Man-1134 Sigma XT+_ECP_02 Page 4 of 5
2.6 Disable Extract output
To disable Extract relay output, press the UP button on the module while at access level 2 until the display shows:
DISABLE
extract output ? Press the Enter button to select this function. The display will show:
ENABLE
extract OUTPUT ? The yellow disabled LED on the module that has been disabled will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Extract relay output repeat the procedure above.
2.7 Turn on Extract output
To turn on the extract relay output, press the DOWN button on the module while at access level 2 until the display shows:
TURN ON
EXTRACT OUTPUT Press the Enter button to select this function. The display will show:
TURN OFF
EXTraCT OUTPUT ? The yellow disabled LED on the module that has been disabled will be lit.
Turn the Enable keyswitch off to leave the Extract output active. To turn off the Extract output, repeat the procedure above.
Note: the extract output does not turn off when the module is reset.
2.8 Reset
To reset the ECU, insert the Enable key, turn to the right then press the Reset button.
The unit will reset only after the Reset Inhibit timer has expired once the activated condition has been established.
2.9 Sounder fault
A fault on either of the sounder circuits will light the Fault LED and the ECU will display:
stage 1 alarms
fault
or
stage 2 alarms
fault
2.10 Power fault
Failure of the mains power or disconnection of the standby battery will cause the Fault LED to light and the display will show:
POWER SUPPLY
FAULT
2.11 System fault
The System Fault and general fault LEDs will light if the configuration memory has not been set or has become corrupted
2.12 Lamp test
Indicators can be lamp tested by holding down the EXIT button for more than 2 seconds.
2.13 Hold condition
Activation of the Hold input on the ECU or at a remotely mounted status unit will cause the Hold Activated indicator to light on
the ECU and on any status units or ancillary boards connected to it.
If the ECU is in the Activated condition and the pre-release timer is running then the Extinguishant release sequence will be
halted and the pulsing, 2nd stage sounders shall change to 1 second on, 2 seconds off.
Release of the Hold input shall re-start the pre-release timer from maximum.
2.14 Turn on Extract output
To turn on the extract relay output, press the DOWN button on the module while at access level 2 until the display shows:
TURN ON
EXTRACT OUTPUT Press the Enter button to select this function. The display will show:
TURN OFF
EXTRACT OUTPUT ? The yellow disabled LED on the module that has been disabled will be lit.
Turn the Enable key switch off to leave the Extract output active. To turn off the Extract output, repeat the procedure above.
Note:theextractoutputdoesnotturnoffwhenthemoduleisreset.
2.15 Released condition
The released pressure switch input will be connected to a pressure switch mounted on the Extinguishant cylinder which operates
when the Extinguishant has been released. This will activate the released indicator on the ECU.
If the Extinguishant has been released by mechanical means i.e. the ECU is not in the activated condition, operation of the
released pressure switch input will establish the Released condition.
2.16 Low pressure switch
The low pressure switch input will be connected to a pressure switch on the Extinguishant cylinder which will operate if the
pressure in the cylinder falls below a set point. This will happen after the Extinguishant has been released but may happen
before release through a leak. The fault LED on the ECU and on the detection part will light and the buzzer will sound when this
input is operated.