable slide switch to on, briefly press the PROCESSOR RESET button on the main panel, wait for a few
seconds and the main panel will show the addresses of the sounder boards that were found on the display
for instance b1 indicates that a sounder board at address 1 has been found.
Press the ENTER button to accept each Sounder board that has been found.
The control panel will report a sounder fault if any Sounder boards that have been
accepted become faulty, have cable faults on their outputs or go off line.
For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation
and maintenance manual.
Please note that Sounder boards can only be fitted to panels containing software
SIGMA242.HEX or later.

Man-1078_Sigma_CP_22
Page 15 of 24
15B16. Panel operation
24B16.1 Normal condition
Under normal conditions, control panels will have only the green,
Power On
LED lit.
25B16.2 Fire condition
Upon receipt of a fire condition by activation of a detector or call point, the
Common Fire
indicator will light
and the zonal
Fire
indicators will flash at around 2Hz.
The fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected
by configuration options 10 to 12 (see table 8).
26B16.3 Silence/sound alarms
The
Silence/Sound alarm
button can only be operated at access level two which means that the
Enable
Control
key must be inserted.
To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.
Pressing the
Silence/Sound alarm
whilst the control panel is in this silenced condition, will cause the
sounders to operate again.
The sounders can be toggled on and off with the
Silence/Sound alarm
button as required.
27B16.4 Reset
To reset the panel, insert the Enable key then press the Reset button.
28B16.5 Zone fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the
Fault
LED and
Zone
Fault
LEDs to light indicating the zone in which the fault has occurred.
29B16.6 Sounder fault
A fault on the wiring to sounder circuits will cause the
Fau
lt and
Sounder Fault
LEDs to light indicating a fault
on the wiring to the sounder circuits.
30B16.7 Power fault
Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit
will cause the
Fault
and
Power Fault
LEDs to light indicating an abnormality in the power supply to the
control panel.
31B16.8 System fault
The
System Fault
LED will light if the configuration memory has not been set or has become corrupt.
32B16.9 Lamp test
All LED indicators can be tested at any time by pressing the
Lamp Test
button. The
Enable Control
key does
not need to be inserted to test the indicators.
The buzzer can be silenced at any time by pressing the
Buzzer Silence
button. The enable key does not need
to be inserted to silence the buzzer.
33B16.10 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building
which may cause the fire alarm system to operate in error.
34B16.10.1 Disable zones
To disable zones, the
Enable Control
key should be inserted and the mode button pressed until “d” appears
in the first of the two seven segment LED displays. The
Select
button should then be pressed to select the
number of the zone which is to be disabled in the second of the two seven segment displays. Once the
desired zone is displayed, the enter button should be pressed to confirm the disablement.
The
Disable
LED will light and the
Zone Fault
LED will light for each disabled zone.
A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8).
If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the
control panel into the fire condition.
The panel should be Reset before enabling any zone with a flashing “dx.” Indication

Man-1078_Sigma_CP_22
Page 16 of 24
Note: The flashing “dx” indicator will only appear on panels with software version sigma_CP 214.hex and
higher produced after July 2012.
35B16.10.2 Disable sounders
To disable sounder outputs, press the mode button to select “db” on the seven segment display. Pressing
enter will disable all sounders and cause the
Disable
and
Sounder Fault
LEDs to light.
36B16.10.3 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears
on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will
have their alarm outputs delayed by the time set in configuration options 00 to 09.
37B16.10.4 Disable fault contact
The fault relay can be disabled by selecting configuration option 22.
38B16.11 Test mode
Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP
range of panels enable the system to be tested single handed by using a test mode. When in test mode,
activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to
the control panel to reset after every activation.
Test mode is entered in a similar way to disablements. With the
Enable Control
key inserted, press the
Mode
button until “t” appears in the first of the seven segment displays. Then press the
Select
button until the
required zone number appears. Pressing the
Enter
button will cause the
Test
and
Zone Fault
LEDs to
illuminate indicating the zones which are in test mode.
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db"
function (for example) toggles between sounders disabled and sounders enabled.
16B17. Configuration options
The Sigma CP range of control panels has many configuration options which can be set at the time of
commissioning to suit the requirements of the installation. These options are normally set once and will
rarely need to change. The configuration options are only available at access level 3. To access level 3,
CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) to the right
position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three
times every few seconds as an indication that it is at this access level.
Configuration options are simple to enter using the codes in table 8 below. When the control panel is at
access level 3, the sub-text of the
Mode
and
Select
buttons is used to enter a number using tens (+10) and
units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units,
seven segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1
to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
Figure 8 –Access level 3 (Write enable) enable switch location
WRITE ENABLE SWITCH

