CASINGS
The casings shall consist of durable 1.2mm (18 gauge)
galvanised steel reinforced to form a rigid monoque
structure. Alledgestoberadiusedandaccesspanelsto
befixedwitheasyreleaseselfretainingfasteners.
DISCHARGE PLENUM
The discharge plenum shall be wholly lined with Class O
acoustic insulation. The plenum shall be provided with
200mmdiameterspigotsforductconnection.
DRIP TRAY
The drip tray shall be manufactured such that when the
unit is mounted level there shall be a positive fall for the
condensate water to the drain connection from all areas
of the drip tray. There shall be no areas where the water
can collect in pools. The drip tray shall be of single
component construction and be located under the coil
assembly and extend to include the valve pack
arrangement. Thetrayshallbefullyinsulated.
FANS
Double inlet double width fans shall be used, driven by a
motor using cradle type resilient mountings. The fan
impellers shall be 160mm diameter and of 'Tablock'
constructionto ensure good performance and lownoise.
Eachimpellershallbedynamicallybalanced.
MOTORS
Motors shall be single speed permanent split capacitor
type. ThemotorsusedshallcomplywithBS5000Part11
1973(revised1989). Speedcontrolshallbeachievedby
applyingavariable voltage to the motor winding. Motors
aretohavemaintenancefreesealedforlifebearingsand
builtinthermaloverloadprotection.
INSULATION
Dual function thermal and acoustic insulation shall be
usedandshallbetoClass0specification.
COILS
All heat exchangers shall be tested at a minimum of 25
bar pressure. The coils shall be manufactured using
solid drawn copper tubes and aluminium fins. Each coil
shallbefittedwithanairventanddraincock.
COIL CONNECTIONS
AllaretobeBS2871Part1:1971andsuitableforbrazed
and compression fittings. Coil connections shall be at
40mm centres to enable easy fitment of industry
standardwatercontrolvalves.
FILTERS
Standard filters shall be of washable type. They shall
have a performance classification of G2 in accordance
with EN779 (EU2) and flame resistance to DIN 53438:
Class1
CONTROLS
All units shall be fitted with an illuminated On/Off switch
and three speed selector switch. Adjacent to this switch
are two additional switches that provide a fine tuning
capability. Intotalaselectionof 27speedsareavailable
with design settings factory set, and dependant on
transformer tapping connections. The unit is supplied
with a 24 volt AC transformer output to drive controllers
and actuators. The control box shall be of a hinge
arrangementwithasinglescrewaccesstoterminalstrips
forcustomerconnection.
PACKAGING
Unitsshallbesuppliedwithshrink wrappedpackaging to
prevent damage and dust contamination. Units shall be
clearly marked with the model identification and site
reference and supplied with installation instructions.
The units will be despatched on pallets with 5 or 6 units
perpalletdependantonunitsizes.
CERTIFICATION
Units shall be supplied with a CE label designating that
theycomplywithCErequirementsforsafety.
COMPACT WATERSIDE FAN COIL SPECIFICATION