Auto ON
DIP 7 OFF
for Relay 1
DIP 8 OFF
for Relay 2
UNIT DESCRIPTION AND OPERATION
The UW Ultrasonic Wall Switch sensors employ 40kHz ultrasonic tech no logy in
a single-gang wall switch unit. The UW sensor can turn a load ON, and hold it
ON as long as the sensor detects occ u p a n c y. After no movement is detec ted for
the selected time delay, the lights switch OFF. A “walk-through” mode can turn
lights OFF after only 3 minutes, if no activity is detect ed after 30 seco n d s
fo l low ing an occupancy detect io n .
The UW-100 has one relay and one ON/OFF button. The UW-200 co n tains two
relays and two ON/OFF buttons to allow co n t rol of one or two load s
in de p en de n tl y. Pre ssing a button tog g les the stat e of the co r responding re la y.
UW sensors co n tain a light level sensor. If adequate daylight is present, the
sensor holds the load OFF until light levels drop, even if the area is occupied. In
the UW-200, light level only affects the load on Relay 2. Users can override this
function by pres sing the ON/OFF button. See Light Level Adjustm e nt .
Turning The Load ON
The relays are prog rammed independently for either Auto ON or Manual ON. In
either mode, the load can be turned ON or OFF using the ON/OFF butto n .
Load turns ON and OFF auto m a t i cal ly based on occu pa n cy. If the
load is turned OFF manually, it stays OFF until 5 minutes afte r
the last occupancy detection, at which time it reverts to Auto ON
mode. This prevents the load from turning ON auto ma t i ca l ly
af ter it was delibera tely turned OFF. Pressing the button to turn
lights ON returns the sensor to Auto ON mode.
** UW-100: Switch 8 is not used. UW-200: Switch 8 default is ON to co mp ly
with CA Energy Commission Title 24 bi-level switching req u ire m e nt s .
Time Delays
The UW sensor holds the load ON until no motion is dete c ted for the selecte d
time delay. Select the time delay using DIP switch settings. The sensor
au to m a t i ca l ly sets the time delay when SmartSet is enabled. In the UW-200,
both relays use the same delay.
Manual ON
DIP 7 ON
for Relay 1
DIP 8** ON
for Relay 2
O ccupants must press the ON/OFF button to turn ON the lo ad .
The sensor keeps the load ON until no motion is detec ted for the
se le c ted time delay. There is a 30 second re - retrigger delay. If
o ccupancy re - t r i g g e rs during the delay, the sensor turns the
load back ON. After the re-trigger delay elapses the ON/OFF
b u t ton must be pressed to turn ON the load .
Shading indica tes default operation and switch setting.