Man-1078_Sigma_CP_22
Page 17 of 24
Table 8 –Configuration codes
CODE
FUNCTION
COMMENTS
00
SOUNDER DELAY TIME = 30 SECONDS
Sets the time delay before sounders operate in combination with
configuration codes 31 to 48 and access level 2 function AD.
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
10
COMMON ALARM MODE (default)
All sounders operate upon any fire condition
11
TWO-STAGE ALARM MODE
Continuous sounders in activated zone, pulsing elsewhere
12
ZONED ALARM MODE
Only sounders connected to zone in alarm operate
21*
DISABLE FIRE BUZZER
Buzzer will not operate on fire condition
22*
DISABLE FAULT OUTPUT
Fault relay will not operate except upon total power failure
23
DISABLE EARTH FAULT MONITORING
Connection of fire alarm wiring will not announce a fault
24
PULSED REMOTE CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
Set as default if panel is two wire “T” series (detectors and call
points on same cables)
26
DISABLE FIRE OUTPUT
Fire relay will not operate upon any alarm
27
REMOVE AUX 24 UPON PANEL RESET
24V supply switches off for about 5 seconds when panel is reset
28
INDICATE CALL POINT ACTIVATION
Activation of a call point with a 270R resistance fitted is
indicated by a flashing zone indicator and “Pu” on the 7
segment display. Activation of a detector will be indicated by a
steady zone indicator and nothing on the 7 segment display.
29
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
Silenced sounders will not re-sound upon further zone
activations
2A
TREAT CALL POINT ALARM AS DETECTOR ALARM
When this option is active, the panel does not distinguish
between detector alarms and call point alarms (v215 onward)
31
ZONE 1 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Access level 2 function Ad must be set for this to take
effect.
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note access level 2 function Ad must be set for this to take
effect.
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3 ALARM FROM CALL POINT DELAYED
44
ZONE 4 ALARM FROM CALL POINT DELAYED
45
ZONE 5 ALARM FROM CALL POINT DELAYED
46
ZONE 6 ALARM FROM CALL POINT DELAYED
47
ZONE 7 ALARM FROM CALL POINT DELAYED
48
ZONE 8 ALARM FROM CALL POINT DELAYED
51
COINCIDENCE ZONE 1
Zone contributes to ancillary board coincidence O/P. Any
number of zones can be selected to contribute.
52
COINCIDENCE ZONE 2
53
COINCIDENCE ZONE 3
54
COINCIDENCE ZONE 4
55
COINCIDENCE ZONE 5
56
COINCIDENCE ZONE 6
57
COINCIDENCE ZONE 7
58
COINCIDENCE ZONE 8
DOT
FLASHING NO DOT
ZONE 1 I.S. BARRIER
OPTION SET ZONE 1 I.S. BARRIER
OPTION NOT SET
Figure 9 –Example display showing option set and not set.

