Kidde GSA-UM Assembly instructions

© 2017 United Technologies Corporation 1 / 7 P/N P-047550-1816-EN • REV 007 • ISS 21SEP17
GSA-UM Universal Class A/B Module Installation
Sheet
The GSA-UM Universal Class A/B Module is an addressable
module that you can configure to provide one of the following:
•Two Class B dry contact initiating device circuits
•One Class A dry contact initiating device circuit
•One Class A or Class B notification appliance circuit
•One Class A or Class B verified two-wire (conventional)
smoke detector circuit without dry contact initiating devices
on the same circuit
•One Class A or Class B unverified two-wire (conventional)
smoke detector circuit with or without dry contact initiating
devices on the same circuit
•One Form C dry contact relay output
The GSA-UM requires two device addresses on the signaling
line circuit (SLC). Addresses are assigned electronically. There
are no addressing switches.
Diagnostic LEDs provide visible indication of the status of the
module:
•Normal: Green LED flashes
•Alarm/active: Red LED flashes
Personality codes
The module requires the loop controller to download the
personality code that determines how the module operates.
Use the personality codes described below to configure the
GSA-UM. Refer to Table 1 for UL 864 programming
requirements. See
Table 2 for personality code electrical characteristics.
Table 1: UL 864 programming requirements
This product incorporates field-programmable software. In order for the
product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain
programming features or options must be limited to specific values or
not used at all as indicated below
Program feature or
option
Permitted in
UL 864?
Possible
settings
Settings
permitted in
UL 864?
Personality code 2
No
N/A
N/A
Personality code 10
No
N/A
N/A
Personality code 1: Alarm - NO latching (Class B): Factory
default. Configures input 1 or 2 for Class B, normally open dry
contact initiating devices (e.g., pull stations, heat detectors,
etc.). When the NO input contact of an initiating device is
closed, an alarm signal is sent to the loop controller and the
alarm condition is latched at the module.
Personality code 2: Alarm - NO delayed latching (Class B):
Same as code 1 except that contact closure must be
maintained for approximately 16 seconds before an alarm
signal is sent. This code is only for use with nonretarded
waterflow alarm switches.
Personality code 3: Active - NO nonlatching (Class B):
Contact closure causes an active instead of an alarm status
and does not latch at the module. Code 3 is typically used for
monitoring fans, dampers, and doors.
Personality code 4: Active - NO latching (Class B): Contact
closure causes an active instead of an alarm status, which is
latched at the module. Code 4 is typically used for monitoring
supervisory and tamper switches.
Personality code 8: Signal - dry contact output: Configures
the module as a Form C dry relay contact to control external
appliances (door closers, fans, dampers) or equipment
shutdown. Note: Jumper JP1 must be moved to pins 2 and 3
for dry contact operation.
Personality code 9: Alarm - NO latching (Class A): Configures
the module for connection of Class A, normally open dry
contact initiating devices (e.g., pull stations, heat detectors,
etc.). When the NO input contact of an initiating device is
closed, an alarm signal is sent to the loop controller and the
alarm condition is latched at the module.

