KStar UDC9100 Series User manual

All rights reserved.
The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network functions,
smart appearance, complying with EMC and safety standards, The UPS meets the
world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.

1
Table of Contents
1. Important Safety Warning ...........................................................................................................2
1-1 Transportation...................................................................................................................2
1-2 Preparation ........................................................................................................................2
1-3 Installation .........................................................................................................................2
1-4 Operation ...........................................................................................................................3
1-5 Maintenance, service and faults......................................................................................3
1-6 Symbols used in this guide .............................................................................................4
2. Installation and setup..................................................................................................................4
2-1 Unpack checking...............................................................................................................4
2-2 Real panel view .................................................................................................................4
2-3 LCD control panel.............................................................................................................6
2-4 Setup the UPS....................................................................................................................6
3. Operations ....................................................................................................................................8
3-1 Button operation ...............................................................................................................8
3-2 LCD display........................................................................................................................9
3-3 UPS setting...................................................................................................................... 11
3-4 Operating Mode Description..........................................................................................14
3-5 Operational Status and Mode(s)....................................................................................14
3-6 Alarm or Fault reference code.......................................................................................15
4. Troubleshooting.........................................................................................................................16
5. Storage and Maintenance .........................................................................................................17
6. Specification...............................................................................................................................18

2
1. Important Safety Warning
Important safety instructions –Save these instructions
Please comply with all warnings and operating instructions in this manual strictly. Save
this manual properly and read carefully the following instructions before installing the unit.
Do not operate this unit before reading through all safety information and operating
instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and
relative laws, otherwise it will result in personnel injury or equipment damage. Safety
instructions in this manual act as a supplementary for the local safety instructions. Our
company will not assume the liability that caused by disobeyingsafety instructions.
1-1Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1-2Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.

3
1-4Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is
not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
1-5Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary
when working with batteries:
-remove wristwatches, rings and other metal objects
-use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.

4
1-6Symbols used in this guide
WARNING!
Riskofelectricshock
CAUTION!
Readthisinformationtoavoidequipmentdamage
2. Installationand setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
2-1Unpack checking
Don’t lean the UPS when moving it out from the packaging
Check the appearance to see if the UPS is damaged or not during the transportation,
do not switch on the UPS if any damage found. Please contact the dealer right away.
Check the accessories according to the packing list and contact the dealer in case of
missing parts.
2-2Real panel view
1KVA(S):
1KVA(H):

5
2KVA(S):
2KVA(H)/3KVA(H)
3KVA(S):

6
1. AC input
2. Network /Fax/Modem Surge Protection(option)
3. Input circuit breaker
4. EPO(option)
5. USB communication port(option)
6. RS-232 communication port
7. SNMP intelligent slot (option)
8. Output receptacles
9. Battery Terminal
10. Output Terminal
2-3LCD control panel
LCD control panel introduction
(1)LED(from top to bottom: “alarm”, “bypass”, “battery”, “inverter”)(2)LCD display(3)
Selectbutton:enter to next item(4)Off button (5)On button
2-4Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
For 200/208/220/230/240VAC models: The power cord is supplied in the UPS
package.

7
Step 2: UPS output connection
For socket-type outputs, simply connect devices to the outlets.
For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2power cords for 3KVA
(200/208/220/230/240VAC models).
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 3 Communication connection
Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
installing either SNMP or Relay card in the UPS, it will provide advanced
communication and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully
configure UPS shutdown. You may insert provided CD into CD-ROM to install the
monitoring software.
Step 6: External battery connection
If your UPS is not including batteries. Please connect external batteries as below
chart.

8
3. Operations
3-1Button operation
Button
Function
ON Button
Turn on the UPS: Press and hold ON button for at least 2
seconds to turn on the UPS.
Down key: Press this button to display next selection in
UPS setting mode.
Exit setting mode:Press this button to confirm seletion
and exit setting mode when LCD display the last selection
in UPS setting mode.
OFF Button
Turn off the UPS: Press and hold this button at least 2
seconds to turn off the UPS in battery mode. UPS will be
in standby mode under power normal or transfer to
Bypass mode if the Bypass enable setting by pressing this
button.
Switch to bypass mode: When the main power is
normal, press and hold this button for 2 seconds. Then
UPS will enter to bypass mode. This action will be
ineffective when the input voltage is out of acceptable
range.
Up key: Press this button to display previous selection in
UPS setting mode.
Select/Mute
Button
Switch LCD message: Press this button to change the
LCD message for input voltage, input frequency, battery
voltage, output voltage and output frequency etc.
Mute the alarm: When the UPS is on battery mode, press
and hold this button for at least 2 seconds to disable or
enable the alarm system. But it’s not applied to the
situations when warnings or errors occur.
Switch to UPS self-test mode: Press and hold this
button for 2 seconds to enter UPS self-testing while in AC
mode.
OFF + Select
Button
Setting mode: Press and hold this button for 5 seconds to
enter UPS setting mode.

