Troubleshooting and fault elimination
Error messages
14
L
EDK82EVXXX EN 2.0
3.2 Error messages at the keypad or in the parameter setting
program Global Drive Control
Keypad PC
1)
Error Cause Remedy
noer
0No fault - -
ccr
71 System fault Strong interferences on control cables Shield control cables
*
Ground or earth loops in the wiring
ce0
*
61 Communication fault to AIF
(configurable in C0126)
Faulty transmission of control commands via AIF Insert the communication module into the hand terminal
ce1
*
62 Communication fault to
CAN-IN1 with Sync control
CAN-IN1 object receives faulty data or
communication is interrupted
•
Plug-in connection - bus module ÙCheck FIF
•
Check transmitter
•
Increase monitoring time under C0357/1 if necessary
ce2
*
63 Communication error to
CAN-IN2
CAN-IN2 object receives faulty data or
communication is interrupted
•
Plug-in connection - bus module ÙCheck FIF
•
Check transmitter
•
Increase monitoring time under C0357/2 if necessary
ce3
*
64 Communication error to
CAN-IN1 with event or time
control
CAN-IN1 object receives faulty data or
communication is interrupted
•
Plug-in connection - bus module ÙCheck FIF
•
Check transmitter
•
Increase monitoring time under C0357/3 if necessary
ce4
*
65 BUS-OFF
(many communication faults
occurred)
Controller has received too many incorrect
telegrams via the system bus and has been
disconnected
•
Check whether bus terminator available
•
Check screen contact of the cables
•
Check PE connection
•
Check bus load, if necessary, reduce the baud rate
ce5
*
66 CAN Time-Out
(configurable in C0126)
For remote parameter setting via system bus
(C0370):
Slave does not answer. Communication monitoring
time exceeded.
•
Check system bus wiring
•
Check system bus configuration
For operation with application I/O:
Faulty parameter setting of parameter set
changeover
In all parameter sets the signal ”parameter set
changeover” (C0410/13, C0410/14) must be combined
with the same source
For operation with module in FIF:
Internal fault
Contact Lenze
ce6
*
67 Function module system bus
(CAN) on FIF has set ”Warning”
or ”BUS-OFF”
(configurable in C0126)
CAN controller sets ”Warning” or ”BUS OFF”
•
Check whether bus terminator available
•
Check screen contact of the cables
•
Check PE connection
•
Check bus load, if necessary, reduce the baud rate
ce7
*
68 Communication fault during
remote parameter setting via
system bus (C0370)
(configurable in C0126)
Participant does respond or is not available
•
Check whether bus terminator available
•
Check screen contact of the cables
•
Check PE connection
•
Check bus load, if necessary, reduce the baud rate
For operation with application I/O:
Faulty parameter setting of parameter set
changeover
In all parameter sets the signal ”parameter set
changeover” (C0410/13, C0410/14) must be combined
with the same source
EEr
*
91 External fault (TRIP-SET) A digital input assigned to the TRIP-Set function
has been activated.
Check external encoder
ErP0
...
ErP19
*
-Communication abort between
keypad and basic device
Various Contact Lenze
FAn1
*
95 E82ZMV fan module (only 8200
motec 3 ... 7,5 kW)
Fan module is defect Replace fan module
FAn1
-TRIP or warning configurable
under C0608 Fan module is not connected Connect fan module
Check wiring
H05
*
105 Internal fault Contact Lenze
id1
*
140 Faulty parameter identification Motor not connected Connect motor
LP1
*
32 Fault in motor phase
(is displayed if C0597 = 1)
•
Failure of one/several motor phase(s)
•
Motor current too low
•
Check motor cables
•
Check V
min
boost
LP1
182 Fault in motor phase
(is displayed if C0597 = 2)
•
Connect motor to corresponding power or adapt the
motor under C0599.