2 / 7 P/N P-047550-1816-EN • REV 007 • ISS 21SEP17
Personality Code 10: Alarm - NO delayed latching (Class A):
Same as code 9 except that contact closure must be
maintained for approximately 16 seconds before an alarm
signal is sent. Code 10 is typically used with waterflow alarm
switches.
Personality code 11: Active - NO nonlatching (Class A):
Same as code 9 except that contact closure causes an active
instead of an alarm status, and does not latch at the module.
Personality code 11 is typically used for monitoring fans,
dampers, and doors.
Personality code 12: Active - NO latching (Class A): Same as
code 9 except that contact closure causes an active instead of
an alarm status, which is latched at the module. Code 12 is
typically used for monitoring supervisory and tamper switches.
Personality code 13: Alarm - two-wire smoke unverified
(Class B): Configures the module for monitoring two-wire
conventional smoke detectors (that do not require alarm
verification) and normally open contact initiating devices (e.g.,
pull stations, heat detectors, etc.) on the same circuit.
Personality code 14: Alarm - two-wire smoke verified
(Class B): Configures the module for monitoring two-wire
conventional smoke detectors (that require alarm verification).
Normally open contact initiating devices may not be mixed with
two-wire conventional smoke detectors.
Personality code 15: Signal - supervised output (Class A):
Configures the module for connection of a Class A output
notification appliance circuit (NAC). Code 15 is typically used
to control bells, speakers, etc.
Personality code 16: Signal - supervised output (Class B):
Configures the module for connection of a Class B output
notification appliance circuit (NAC). Code 16 is typically used
to control bells, speakers, etc.
Personality code 20: Alarm - two-wire smoke unverified
(Class A): Same as personality code 13, except that wiring is
Class A.
Personality code 21: Alarm - two-wire smoke verified
(Class A): Same as personality code 14, except that wiring is
Class A.
For personality codes 13, 14, 20 and 21
First SIGA-UM on a loop to go into alarm will maintain the 2
wire detector circuit voltage and current so that the 2 wire
detector can maintain its LED. Second SIGA-UM on the same
loop to get an alarm from a 2 wire detector will indicate the
alarm at the control panel but will reduce voltage and current
on its 2 wire circuit causing the detector LED to turn on and off.
Installation
WARNINGS
•Connecting a device that exceeds this module’s pilot duty
contact ratings may cause activation failure. This module
does not support capacitive loads. See “Specifications” on
page 6 for contact ratings.
•The personality code for this device is factory set to 0.
This module will not operate until it is assigned a
personality code of 1, 2, 3, 4, 8, 9, 10, 11, 12, 13, 14, 15,
16, 20, or 21.
•Electrocution hazard. Dangerous voltages may be present
at the module terminals even when power is shut off.
Notes
•The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
•This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
•This module does not support conventional four-wire
smoke detectors.
Install in accordance with all applicable local codes and
standards and the local authority having jurisdiction.
To install the module:
1. Wire in accordance with “Wiring” on page 3.
2. Write the address assigned to the module on the label
provided and apply the label to the module. Remove the
serial number label from the detector and attach it to the
project documentation.
3. Using the screw provided, mount the wall plate to the
module. See Figure 1 on page 3 for mounting details.
4. Using the screws provided, mount the wall plate (with the
module attached) to one of the compatible electrical boxes
listed in “Specifications” on page 6.

P/N P-047550-1816-EN • REV 007 • ISS 21SEP17 3 / 7
Figure 1: Mounting the UM
(1) (2)
(3)
(4)
(5)
(6)
(1) Compatible electrical box
(2) Gang ring cover (if required)
(3) GSA-UM module
(4) Wall plate, white (dual-gang)
(5) #6-32 × 5/8 machine screw
(6) #4 × 1/2 self-tapping screw
Protection from transient spikes
For installations in which the output circuit connects to
electromechanical bells or horns, install a bipolar transient
protector (P/N 235196P) to prevent damage to the module
from transient spikes caused by switching inductive loads.
Locate all bells and horns at least 6 ft. (1.8 m) from the
module.
To install a transient protector:
1. Install the transient protector inside the module’s electrical
box. See Figure 2 below for wiring details.
Figure 2: Bell circuit showing bipolar transient protector
placement
12 11
(1) (2)
(1) Normal state
(2) Active state
Wiring
Wire in accordance with applicable requirements of the latest
editions of the local codes and standards and the local
authority having jurisdiction.
Note: When stripping wire ends, exposing more wire may
cause a ground fault; exposing less wire may result in a faulty
connection.
Strip 1/4 in. (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
General wiring notes
•Refer to the Signature loop controller installation sheet for
SLC wiring specifications.
•Each terminal on the module is limited to a single
conductor.
•Only personality codes 13, 14, 20, and 21 support two-
wire smoke detectors.
•Test resistors are supplied with the GSA-UM to prevent
trouble signals on unused circuits during installation.
When connecting field wires, remove the test resistors and
install a UL/ULC Listed 47 kΩEOLR at the end of the
circuit.
Riser notes
•For maximum line impedance, refer to the installation
manual for the fire alarm panel. Maximum circuit
capacitance is 0.1 µF.
•If the riser is used for more than one notification zone,
install in accordance with the survivability from attack by
fire requirements in NFPA 72 National Fire Alarm and
Signaling Code.
Two-wire smoke detector notes
•A maximum of 15 GSA-UM modules per circuit can be
configured to support two-wire smoke detectors
(personality codes 13, 14, 20, and 21). However, if a
Signature Series IM module or Signature Series detector
with an isolator base (IB) is installed on the SLC, only 7
GSA-UM modules may be configured to support two-wire
smoke detectors.
•Use compatible smoke detectors. See the control panel
compatibility list for type and quantity.
•Polarity at terminals is shown in the supervisory condition.
Connect as shown in the diagram. (Polarity reverses on
alarm.)
•IDC wiring is Style B (Class B) or Style D (Class A).
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections using the appropriate figure
below for the desired function (personality code).

