manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Kidde
  6. •
  7. Control Unit
  8. •
  9. Kidde CTM City Tie Assembly instructions

Kidde CTM City Tie Assembly instructions

Other Kidde Control Unit manuals

Kidde GSA-CC1 Assembly instructions

Kidde

Kidde GSA-CC1 Assembly instructions

Kidde FX-2WIRE Assembly instructions

Kidde

Kidde FX-2WIRE Assembly instructions

Kidde FX-IDC1A Assembly instructions

Kidde

Kidde FX-IDC1A Assembly instructions

Kidde AEGIS 84-732001-001 User manual

Kidde

Kidde AEGIS 84-732001-001 User manual

Kidde CO120X User manual

Kidde

Kidde CO120X User manual

Kidde AEGIS User manual

Kidde

Kidde AEGIS User manual

Kidde ARIES User manual

Kidde

Kidde ARIES User manual

Kidde Alarmline II User manual

Kidde

Kidde Alarmline II User manual

Kidde GSA-REL Product manual

Kidde

Kidde GSA-REL Product manual

Kidde GSA-UM Assembly instructions

Kidde

Kidde GSA-UM Assembly instructions

Kidde FX-IDCWS Assembly instructions

Kidde

Kidde FX-IDCWS Assembly instructions

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

P/N 3101025-EN • REV 03 • ISS 16NOV15 1 / 2
CTM City Tie Module
Installation Sheet
Description
The CTM City Tie Module provides a single municipal box connection
for activating a local energy type master box connected to a public fire
alarm reporting system.
Installation
Install the CTM in accordance with NFPA 70 National Electrical Code.
WARNING: This device will not operate without electrical power. As
fires frequently cause power interruptions, we suggest you discuss
further safeguards with your fire protection specialist.
The CTM is shipped from the factory as an assembled unit; it contains
no user-serviceable parts and should not be disassembled.
For more information, refer to the technical reference manual listed
inside the control panel door.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground
faults.
2. Make all wiring connections as shown in the wiring diagram. See
Figure 1.
3. Using the 4-24 × 1/2 in (13 mm) self-tapping screw provided,
mount the wall plate to the module.
4. Using the two 6-32 × 1/2 in (13 mm) machine screws provided,
mount the module to the electrical box.
Wiring
Wire the CTM to a dedicated notification appliance circuit (NAC) as in
Figure 1 on page 2. Do not install other notification appliances on the
same circuit.
Specifications
Voltage
24 VDC nom.
Current
Standby
Alarm
20 mA
300 mA, max.
Ground fault impedance
0 Ω
Wire size
12 to 18 AWG (0.75 to 2.5 sq mm)
Mounting
North American 2-1/2 in (64 mm) deep
1-gang box
Municipal box connection
Wire resistance:
Trip current:
26 Ω
200 mA into a 14.5 Ω coil
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Contact information
For contact information, see www.edwardsfiresafety.com.
© 2015 Walter Kidde Portable Equipment, Inc.
All rights reserved.
12
3
4
21
firealarmresources.com
2 / 2 P/N 3101025-EN • REV 03 • ISS 16NOV15
Figure 1: CTM installation wiring diagram
[1] Power-limited and supervised for opens, shorts, and ground faults
[2] Nonpower-limited and supervised for opens and ground faults only.
26 Ω, max. 4.4 A, max.
[3] Use end-of-line resistor value required by the notification appliance
circuit
[4] NAC output signal must be compatible with the input rating of the
local energy type master box.
21
1234
+
– ActiveNormal
Public fire alarm
reporting system
Local energy type
master box
+
–
+
– +
–
EOLR [3]
ActiveNormal
From dedicated notification
appliance circuit [4]
Compatible electrical box
CTM
Wall plate
Screws
14.5 Ω
trip coil
[1]
[2]
firealarmresources.com