KMC Controls AppStat User manual

Applicable models
This installation sheet applies to AppStat controllers
for fan coil units. The model numbers for these
models end with "0001". Additional information for
the controllers can be found in the document
Installation, Operation and Application Guide for the
AppStat which is available on the KMC partners web
site.
Illustration 1—Fan Coil Unit models
BAC-4 _ _ _ CW0001
1 3-speed fan, On/off valves
2 3-speed fan, Modulating valves
7Modulating fan, ON/Off valves
8 Modulating fan, Modulating Valves
0 Without humidity
2 With humidity
0 Without motion
2 With motion
Planning for motion sensing
For models with a motion sensor mount the AppStat
on a wall that will have an unobstructed view of the
typical traffic in the coverage area. When choosing a
location, do not install the sensor in the following
areas.
Behind curtains or other obstructions
In locations that will expose it to sunlight or heat
sources
Near a heating or cooling inlet or outlet.
Illustration 2—Typical motion sensing coverage area
The effective detection range is approximately 10
meters or 33 feet. Factors that may reduce the range
include:
The difference between the surface temperature
of the object and the background temperature of
the room is too small.
Object movement in a direct line toward the
sensor.
Very slow or very fast object movement.
Obstructions as shown in the illustration Typical
motion sensing coverage area on page 1.
False detections may be triggered by:
The temperature inside the detection range
suddenly changes because of the entry of cold or
warm air from an air-conditioning or heating
unit.
The sensor being directly exposed to sunlight, an
incandescent light, or other source of far-infrared
rays.
Small animal movement.
Mounting the AppStat
For the most accurate performance, install the
AppStat on an inside wall where it can sense the
average room temperature. Avoid locations with
direct sunlight, heat sources, windows, air vents,
and air circulation or obstructions such as curtains,
furniture, etc.
The AppStat must not be:
Mounted on an exterior wall.
Mounted on or near an object with large a
thermal mass such as a concrete block wall.
Blocked from normal air circulation by
obstructions.
Exposed to heat sources such as lights,
computers, copiers, or coffee makers, or to direct
sunlight at any time of the day.
Exposed to drafts from windows, diffusers, or
returns.
AppStat For Fan Coil Units
BAC-4000 Series BACnet Controllers
Installation Guide
AppStat For Fan Coil Units 1 Installation Guide
AppStat For Fan Coil Units 2 Installation Guide
Exposed to air flow through connecting conduits
or empty spaces behind walls.
For models with motion sensing, see the topic,
Planning for motion sensing.
Rough-in preparation
Complete rough-in wiring at each location before
mounting an AppStat. This includes the following
steps.
Install the supplied mounting base directly to a
wall, a vertical electrical box, or a box with a wall
plate kit.
Routing the connecting cable or cables from the
AppStat to the equipment it is controlling.
If required, install an appropriate wall plate kit.
Block leaks and airflow from conduits with
plumber’s putty or similar material.
If replacing an existing thermostat, label existing
wires for reference when removing the existing
thermostat.
Illustration 3—AppStat mounting base details
A
5.12 in.
130 mm
3.50 in.
89 mm
Inputs and
network
Power and outputs
Installing the AppStat
To install the controller on a mounting base, do the
following:
1. Turn the Allen screw in the base of the sensor
clockwise until it clears the case.
Turn clockwise to remove
from base.
2. Swing the AppStat away from the mounting base
to remove it.
3. Route wiring for the AppStat through the
mounting base.
4. Position the base with the embossed UP toward
the ceiling and fasten it directly to a vertical 2x4
inch electrical box. For horizontal boxes or 4x4
applications, use a wall plate kit. See Installation
accessories on page 4 for part numbers.
5. Connect the wires for the AppStat to the
terminals in the mounting base.
6. Place the top of the sensor over the top of the
mounting base and swing it down over the Allen
screw bracket. Be careful not to pinch any wiring.
7. Turn the Allen screw counterclockwise until it
backs out of the mounting base and engages the
case.
Turn counterclockwise
until the screw engages
the base.
Caution
To prevent mounting screw heads from
touching the circuit board in the
controller, use only the mounting
screws supplied by KMC Controls.
Using screws other than the type
supplied may damage the AppStat.
Connecting inputs
The inputs for the AppStat are configured for
specific functions and do not require set up in the
field. Not all inputs are required for every model or
application.
Illustration 4—FCUinputs
Remote Space Temp.
Water Source Temp.
Discharge Air Temp.
N.C. Fan Status