4 / 7 P/N P-047550-1816-EN • REV 007 • ISS 21SEP17
Figure 3: Class B initiating device circuit (personality codes 1, 2, 3, 4)
3 2 1 JP1
(4)
+(5)
+
(6)
(1)
(3)
(1)
(1) 47 kΩ EOL resistor (PN EOL-47) used for Class B only
(2) Input 2: Typical NO initiating device
(3) Input 1: Typical NO initiating device
(4) Maximum 10 VDC at 350 µA
(5) Signaling line circuit (SLC) to next device
(6) Signaling line circuit (SLC) from previous device, power-limited
and supervised
Figure 4: Form C dry contact relay (personality code 8)
++
NO
NC
C
3 2 1 JP1
(1)(2)(3)
(7)(8)
(4)
(6)
(5)
(1) GSA-UM must be installed in the same room as the device it
controls
(2) Power-limited unless connected to a nonpower-limited source. If
the source is nonpower-limited, eliminate the power-limited mark
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be
capable of handling fault current from nonpower-limited source.
—or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.4 mm) space or by a nonconductive sleeve or nonconductive
barrier from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(3) The relay function is programmable
(4) Normally open
(5) Normally closed
(6) Common
(7) Signaling line circuit (SLC) to next device
(8) Signaling line circuit (SLC) from previous device, power-limited
and supervised

P/N P-047550-1816-EN • REV 007 • ISS 21SEP17 5 / 7
Figure 5: Class A initiating device circuit (personality codes 9, 10, 11, 12)
2 1 JP1
3
+(5)
+
(6)
(1) Input 1: Typical NO initiating device
(2) Maximum 10 VDC at 350 µA
(3) Maximum 12.5 Ω resistance per wire for Class A configurations.
(4) Supervised and power-limited unless connected to a nonpower-
limited source. If the source is nonpower-limited, eliminate the
power-limited mark and maintain a minimum of 0.25 in.
(6.4 mm) space from power-limited wiring. For other mounting
methods, see enclosure and bracket installation sheets to
maintain separation of power-limited and nonpower-limited
wiring. The wire size must be capable of handling fault current
from nonpower-limited source.
—or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.4 mm) space or by a nonconductive sleeve or nonconductive
barrier from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(5) Signaling line circuit (SLC) to next device
(6) Signaling line circuit (SLC) from previous device, power-limited
and supervised
Figure 6: Two-wire smoke detectors and initiating devices (personality codes 13, 14, 20, 21)
3 2 1 JP1
(9)
+(7)
+
(8)
(5)
+
-
+
-(4)
(4)
(1)(2)
(3)
(6)
(1) Class A two-wire smoke circuit
(2) Maximum 12.5 Ω resistance per wire for Class A configurations
(3) Class B two-wire smoke circuit
(4) Not allowed with personality codes 14 and 21
(5) UL/ULC Listed 15 kΩ EOLR (PN EOL-15) for Class B only
(6) Class B smoke detector power (24 VDC) from Signature
controller, SMK, or 2-SMK
(7) Signaling line circuit (SLC) to next device
(8) Signaling line circuit (SLC) from previous device, power-limited
and supervised
(9) UL/ULC Listed 22 kΩ EOLR (PN EOL-22) for Class A only