Man-1078_Sigma_CP_22
Page 18 of 24
61
CONFIGURE Z1 FOR I.S BARRIER
Detection threshold changed for use with IS barrier
62
CONFIGURE Z2 FOR I.S BARRIER
63
CONFIGURE Z3 FOR I.S BARRIER
64
CONFIGURE Z4 FOR I.S BARRIER
65
CONFIGURE Z5 FOR I.S BARRIER
66
CONFIGURE Z6 FOR I.S BARRIER
67
CONFIGURE Z7 FOR I.S BARRIER
68
CONFIGURE Z8 FOR I.S BARRIER
CODE
FUNCTION
COMMENTS
71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the
zone so that the control panel can be
used on older systems that had no short
circuit monitoring.
72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
74*
ZONE 4 SHORT CIRCUIT INDICATES ALARM
75*
ZONE 5 SHORT CIRCUIT INDICATES ALARM
76*
ZONE 6 SHORT CIRCUIT INDICATES ALARM
77*
ZONE 7 SHORT CIRCUIT INDICATES ALARM
78*
ZONE 8 SHORT CIRCUIT INDICATES ALARM
81*
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset itself when
sounders are operating
82*
ZONE 2 NON-LATCHING
83*
ZONE 3 NON-LATCHING
84*
ZONE 4 NON-LATCHING
85*
ZONE 5 NON-LATCHING
86*
ZONE 6 NON-LATCHING
87*
ZONE 7 NON-LATCHING
88*
ZONE 8 NON-LATCHING
91
ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs.
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
A1*
ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously
before an alarm is generated.
A2*
ZONE 2 ANY ALARM DELAYED
A3*
ZONE 3 ANY ALARM DELAYED
A4*
ZONE 4 ANY ALARM DELAYED
A5*
ZONE 5 ANY ALARM DELAYED
A6*
ZONE 6 ANY ALARM DELAYED
A7*
ZONE 7 ANY ALARM DELAYED
A8*
ZONE 8 ANY ALARM DELAYED
C1
ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders.
On 2 wire “T” series panels this enables individual zones to be
configured for use with conventional (non 2-wire) detector
bases.
SOFTWARE VERSIONS SIGMA242.HEX and above only
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4
ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8 SOUNDERS INHIBITED
E1*
ZONE 1 WILL NOT OPERTATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching
function to prevent ring around on interconnected panels.
SOFTWARE VERSIONS SIGMA242.HEX and above only
E2*
ZONE 2 WILL NOT OPERTATE FIRE RELAY
E3*
ZONE 3 WILL NOT OPERTATE FIRE RELAY
E4*
ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5*
ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6*
ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7*
ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8*
ZONE 8 WILL NOT OPERTATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with EN54-2

Man-1078_Sigma_CP_22
Page 19 of 24
Once the required configuration options have been set, the Write enable switch must be returned to its
normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned
off.
17B18. Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will
attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate
these events.
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front
panel, the CPU fault LED inside the panel.
This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control
panel. The control panel buzzer can not be silenced and will continue to sound until the watchdog activation
is reset.
1819. Processor reset switch
Once started, the microprocessor controlling the panel should continue to run continuously without
interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET
button on the PCB inside the control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving
abnormally. The system should resume normal operation within a couple of seconds of pressing the
processor reset button.
19B20. Internal indications –troubleshooting
To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of
internal indicators are visible with the front cover removed as follows:
39B20.1 Mains fail
Indicates that the 230V AC supply is not present and the system is running on standby batteries.
If there is not a power cut, check the panels mains fuse.
40B20.2 Batt fail
Indicates that the standby battery has become disconnected or that the charging circuit of the control panel
has a high resistance or has failed. Check that both batteries are connected and linked together. Test
battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads.
41B20.3 CPU fault
Indicates that the central processor unit has failed to correctly execute code and has been re-started by the
system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition.
Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs
the circuit board replacing. (See maintenance section).
42B20.4 Aux 24V fault
The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary
equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output
has been exceeded. The fuse is a self resetting type and the supply will resume when the fault condition is
removed.
43B20.5 Batt low
Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the
minimum battery voltage).
44B20.6 Earth fault
Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect
cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on.

Man-1078_Sigma_CP_22
Page 20 of 24
45B20.7 Sys fuse fault
Indicates that the total power rating of the power supply has been exceeded and that the system fuse has
come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips
fuse to identify troublesome circuit.
46B20.8 S1 fault and S2 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check
sounder circuit wiring.
47B20.9 Comms fault
Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault
at all repeaters and ancillary boards to identify the source of the problem.
20B
This manual suits for next models
1
Table of contents
Other Kentec Electronics Control Panel manuals

Kentec Electronics
Kentec Electronics Syncro ASM User manual

Kentec Electronics
Kentec Electronics Solo 2 Lite Guide

Kentec Electronics
Kentec Electronics Sigma ZXT User manual

Kentec Electronics
Kentec Electronics Sigma ZXT SI User manual

Kentec Electronics
Kentec Electronics Sigma ZXT User manual

Kentec Electronics
Kentec Electronics Syncro User manual

Kentec Electronics
Kentec Electronics Syncro View Marine User manual

Kentec Electronics
Kentec Electronics Taktis User manual

Kentec Electronics
Kentec Electronics Taktis User manual

Kentec Electronics
Kentec Electronics Sigma ZXT User manual