9
3-2LCD display
There are 8 interfaces available in the LCD display
Item
Interface Description
Content Displayed
01
Input voltage
02
Battery voltage
03
Output voltage

10
04
Load
05
Temperature
(Environment Temperature
& Heatsink Temperature)
06
Firmware Version & UPS
model.

11
07
CODE
(Operational status and
mode)
08
Alarm Code(Warming
Message)
All alarm codes are
present when abnormal
behavior(s) occur(s)
09
The charging status can
also be shown on the
screen as below while
the charger is on.
3-3UPS setting
The setting fuction is controled by 3 buttons (Enter/Select,Off/up ▲, On/down▼): Enter
+Off/up ▲---goes into the setting page,Enter --- value adjustment; Off ▲ & On ▼---for choosing
different pages.
After the UPS turn ON, press buttons & ▲ for 5seconds and then goes into the setting interface
page.
Note: Figure at left corner is the page number of the setting pages.

12
Item
Settings
Content Displayed
01
Mode setting
Press select button to change the
setting (ECO or NOR).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.
02
Output voltage setting
Press select button to change the
setting (100,110,115,120,127 or
200,208,220, 230, 240).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.
03
Frequency setting
Press select button to change the
setting (50 or 60Hz).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.
04
Battery capacity setting
Press select button to change the
setting (Battery capacity range is
1-200Ah).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.

13
05
Bypass voltage upper limit
setting
Press select button to change the
setting(The bypass voltage upper limit
range is 230-264Vac ).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.
06
Bypass voltage lower limit
setting
Press select button to change the
setting(The bypass voltage lower limit
range is 170-220Vac).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to select the
next setting.
07
Mute setting
Press select buttonto change
thesetting(ON or OFF).
Press UP button ▲ to select the
previous setting.
Press DOWN ▼button to save and
exit the setup.

14
3-4Operating Mode Description
Operating mode
Description
Display
Online mode
When the input voltage is
within acceptable range,
UPS will provide pure and
stable AC power to output.
The UPS will also charge
the battery at online mode.
Inverter led light
ECO mode
Energy saving mode:
When the input voltage is
within voltage regulation
range, UPS will bypass
voltage to output for
energy saving.
Bypass led light
Battery mode
When the input voltage is
beyond the acceptable
range or power failure and
alarm is sounding every 4
second, UPS will backup
power from battery.
Battery led light
Standby mode
UPS is powered off and no
output supply power, but
still can charge batteries.
All LEDs turn off
Bypass mode
When input voltage is
within acceptable range
but UPS is overload, UPS
will enter bypass mode or
bypass mode can be set
by front panel.
Bypass led light
3-5Operational Status and Mode(s)
item
Content Displayed
1
Initialized
2
Standby Mode
3
No Output
4
Bypass Mode
5
Utility Mode
6
Battery Mode
7
Battery Self-diagnostics
8
Inverter is starting up
9
ECO Mode
10
EPO Mode
11
Maintenance Bypass Mode
12
Fault Mode

15
3-6Alarm or Fault reference code
Event log
UPS Alarm Warning
Buzzer
LED
1
Rectifier Fault
Beep continuously
Fault LED lit
2
Inverter fault(Including Inverter
bridge is shorted)
Beep continuously
Fault LED lit
9
Fan fault
Beep continuously
Fault LED lit
12
Selftest fault
Beep continuously
Fault LED lit
13
Battery Charger fault
Beep continuously
Fault LED lit
15
DC Bus over voltage
Beep continuously
Fault LED lit
16
DC Bus below voltage
Beep continuously
Fault LED lit
17
DC bus unbalance
Beep continuously
Fault LED lit
18
Soft start failed
Beep continuously
Fault LED lit
19
UPS Inside Over Temperature
Twice per second
Fault LED lit
20
Heatsink Over Temperature
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Input current limit
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV or BPS LED
blinking
33
No battery
Once per second
Battery LED blinking
34
Battery under voltage
Once per second
Battery LED blinking
35
Battery low pre-warning
Once per second
Battery LED blinking
36
Over load time out
Once per 2 seconds
Fault LED blinking
37
DC component over limit.
Once per 2 seconds
INV LED blinking
39
Mains volt.Abnormal
Once per 2 seconds
Battery LED lit
40
Mains freq. abnormal
Once per 2 seconds
Battery LED lit
41
Bypass Not Available
BPS LED blinking
42
Bypass unable to trace
BPS LED blinking
43
Inverter on invalid
44
Not at Inverter side

16
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptom
Possible cause
Remedy
No indication and alarm even
though the mains is normal.
The AC input power is not
connected well.
Check if input power cord
firmly connected to the
mains.
The AC input is connected to
the UPS output.
Plug AC input power cord to
AC input correctly.
Alarm code is shown as“33” and
battery led blinking.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
Alarm code is shown as “26”
and battery led blinking.
Battery voltage is too high or
the charger is fault.
Contact your dealer.
Alarm code is shown as “34”
and battery led blinking
Battery voltage is too low or
the charger is fault.
Contact your dealer.
Alarm code is shown as “32”
and INV or BYPASS led
blinking.
UPS is overload
Remove excess loads from
UPS output.
Alarm code is shown as “29”
and FAULT led light.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.
Alarm code is shown as “9” and
FAULT led light.
Fan fault.
Contact your dealer.
Alarm code is shown as “01,02,
15,16,17,18”
A UPS internal fault has
occurred.
Contact your dealer.
Battery backup time is
shorter than nominal value
Batteries are not fully
charged
Charge the batteries for at
least 5 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to
replace the battery.