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Remote space temperature sensor (optional)
Connect a 10kΩ, TypeII thermistor temperature
sensor to the remote space temperature (RS) input
and ground (GND) terminals. The input includes
AppStat For Fan Coil Units 3 Installation Guide
the internal pull-up resistor. An STE-6011W10
sensor is suitable for this application. Follow the
instructions supplied with the sensor for
installation.
When a remote space temperature input is
connected to the AppStat, the remote temperature is
used instead of the internal temperature sensor.
Fan status switch (optional)
Connect a Normally Closed Fan Status switch to the
Discharge Air Temperature (DAT) input and ground
(GND) terminals. The input includes the internal
pull-up resistor. A CSE-1102 differential pressure
switch is suitable for this application. Follow the
instructions supplied with the switch for
installation.
Water temperature sensor
Connect a 10kΩ, Type III thermistor temperature
probe to the water temperature (WST) input. The
input includes the internal pull-up resistor. An
STE-1455 sensor is suitable for this application.
Follow the instructions supplied with the sensor for
installation.
Note: The water temperature sensor is a required
input sensor for 2-pipe fancoil units.
Discharge air temperature
Connect a 10kΩ, Type III thermistor temperature
probe to the discharge air temperature (DAT) input.
The input includes the internal pull-up resistor. An
STE-1405 sensor is suitable for this application.
Follow the instructions supplied with the sensor for
installation.
Connecting outputs
The AppStat outputs are model dependent and are
configured for specific applications.
No field programming or set up is required or
possible.
Depending on model and application, the
AppStat outputs are designed for either 24
voltAC or 0-10 voltDC loads.
The outputs may represent analog or digital
signals.
Caution
Improperly connecting loads or
equipment to output terminals may
damage the equipment. Connect only
as shown in the following diagrams or
application drawings.
Illustration 5—FCU output terminals
0-10VDC
0-10VDC
0-10VDC
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
24 VAC
24VAC
24VAC
24VAC
24VAC
24VAC
Connecting power
The AppStat requires an external, 24 volt, AC power
source. Use the following guidelines when choosing
and wiring transformers.
Use only a Class-2 transformer of the
appropriate size to supply power.
KMC Controls recommends powering the
AppStat from a dedicated controls transformer.
Connect the transformer’s neutral lead to the
COM terminal.
Connect the AC phase lead to the 24VAC
terminal.
Power is applied to the controller when the
transformer is powered.
See Installation accessories on page 4 for a list of
transformers available from KMC Controls, Inc.
Illustration 6—Wiring for AppStat power
24 VAC
Class-2
Controls
transformer
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
AppStat For Fan Coil Units 4 919-019-01B
Maintenance
Remove dust as necessary from the holes in the top
and bottom. Clean the display with soft, damp cloth
and mild soap.
Specifications
AppStat specifications are subject to change without
notice.
Supply Voltage 24 volts AC (–15%, +20%),
50-60 Hz, 12 VA,
Class 2 only
Inputs 0–12 volts DC with internal 10kΩ
pull-up resistors
Relay outputs SPST, 24 volts, 1 amp AC or DC
Maximum for all relay outputs is
3 amps
Analog outputs Short protected 10mA 0–12 VDC
Environmental
limits
Operating 34 to 125° F (1.1 to
51.6° C)
Shipping –40 to 140° F
(–40 to 60° C)
Humidity 0 to 95% RH
(non-condensing)
Regulatory UL 916 Energy Management
Equipment
FCC Class B, Part 15, Subpart B
and complies with Canadian
ICES-003 Class B
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation.
Installation accessories
The following accessories are available from KMC
Controls, Inc.
XEE-6111-040 Single-hub 120 volt power
transformer
XEE-6112-040 Dual-hub 120 volt power
transformer
XEE-6311-075 120/240/277/480VAC, 24 VAC, 75 VA
transformer
HMO-10000W White mounting plate kit for retrofit
on horizontal boxes or 4 x 4 handy
boxes
Additional resources
The latest support files are always available on the
KMC Controls web site.
For detailed specifications, installation, operating ,
application, and system integration information, see
The Installation, Operation, and Application Guide
for AppStat.
For additional specifications information, see the
BAC-4000 AppStat Data Sheet.
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice. KMC
Controls, Inc. makes no representations or
warranties with respect to this document. In no
event shall KMC Controls, Inc. be liable for any
damages, direct or incidental, arising out of or
related to the use of this document.
KMC Controls, Inc.
P.O. Box 497
19476 Industrial Drive
New Paris, IN 46553
U.S.A.
TEL: 1.574.831.5250
FAX: 1.574.831.5252
E-mail: info@kmccontrols.com