6 / 7 P/N P-047550-1816-EN • REV 007 • ISS 21SEP17
Figure 7: Class A or B notification appliance circuit (personality codes 15, 16)
3 2 1 JP1
(11)(12)(13)
+
+
+
+
(8)
(7)
(10)(9)
(1)(3)(4)(5)
(2)(3)(4)(5)
-
+
-+
-
+
(12)
(1) Class A notification appliance circuit
(2) Class B notification appliance circuit
(3) Signal polarity shown when the circuit is normal. Polarity
reverses when the circuit is active.
(4) Use twisted pair wires for speaker circuits. All other circuit types
use untwisted pair.
(5) Supervised and power-limited unless connected to a nonpower-
limited source. If the source is nonpower-limited, eliminate the
power-limited mark and maintain a minimum of 0.25 in.
(6.4 mm) space from power-limited wiring. For other mounting
methods, see enclosure and bracket installation sheets to
maintain separation of power-limited and nonpower-limited
wiring. The wire size must be capable of handling fault current
from nonpower-limited source.
—or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.4 mm) space or by a nonconductive sleeve or nonconductive
barrier from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(6) 47 kΩ EOLR (P/N EOL-47) used for Class B only
(7) Signaling line circuit (SLC) from previous device, power-limited
and supervised
(8) Signaling line circuit (SLC) to next device
(9) Audio riser (from previous device)
(10) Audio riser (to next device)
(11) Power-limited regulated, power supply listed for fire protective
signaling use
(12) Use twisted pair wires for audio riser. All other riser types use
untwisted pair.
(13) If using horns while connected to a compatible fire alarm control
panel that does not produce a temporal pattern, a CDR-3 bell
coder must be used to comply with ANSI S3.41.This module
does not provide signal synchronization.
Specifications
Operating voltage range
15.20 to 19.95 VDC
Current
See
Table 2 on page 7
Output ratings (special
applications)
24 VDC
25 VRMS audio
70 VRMS audio
End-of-Line Resistor
Circuit capacitance
2 A
50 W
35 W
47 kΩ, UL/ULC listed
0.1 µF max.
Initiating device circuit (IDC)
Circuit resistance
Circuit capacitance
Alarm current
Operating voltage
50 Ω max. (25 Ω per wire)
0.1 µF max.
17 mA max.
16.0 to 24.0 VDC
Maximum line impedance
Refer to the fire alarm panel
installation manual
Ground fault impedance
10 kΩ
Compatible smoke detectors
Refer to the fire alarm panel
compatibility list.
Two-wire smoke ripple voltage
2 VAC
EOLR part numbers
15 kΩ
22 kΩ
47 kΩ
EOL-15
EOL-22
EOL-47
Circuit designation
Signaling line circuit
Notification line circuit
Initiating device circuit
Telephone riser circuit
Class A, Style 6 or Class B, Style 4
Class A, Style Z or Class B, Style Y
Class A, Style D
Class B, Style 4
Contact ratings (pilot duty)
24 VDC at 2 A
120 VAC at 0.5 A
Contact type
Form C, programmable
Compatible electrical boxes
2-1/2 in. (64 mm) deep double-gang
box;
4 in. square box, 1-1/2 in. (38 mm)
deep, with a double-gang cover
Wire size
12 to 18 AWG wire (0.75 to 2.5 mm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH
Storage Temperature Range
−4 to 140°F (−20 to 60°C)

P/N P-047550-1816-EN • REV 007 • ISS 21SEP17 7 / 7
Regulatory information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired operation.
North American
standards
UL864, CAN/ULC-S527
Table 2: Personality code characteristics
Personality code
Mode of operation
Standby current
Activated current
EOL resistor
1, 2, 3, 4
Class B initiating device circuit
458 µA
700 µA
47 kΩ
8
Form C dry contact relay
127 µA
120 µA
N/A
9, 10, 11, 12
Class A initiating device circuit
307 µA
450 µA
N/A
13, 14, 20, 21
Two-wire smoke detectors and initiating devices
3.1 mA
(from 3rd wire)
N/A
Class A: 22 kΩ
Class B: 15 kΩ
N/A
First UM module to go into alarm (Class A or B)
N/A
12 mA smoke detector
17 mA contact closure
N/A
N/A
Each subsequent UM to go into alarm
N/A
100 µA (from data line)
N/A
15, 16
Class A or B notification appliance circuit
317 µA
140 µA
Class A: N/A
Class B: 47 kΩ
Contact information
For contact information, see www.edwardsfiresafety.com.
Table of contents
Other Kidde Control Unit manuals

Kidde
Kidde GSA-REL Product manual

Kidde
Kidde FX-IDC1A Assembly instructions

Kidde
Kidde CTM City Tie Assembly instructions

Kidde
Kidde FX-IDCWS Assembly instructions

Kidde
Kidde ARIES User manual

Kidde
Kidde GSA-CC1 Assembly instructions

Kidde
Kidde FX-2WIRE Assembly instructions

Kidde
Kidde Alarmline II User manual

Kidde
Kidde AEGIS User manual

Kidde
Kidde AEGIS 84-732001-001 User manual
Popular Control Unit manuals by other brands

Tektronix
Tektronix ECO8000 Series user manual

Emerson
Emerson Fisher TBX instruction manual

Carel
Carel E5V instructions

Valve Concepts
Valve Concepts 3200 Installation, operation and maintenance manual

Academy Audio
Academy Audio Hi-End MUSES user manual

ADLINK Technology
ADLINK Technology USB-7230 quick start guide