17
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case,
please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it
to your dealer in the replacement battery packing material.

18
6. Specification
MODEL
1KVA(S)
1KVA(H)-
B
1KVA(H)
2KVA(S)
2KVA(H)-
B
2KVA(H)
3KVA(S)
3KVA(H)-
B
3KVA(H)
PHASE
Single phase with ground
Capacity (VA/Watts)
1000VA / 900W
2000VA / 1800W
3000VA / 2700W
INPUT
Nominal voltage
200/208/220/230/240VAC
Operating
voltage range
Low
line
transf
er
160Vac±5% @100%-80% load;
140Vac±5% @80%-70% load;
120Vac±5% @70%-60% load;
110Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
Low
line
come
back
175Vac±5% @100%-80% load;
155Vac±5% @80%-70% load;
135Vac±5% @70%-60% load;
125Vac±5% @60%-0% load;
(Ambient Temp. <35℃)
High
line
transf
er
300Vac ±5%
High
line
come
back
290Vac ±5%
Operating frequency
range
40-70Hz
Power factor
0.99@100% load(Nominal Input Voltage)
Bypass voltage range
Bypass high voltage point
230-264: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
Bypass low voltage point
170-220: setting the low voltage point in LCD from 170Vac to 220Vac. (Default: 170Vac)
Generator input
Support
OUTPUT
Output voltage
200/208/220/230/240Vac
Power factor
0.9
Voltage regulation
±1%
Frequency
Line
Mode
(synchro
nized
range)
47-53Hz or 57-63Hz
Bat. Mode
(50/60±0.1)Hz
Crest factor
3:1
Harmonic distortion
(THDv)
≤3% THDwith linear load
≤6% THD with non linear load
Waveform
Pure Sinewave
Transfer
time
AC
mode
<->Batt.
mode
Zero
Inverter
<->
bypass
4ms(Typical)
Efficiency
88%(AC mode)
85%(DC mode)
92%(AC mode)
88%(DC mode)
92%(AC mode)
90%(DC mode)
BATTERY

19
Battery Type
12V9A
H
depends on the
capacity of
external
batteries
12V9A
H
depends on the
capacity of external
batteries
12V9AH
depends on the
capacity of
external
batteries
Numbers
2
2
3
4
4
6
6
6
8
Backup time
Long run unit depends on the capacity of external batteries
Typical recharge
time(standard modle)
4 hours recover to 90% capacity (Typical)
Charging voltage
27.4
VDC
±1%
27.4
VDC
±1%
41.0
VDC
±1%
54.7
VDC
±1%
54.7
VDC
±1%
82.1
VDC
±1%
82.1
VDC
±1%
82.1
VDC
±1%
109.4
VDC
±1%
Charge current
1A
12A max
1A
12A max
1A
12A max
SYSTEM FEATURES
Overload
@35℃
Line
Mode
Battery
Mode
Ambient Temp.<35℃
105%~110%: UPS transfer to bypass after 10minuteswhen the utility is normal
110%~130%: UPS transfer to bypass after 1minute when the utility is normal
130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
>150%: UPS transfer to bypass immediately when the utility is normal
35℃<Ambient Temp.<40℃
105%~110%: UPS transfer to bypass after 1minute when the utility is normal
110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal
>130%: UPS transfer to bypass immediately when the utility is normal
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
EPO (optional)
Shut down UPS immediately
Audible & Visual alarms
Line Failure, Battery Low, Overload, System Fault
Comunication interface
USB(or RS232), SNMPcard(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature
0℃~40℃
Storage temperature
-25℃~55℃
Humidity range
20-90 % RH @ 0- 40°C (non-condensing)
Altitude
< 1000m
Noise level
Less than 50dBA at 1 Meter
PHYSICAL
Dimension W×H×D
(mm)
144*209*293
144*209*399
191*337*460
144*209*399
Net Weight (kg)
8.9
4.2
16.2
6.3
24.8
6.5
STANDARDS
Safety
IEC/EN62040-1,IEC/EN60950-1
EMC
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
* Derate to 80% of capacity when the output voltage is adjusted to 200/208VAC
** Product specifications are subject to change without further notice.
Table of contents
Other KStar UPS manuals

KStar
KStar YDC9300-0.8 User manual

KStar
KStar YMK3300 Series User manual

KStar
KStar GP800 User manual

KStar
KStar UDC9101S One User manual

KStar
KStar 600 User manual

KStar
KStar MEMO PLUS RT II (MP9100RTII-0.9) 1-3K User manual

KStar
KStar 6kVA User manual

KStar
KStar UDC9101RTS User manual

KStar
KStar YMK3300-200k User manual

KStar
KStar YDC9300-B User manual