Other KMC Controls Controllers manuals

KMC Controls CSC-1001 User manual

KMC Controls

KMC Controls CSC-1001 User manual

KMC Controls BAC-7302 Operating instructions

KMC Controls

KMC Controls BAC-7302 Operating instructions

KMC Controls CEE-3009 User manual

KMC Controls

KMC Controls CEE-3009 User manual

KMC Controls FlexStat BAC-120063CW-ZEC Operator's manual

KMC Controls

KMC Controls FlexStat BAC-120063CW-ZEC Operator's manual

KMC Controls KMDigital KMD-5290E Operating instructions

KMC Controls

KMC Controls KMDigital KMD-5290E Operating instructions

KMC Controls BAC-9300 Series User manual

KMC Controls

KMC Controls BAC-9300 Series User manual

KMC Controls SimplyVAV BAC-8001 User guide

KMC Controls

KMC Controls SimplyVAV BAC-8001 User guide

KMC Controls KMD-7001 Original operating instructions

KMC Controls

KMC Controls KMD-7001 Original operating instructions

KMC Controls CSC 3000 Series User guide

KMC Controls

KMC Controls CSC 3000 Series User guide

KMC Controls MCP-1160 Series User manual

KMC Controls

KMC Controls MCP-1160 Series User manual

KMC Controls CSC 3000 Series User guide

KMC Controls

KMC Controls CSC 3000 Series User guide

KMC Controls CSP-4702 User manual

KMC Controls

KMC Controls CSP-4702 User manual

KMC Controls BAC-4000 series User guide

KMC Controls

KMC Controls BAC-4000 series User guide

KMC Controls CSC-2000 Series User manual

KMC Controls

KMC Controls CSC-2000 Series User manual

KMC Controls MEP-4201 User manual

KMC Controls

KMC Controls MEP-4201 User manual

KMC Controls MEP-46 Q Series User manual

KMC Controls

KMC Controls MEP-46 Q Series User manual

KMC Controls MEP-3001 Operating instructions

KMC Controls

KMC Controls MEP-3001 Operating instructions

KMC Controls MEP-1500 Series User manual

KMC Controls

KMC Controls MEP-1500 Series User manual

KMC Controls FlexStat BAC-12 63 Series User manual

KMC Controls

KMC Controls FlexStat BAC-12 63 Series User manual

KMC Controls SimplyVAV BAC-8001 User manual

KMC Controls

KMC Controls SimplyVAV BAC-8001 User manual

KMC Controls KMD-5205 Operating instructions

KMC Controls

KMC Controls KMD-5205 Operating instructions

KMC Controls KMD-5831 Original operating instructions

KMC Controls

KMC Controls KMD-5831 Original operating instructions

KMC Controls KMD-5210 Operating instructions

KMC Controls

KMC Controls KMD-5210 Operating instructions

KMC Controls CSC 3000 Series User guide

KMC Controls

KMC Controls CSC 3000 Series User guide

Popular Controllers manuals by other brands

FLYGT FPC100 Installation and user manual

FLYGT

FLYGT FPC100 Installation and user manual

Phoenix Contact ILC 330 user manual

Phoenix Contact

Phoenix Contact ILC 330 user manual

ICP DAS USA ALM-06-WF user manual

ICP DAS USA

ICP DAS USA ALM-06-WF user manual

THOMSON MEC 310 - APLLICATION NOTES EXTERNAL I-O... Application notes

THOMSON

THOMSON MEC 310 - APLLICATION NOTES EXTERNAL I-O... Application notes

emicol STORM ST101 2HP user manual

emicol

emicol STORM ST101 2HP user manual

Securimax smart-vent colourtouch user manual

Securimax

Securimax smart-vent colourtouch user manual

Autogrow MultiGrow installation guide

Autogrow

Autogrow MultiGrow installation guide

Conrad Electronic KW-9015 operating instructions

Conrad Electronic

Conrad Electronic KW-9015 operating instructions

Sensus 496 Installation and maintenance instructions

Sensus

Sensus 496 Installation and maintenance instructions

ADVATEK LIGHTING PixLite E4-S Mk3 quick start guide

ADVATEK LIGHTING

ADVATEK LIGHTING PixLite E4-S Mk3 quick start guide

UNIPRODO UNI SAUNA C04 user manual

UNIPRODO

UNIPRODO UNI SAUNA C04 user manual

EVERSPRING AN194 quick start guide

EVERSPRING

EVERSPRING AN194 quick start guide

Ascon tecnologic Z31Y operating instructions

Ascon tecnologic

Ascon tecnologic Z31Y operating instructions

TRIAC FR Series Installation & maintenance manual

TRIAC

TRIAC FR Series Installation & maintenance manual

Lightware RAP-B511-EU user manual

Lightware

Lightware RAP-B511-EU user manual

Komfovent C5 Electrical installation and Operation Manual

Komfovent

Komfovent C5 Electrical installation and Operation Manual

Elitech STC-1000Pro TH quick start guide

Elitech

Elitech STC-1000Pro TH quick start guide

Mitsubishi FX2NC-485ADP manual

Mitsubishi

Mitsubishi FX2NC-485ADP manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.