DEVICE DESCRIPTION 2
9
OPTIBAR DP 7060
www.krohne.com07/2021 - 4004333703 - AD OPTIBAR 7060 Ex ia R03 en
The intrinsically safe circuits are galvanically isolated from parts which can be grounded.
The metallic parts of OPTIBAR DP 7060 VGK7*A/W/V C/H/0 are electrically connected with the
ground terminals.
For applications requiring equipment category 1G or 1/2G, the intrinsically safe supply and
signal circuits must correspond to protection level ia.
OPTIBAR DP 7060 VGK7*A/W/V C/H/0 with integrated electronics Z (4…20 mA),
H (4…20 mA/HART®) or A (4…20 mA/HART® with SIL qualification), version with double
chamber housing D, W or R
Supply and signal circuit:
(Terminals 1[+], 2[-] in "Ex-i" terminal
compartment)
In protection type intrinsic safety Ex ia IIC/IIB
Only for connection to a certified, intrinsically safe circuit
Maximum values
•Ui : 30 V
•Ii : 131 mA
•Pi : 983 mW
The effective inner capacitance Ci is negligibly small.
In the version with permanently mounted connection cable,
Ci wire/wire = 150 pF/m and
Ci wire/shield = 270 pF/m must be taken into account.
The effective inner inductance Li is Li 10 H. In the version
with permanently mounted connection cable,
Li = 0.62 H/m must be taken into account additionally.
Table 2-4: Electrical data for OPTIBAR DP 7060 with integrated electronics Z, H or A, version with double chamber
housing D, W or R
Intrinsically safe circuit for the display and adjustment module
OPTIBAR DP 7060 VGK7*A/W/V C/H/0 with integrated electronics Z (4…20 mA),
H (4…20 mA/HART®), A (4…20 mA/HART® with SIL qualification), F (Foundation Fieldbus) or P
(Profibus PA), version with single chamber housing A, K, V or 8
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
electronics compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
Table 2-5: Intrinsically safe circuit for the display and adjustment module OPTIBAR DP 7060 with integrated electronics
Z, H A, F or P, version with single chamber housing A, K, V or 8
Intrinsically safe circuit for the display and adjustment module
OPTIBAR DP 7060 VGK7*A/W/V C/H/0 with integrated electronics Z (4…20 mA),
H (4…20 mA/HART®), A (4…20 mA/HART® with SIL qualification), F (Foundation Fieldbus) or P
(Profibus PA), version with double chamber housing D, W or R
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
terminal compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
and circuit for the display and
adjustment module: (spring contacts in
the "Ex-i" electronics compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
Table 2-6: Intrinsically safe circuit for the display and adjustment module OPTIBAR DP 7060 with integrated electronics
Z, H, A, F or P, version with double chamber housing D, W or R